SPEC 70070

600V SEOPRENE® SEOOW Cord Control with Black Jacket 105°C. Silicone-Free

600 Volt Cord. 105°C Premium Oil Resistance, Sunlight, Water Resistance and Flame Retardant

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (other colors available upon request)

Applications and Features:

Southwire Type SEOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2020 National Electrical Code. The cable is rated -40°C to 105°C, water, oil, and weather resistant. Southwire Type SEOOW Flexible Cords are designed for extra hard usage on industrial equipment, heavy tools, battery chargers, portable lights, welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Sample Print Legend:

    SOUTHWIRE® SEOPRENE® CORD X/C XX AWG (X.XXmm2) SEOOW E46194 (UL) 600V -40C TO 105C -- CSA LL90458 SEOOW 600V -50C TO 105C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmilmilinchlb/1000ftAmp
    550560222251821630600.3425210
    550561223251831630650.3656410
    551469224251841630600.387748
    569645305051851630850.4621068
    598758306051861630800.4841168
    598728307051871630800.4881247
    598729308051881630800.5171387
    5987303100518101630800.6001705
    5987313120518121630800.6131905
    5987323140518141630800.6402145
    5954873160518161630950.6972555
    598733NA182441301000.8103444
    550634222261622630600.3686313
    550464224261642630600.4169310
    550555305061652630800.49212810
    595375307061672630800.5251549
    562791306061662630850.53314910
    589888308061682630800.5601739
    5987353100616102630800.6382116
    5948893120616122630950.6982596
    5987363140616142630950.7252866
    5987373160616162630950.7573166
    595667NA16246530950.8644425
    550562222271424145800.49711318
    550398223271434145800.52213618
    550399224271444145900.59218014
    598739306071464145950.69024714
    598740307071474145950.69026112
    598741308071484145950.74329812
    5899213100714104145950.8353529
    5504322222812265451050.57015825
    550395223281236545950.60319325
    550397224281246545950.64223120
    5504973050812565451050.70728420
    598745306081266545950.74531620
    598746308081286545950.80437617
    55043122229102104451000.61719630
    55039322329103104451050.65224630
    55039422429104104451000.70330424
    55087530509105104451050.76236324
    59875230709107104451150.84546921
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmmmmmmkg/kmAmp
    55056022225182160.761.528.697710
    55056122325183160.761.659.279510
    55146922425184160.761.529.831108
    56964530505185160.762.1611.731588
    59875830605186160.762.0312.291738
    59872830705187160.762.0312.401857
    59872930805188160.762.0313.132057
    598730310051810160.762.0315.242535
    598731312051812160.762.0315.572835
    598732314051814160.762.0316.263185
    595487316051816160.762.4117.703795
    598733NA1824410.762.5420.575124
    55063422226162260.761.529.359413
    55046422426164260.761.5210.5713810
    55055530506165260.762.0312.5019010
    59537530706167260.762.0313.332299
    56279130606166260.762.1613.5422210
    58988830806168260.762.0314.222579
    598735310061610260.762.0316.213146
    594889312061612260.762.4117.733856
    598736314061614260.762.4118.424266
    598737316061616260.762.4119.234706
    595667NA1624650.762.4121.956585
    55056222227142411.142.0312.6216818
    55039822327143411.142.0313.2620218
    55039922427144411.142.2915.0426814
    59873930607146411.142.4117.5336814
    59874030707147411.142.4117.5338812
    59874130807148411.142.4118.8744312
    589921310071410411.142.4121.215249
    55043222228122651.142.6714.4823525
    55039522328123651.142.4115.3228725
    55039722428124651.142.4116.3134420
    55049730508125651.142.6717.9642320
    59874530608126651.142.4118.9247020
    59874630808128651.142.4120.4256017
    550431222291021041.142.5415.6729230
    550393223291031041.142.6716.5636630
    550394224291041041.142.5417.8645224
    550875305091051041.142.6719.3554024
    598752307091071041.142.9221.4669821

    Color Code

    # of ConductorColor SequenceTracer# of ConductorColor SequenceTracer
    1Black21OrangeGreen
    2White22BlackWhite/Red
    3Red23WhiteBlack/Red
    4Green24RedBlack/White
    5Orange25GreenBlack/White
    6Blue26OrangeBlack/White
    7WhiteBlack27BlueBlack/White
    8RedBlack28BlackRed/Green
    9GreenBlack29WhiteRed/Green
    10OrangeBlack30RedBlack/Green
    11BlueBlack31GreenBlack/Orange
    12BlackWhite32OrangeBlack/Green
    13RedWhite33BlueWhite/Orange
    14GreenWhite34BlackWhite/Orange
    15BlueWhite35WhiteRed/Orange
    16BlackRed36OrangeWhite/Blue
    17WhiteRed37WhiteRed/Blue
    18OrangeRed38BlackWhite/Green
    19BlueRed39WhiteBlack/Green
    20RedGreen40RedWhite/Green

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:40 p.m. UTC