SPEC 45262
4/C CU 600V EPR XHHW-2 Thermoplastic CPE-TP Power Cable With Ground
Type TC-ER Power Cable 600Volt Four Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket with 1 Tinned CU Ground. VW-1 rated

Construction:
- Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
- Grounding Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 rated
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} ROYAL{TM} E75755 MASTER-DESIGN {UL} XXX AWG (XX.X{mm2}) 4/C EPR/CPE TYPE TC-ER EPR XHHW-2 CDRS GW 1 X 6 AWG 600V 90{D}C DRY/ 90{D}C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90{D}C USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
591982 | 8 | 7 | 0.141 | 45 | 1 x 10 | 60 | 0.724 | 238 | 385 |
591984 | 6 | 7 | 0.177 | 45 | 1 x 8 | 60 | 0.816 | 378 | 553 |
591986 | 4 | 7 | 0.225 | 45 | 1 x 8 | 80 | 0.936 | 572 | 802 |
591988 | 2 | 7 | 0.282 | 45 | 1 x 6 | 80 | 1.123 | 909 | 1214 |
591990 | 1 | 19 | 0.322 | 55 | 1 x 6 | 80 | 1.279 | 1125 | 1527 |
591992 | 1/0 | 19 | 0.361 | 55 | 1 x 6 | 80 | 1.357 | 1399 | 1828 |
591994 | 2/0 | 19 | 0.405 | 55 | 1 x 6 | 80 | 1.464 | 1742 | 2210 |
TBA | 3/0 | 19 | 0.456 | 55 | 1 x 4 | 80 | 1.541 | 2221 | 2636 |
591997 | 4/0 | 19 | 0.512 | 55 | 1 x 4 | 110 | 1.740 | 2769 | 3369 |
591999 | 250 | 37 | 0.558 | 65 | 1 x 4 | 110 | 1.939 | 3248 | 4006 |
592001 | 350 | 37 | 0.661 | 65 | 1 x 3 | 110 | 2.202 | 4530 | 5420 |
592003 | 500 | 37 | 0.789 | 65 | 1 x 2 | 110 | 2.464 | 6443 | 7386 |
646849 | 600 | 61 | 0.865 | 80 | 1 x 2 | 140 | 2.790 | 7691 | 9439 |
TBA | 750 | 61 | 0.968 | 80 | 1 x 1 | 140 | 3.021 | 9607 | 10952 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
591982 | 8 | 2.8 | 528 | 0.653 | 0.786 | 0.052 | 32 | 40 | 44 |
591984 | 6 | 3.2 | 839 | 0.411 | 0.495 | 0.051 | 44 | 52 | 60 |
591986 | 4 | 3.7 | 1335 | 0.258 | 0.31 | 0.048 | 56 | 68 | 76 |
591988 | 2 | 5.6 | 2123 | 0.162 | 0.195 | 0.045 | 76 | 92 | 104 |
591990 | 1 | 6.3 | 2678 | 0.128 | 0.154 | 0.046 | 88 | 104 | 116 |
591992 | 1/0 | 6.7 | 3379 | 0.102 | 0.122 | 0.044 | 100 | 120 | 136 |
591994 | 2/0 | 7.3 | 4259 | 0.081 | 0.097 | 0.043 | 116 | 140 | 156 |
TBA | 3/0 | 7.7 | 5369 | 0.064 | 0.078 | 0.042 | 132 | 160 | 180 |
591997 | 4/0 | 8.7 | 6771 | 0.051 | 0.062 | 0.041 | 156 | 184 | 208 |
591999 | 250 | 9.6 | 8000 | 0.043 | 0.053 | 0.041 | 172 | 204 | 232 |
592001 | 350 | 13.2 | 11200 | 0.031 | 0.039 | 0.040 | 208 | 248 | 280 |
592003 | 500 | 14.7 | 16000 | 0.022 | 0.029 | 0.039 | 256 | 304 | 344 |
646849 | 600 | 16.7 | 19200 | 0.018 | 0.025 | 0.039 | 280 | 336 | 380 |
TBA | 750 | 18.1 | 24000 | 0.014 | 0.022 | 0.038 | 320 | 380 | 428 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C