SPEC 70002

600V ROYAL® SOOW Power Cord Non-UL/CSA with Black Jacket 90°C. Silicone-Free. MSHA Approved

600 Volt, 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, Non UL / Non CSA.

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper fillers
  4. Jacket:Black CPE (Other colors available upon request)

Applications and Features:

Southwire Royal® Non UL/Non CSA SOOW cord is designed for use with industrial equipment, heavy tools, battery chargers, portable lights and power extensions, suitable for outdoor applications. The cable is rated -40°C to 90°C, sunlight, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • MSHA flame test - P07-KA070018-1MSHA
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® CORD X/C X AWG (X.XXmm2) SOOW 600V -40C TO 90C

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilNo.No.milmilinchlb/1000ftAmp
    5699728222208213345750.61521840
    5580888223208313345750.64528940
    5580938224208413345750.71137732
    55810582247085133451050.83449232
    56997382222162133451000.72133555
    5580928223216313345900.72641855
    5580918224216413345950.80354944
    55816182252165133451100.93770244
    5581378223224313345950.82558970
    55809082242244133451000.95076156
    56997582255245133451551.155112156
    55813682232323168451151.090102895
    55808982242324168451301.290132776
    56997682255325168451201.373167176
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilNo.No.mmmmmmkg/kmAmp
    569972822220821331.141.9115.6232440
    558088822320831331.141.9116.3843040
    558093822420841331.141.9118.0656132
    558105822470851331.142.6721.1873232
    569973822221621331.142.5418.3149955
    558092822321631331.142.2918.4462255
    558091822421641331.142.4120.4081744
    558161822521651331.142.7923.80104544
    558137822322431331.142.4120.9687770
    558090822422441331.142.5424.13113256
    569975822552451331.143.9429.34166856
    558136822323231681.142.9227.69153095
    558089822423241681.143.3032.77197576
    569976822553251681.143.0534.87248776

    Color Code

    # of ConductorColor Sequence
    2Black, White
    3Black, White, Green
    4Black, White, Red, Green
    5Black, White, Red, Green, Orange

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:40 p.m. UTC