SPEC 70118

600V ROYAL® SOOW Cord Control with Black Jacket 90°C. Silicone-Free. MSHA Approved

600 Volt 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation, Heat, Moisture and Oil Resistant Flexible CPE Jacket

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black CPE (Other colors available upon request)

Applications and Features:

Southwire Type SOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 90°C, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • MSHA flame test - P07-KA070018-1MSHA
  • Passes CSA FT2 Flame Test
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE{R} ROYAL{R} CORD XX/C XX AWG ({mm2}) SOOW E46194 MASTER-DESIGN {UL} 600V -40{D}C TO 90{D}C -- {CSA} LL90458 SOOW 600V -40{D}C TO 90{D}C FT2 WATER RESISTANT {NOM}-ANCE -- {MSHA}

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmilmilinchlb/1000ftAmp
    5582358305051851630950.4651348
    5582368306051861630850.4881378
    5582378307051871630800.4881387
    5582388308051881630850.5211627
    57003483100518101630900.5962005
    57003783120518121630900.6172265
    59830283140518141630900.6402535
    570039831605181616301000.6682825
    57004283200518201630950.7393305
    570043832405182416301100.8304094
    571692833005183016301000.8684564
    5582328306061662630900.49416410
    5582318305061652630950.51416210
    5582348308061682630900.5151919
    5582338307061672630900.5642019
    56052683100616102630900.6482716
    560527831206161226301050.6963246
    598305831406161426301100.7273376
    57001883200616202630950.7744066
    560528831606161626301100.7783736
    570019832406162426301100.9195075
    570026833006163026301300.9826475
    55814783050714541451050.65525414
    55814983060714641451050.66432314
    5581508307071474145950.71231212
    55823083080714841451150.73034612
    569994831007141041451100.7704049
    571270831207141241451100.8834719
    569995831407141441451300.9806029
    569997831607141641451301.0166429
    569999832407142441451351.1758808
    570004833007143041451251.33810478
    55810483050812565451000.70929520
    55814483060812665451100.74037920
    5581458307081276545950.74035317
    55814683080812865451100.79642917
    57139783090812965451100.85248317
    569981831008121065451000.89450012
    569982831208121265451301.02963912
    598307831408121465451301.03570412
    569983832008122065451151.20093912
    569987833708123765451301.536156010
    558103830509105104451200.77244424
    569979830609106104451100.83048324
    569980830709107104451150.84051621
    5956628310091010104451301.02973515
    5700068312091012104451301.06784915
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmmmmmmkg/kmAmp
    558235830505185160.762.4111.811998
    558236830605186160.762.1612.402048
    558237830705187160.762.0312.402057
    558238830805188160.762.1613.232417
    5700348310051810160.762.2915.142985
    5700378312051812160.762.2915.673365
    5983028314051814160.762.2916.263775
    5700398316051816160.762.5416.974205
    5700428320051820160.762.4118.774915
    5700438324051824160.762.7921.086094
    5716928330051830160.762.5422.056794
    558232830606166260.762.2912.5524410
    558231830506165260.762.4113.0624110
    558234830806168260.762.2913.082849
    558233830706167260.762.2914.332999
    5605268310061610260.762.2916.464036
    5605278312061612260.762.6717.684826
    5983058314061614260.762.7918.475026
    5700188320061620260.762.4119.666046
    5605288316061616260.762.7919.765556
    5700198324061624260.762.7923.347545
    5700268330061630260.763.3024.949635
    558147830507145411.142.6716.6437814
    558149830607146411.142.6716.8748114
    558150830707147411.142.4118.0846412
    558230830807148411.142.9218.5451512
    5699948310071410411.142.7919.566019
    5712708312071412411.142.7922.437019
    5699958314071414411.143.3024.898969
    5699978316071416411.143.3025.819559
    5699998324071424411.143.4329.8513108
    5700048330071430411.143.1833.9915588
    558104830508125651.142.5418.0143920
    558144830608126651.142.7918.8056420
    558145830708127651.142.4118.8052517
    558146830808128651.142.7920.2263817
    571397830908129651.142.7921.6471917
    5699818310081210651.142.5422.7174412
    5699828312081212651.143.3026.1495112
    5983078314081214651.143.3026.29104812
    5699838320081220651.142.9230.48139712
    5699878337081237651.143.3039.01232210
    5581038305091051041.143.0519.6166124
    5699798306091061041.142.7921.0871924
    5699808307091071041.142.9221.3476821
    59566283100910101041.143.3026.14109415
    57000683120910121041.143.3027.10126315

    Color Code

    # of ConductorColor SequenceTracer# of ConductorColor SequenceTracer
    1Black21OrangeGreen
    2White22BlackWhite/Red
    3Red23WhiteBlack/Red
    4Green24RedBlack/White
    5Orange25GreenBlack/White
    6Blue26OrangeBlack/White
    7WhiteBlack27BlueBlack/White
    8RedBlack28BlackRed/Green
    9GreenBlack29WhiteRed/Green
    10OrangeBlack30RedBlack/Green
    11BlueBlack31GreenBlack/Orange
    12BlackWhite32OrangeBlack/Green
    13RedWhite33BlueWhite/Orange
    14GreenWhite34BlackWhite/Orange
    15BlueWhite35WhiteRed/Orange
    16BlackRed36OrangeWhite/Blue
    17WhiteRed37WhiteRed/Blue
    18OrangeRed38BlackWhite/Green
    19BlueRed39WhiteBlack/Green
    20RedGreen40RedWhite/Green

    Revision: 1.000.000