SPEC 45302

CU 600/1000V XLPE Insulation ARMOR-X® Thermoplastic LSZH-TP Jacket. XHHW-2 VFD Cable

Type MC-HL Power Cable 600 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Thermoplastic Solonon® Low Smoke Zero Halogen (LSZH-TP) Jacket with Bare CU Ground

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:ARMOR-X® Continuous Corrugated Welded Armor
  7. Overall Jacket:Thermoplastic Solonon® Low Smoke Zero Halogen (LSZH-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Cables with 3 ground wires suitable for VFD application.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE{R} MASTER-DESIGN {UL} ARMOR-X® TYPE MC-HL 3/C XXX AWG (XX{mm2}) CU XHHW-2 GW 3 X X AWG 90{D}C SOLONON{R} JACKET -40{D}C ST1 SUN.RES. DIR. BUR. FOR CT USE 600V IEEE1202/FT4 -- VFD -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessDiameter Over InsulationGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilinchNo. x AWGinchmilinchlb/1000ftlb/1000ft
    TBA8370.141450.2313 x 140.750500.85019271453
    TBA6370.177450.2673 x 120.840500.94030679603
    6476994370.225450.3151 x 80.920501.02043988718
    6779332370.282450.3711 x 61.020501.1206991211045
    TBA1/03190.361550.4713 x 101.350501.45010832141704
    TBA2/03190.405550.5153 x 101.480501.58013402342024
    6726732/03190.405550.5223 x 101.470601.59013422342011
    5866743/03190.456550.5703 x 81.540601.66017242452427
    TBA4/03190.512550.6223 x 81.670601.79021302663000
    TBA2503370.558650.6883 x 81.845601.96524902993494
    TBA3503370.661650.7913 x 62.200602.32034663534668
    TBA5003370.789650.9193 x 62.430752.58049183916429
    TBA7503610.968801.1283 x 42.880753.03073194659264
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA835.93960.6530.7860.052405055
    TBA636.56290.4110.4950.051556575
    647699437.110010.2580.3100.048708595
    677933237.815920.1620.1950.04595115130
    TBA1/0310.125340.1020.1220.044125150170
    TBA2/0311.031940.0810.0970.043145175195
    6726732/0311.131940.0810.0970.043145175195
    5866743/0311.640270.0640.0780.042165200225
    TBA4/0312.550780.0510.0620.041195230260
    TBA250313.760000.0430.0530.041215255290
    TBA350316.284000.0310.0390.040260310350
    TBA500318.0100000.0220.0290.039320380430
    TBA750321.2100000.0140.0220.038400475535
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.007

    Updated On: Sept. 28, 2023, 7:07 p.m. UTC