SPEC 70078

600V SEOPRENE PLUS® SEOOW Cord with Yellow Jacket 105°C. Silicone-Free

600 Volt, 105°C Flexible Cord. Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant, UL / CSA listed.

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Yellow TPE (other colors available upon request)

Applications and Features:

Southwire Type SEOOW Flexible Cords are permitted for indoor and outdoor temporary power uses, portable industrial machinery and compressors, food processing and washdown facilities. Type SEOOW Cords are suitable for use in temperatures between -40°C to maximum 105°C.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Sample Print Legend:

    SOUTHWIRE{R} SEOPRENE PLUS{TM} CORD X/C XX AWG (X.XX{mm2}) SEOOW E46194 {UL} 600V -40{D}C TO 105{D}C -- CSA LL90458 SEOOW 600V -50{D}C TO 105{D}C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    6556621831630600.3636310
    5983351841630600.387758
    6556881622630600.3676113
    6556961632630600.3877713
    6557041642630600.4169310
    6722721652630850.50313110
    5983361424145800.49711118
    6557201434145800.52213518
    6557381444145800.56516414
    6557461226545950.57014925
    6557531236545950.59218525
    6557611246545950.64222920
    655787103104451050.65224430
    655795104104451000.70330124
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    655662183160.761.529.229410
    598335184160.761.529.831128
    655688162260.761.529.329113
    655696163260.761.529.8311513
    655704164260.761.5210.5713810
    672272165260.762.1612.7819510
    598336142411.142.0312.6216518
    655720143411.142.0313.2620118
    655738144411.142.0314.3524414
    655746122651.142.4114.4822225
    655753123651.142.4115.0427525
    655761124651.142.4116.3134120
    6557871031041.142.6716.5636330
    6557951041041.142.5417.8644824

    Color Code

    # of ConductorColor Sequence
    2Black, White
    3Black, White, Green
    4Black, White, Red, Green

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:40 p.m. UTC