SPEC 70065

300V SEOPRENE® SJEOOW Cord with Black Jacket 105°C. Silicone Free

300 Volt 105°C Flexible Cord. Premium Oil Resistance, Sunlight, Chemical, Water Resistance and Flame Retardant

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant TPE
  3. Filler:Non-wicking polypropylene fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black TPE (Other colors available upon request)

Applications and Features:

Southwire Type SJEOOW Flexible Cords are permitted for indoor and outdoor temporary power uses, portable industrial machinery, compressors, conveyor and automated production equipment. Cords are suitable for use in temperatures between -40°C to maximum 105°C.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® SEOPRENE® CORD X/C XX AWG (X.XXmm2) SJEOOW E46194 (UL) 300V -40C TO 105C -- CSA LL90458 SJEOOW 300V -50C TO 105C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmilmilinchlb/1000ftAmp
    550528232251821630350.2863810
    550445233251831630350.3084710
    550474234251841630300.328587
    550495232261622630300.3104613
    550403233261632630300.3296013
    550435234261642630300.3707810
    550559232271424130300.3406018
    550433233271434130350.3638018
    550401234271444130300.3939915
    550627232281226530500.4109325
    5987550N/A1236530450.42811825
    550396233281236530450.42811425
    550465234281246530450.46815120
    5507672322910210445650.54115830
    5504482332910310445650.57320530
    5506282342910410445650.62826125
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    ^ Color Sequence: Black, Red
    ! White PVC jacket
    ** Not a Federal and Military Specification JC-580B
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmmmmmmkg/kmAmp
    55052823225182160.760.897.265710
    55044523325183160.760.897.827010
    55047423425184160.760.768.33867
    55049523226162260.760.767.876813
    55040323326163260.760.768.368913
    55043523426164260.760.769.4011610
    55055923227142410.760.768.648918
    55043323327143410.760.899.2211918
    55040123427144410.760.769.9814715
    55062723228122650.761.2710.4113825
    5987550N/A123650.761.1410.8717625
    55039623328123650.761.1410.8717025
    55046523428124650.761.1411.8922520
    550767232291021041.141.6513.7423530
    550448233291031041.141.6514.5530530
    550628234291041041.141.6515.9538825
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    ^ Color Sequence: Black, Red
    ! White PVC jacket
    ** Not a Federal and Military Specification JC-580B

    Color Code

    # of ConductorColor Sequence
    2Black, White
    ^2Black, Red
    3Black, White, Green
    4Black, White, Red, Green

    Revision: 3.0.00M