SPEC 45307

4/C CU 600V XLPE XHHW-2 AIA PVC Power Cable With Ground. Silicone Free

Type MC Power Cable 600Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE MASTER-DESIGN {UL} 4/C (XX AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90{D}C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGinchmilinchlb/1000ftlb/1000ft
    TBA870.141450.2311 x 100.781500.881237462
    574460670.177450.2671 x 80.865500.965378647
    TBA470.225450.3151 x 80.984501.084571873
    580730270.282450.3721 x 61.113501.2139091274
    TBA1190.322550.4321 x 61.267501.36711231553
    8902291/0190.361550.4711 x 61.352501.45213991902
    TBA2/0190.405550.5151 x 61.568601.68817392294
    TBA3/0190.456550.5661 x 41.691601.81122212860
    5626054/0190.512550.6221 x 41.785601.90527693525
    557959250370.558650.6881 x 41.94602.0632484144
    551452350370.661650.7911 x 32.179602.29945305699
    TBA350370.661650.7911 x 2/02.236602.35645265452
    605410500370.789650.9191 x 22.484752.63464437839
    563407600610.865801.0251 x 22.798752.94876919279
    672989600610.865801.0251 x 4/02.798802.96481459680
    TBA750610.968801.1281 x 13.051853.221960711175
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA86.15280.6530.7860.052324044
    57446066.78390.4110.4950.051445260
    TBA47.513350.2580.310.048566876
    58073028.421230.1620.1950.0457692104
    TBA19.526780.1280.1540.04688104116
    8902291/010.133790.1020.1220.044100120136
    TBA2/011.842590.0810.0970.043116140156
    TBA3/012.653690.0640.0780.042132160180
    5626054/013.367710.0510.0620.041156184208
    55795925014.480000.0430.0530.041172204232
    55145235016.0112000.0310.0390.04208248280
    TBA35016.4112000.0310.0390.040208248280
    60541050018.4160000.0220.0290.039256304344
    56340760020.6192000.0180.0250.039280336380
    67298960020.7192000.0180.0250.039280336380
    TBA75022.5240000.0140.0220.038320380428
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.

    Revision: 3.0.00C