SPEC 45258

CU 600/1000V XLPE Insulation PVC Jacket. XHHW-2

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX KCMIL (XXX{mm2}) CU 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    557009870.141451 x 10600.755238403
    560102670.177451 x 8800.902378613
    556993470.225451 x 8800.918572804
    554303270.282451 x 6801.0469091185
    6020111190.322551 x 6801.20211251496
    5544361/0190.361551 x 6801.29913991754
    5569852/0190.405551 x 6801.42017422144
    6020373/0190.456551 x 4801.52122232693
    5544444/0190.512551 x 41101.72127693425
    602052250370.558651 x 41101.84232484003
    675713350370.661651 x 11102.08146275524
    644547350370.661651 x 31102.09345305437
    602078350370.661651 x 31102.09545305351
    TBA350370.661651 x 31102.14645265276
    672237500370.789651 x 1/01102.38265667656
    675711500370.789651 x 2/01102.38266527742
    672235500370.789651 x 11102.38264987588
    554469500370.789651 x 21102.38264437427
    672240500370.789651 x 4/01102.51168968014
    675706600610.865801 x 1/01402.75678139251
    649649600610.865801 x 4/01402.90381449621
    675708600610.865801 x 2501402.90382639741
    570961750610.968801 x 11403.003961611307
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    55700983.05280.6530.7860.052324044
    56010263.68390.4110.4950.051445260
    55699343.613350.2580.3100.048566876
    55430325.221230.1620.1950.0457692104
    60201116.026780.1280.1540.04688104116
    5544361/06.433790.1020.1220.044100120136
    5569852/07.142590.0810.0970.043116140156
    6020373/07.653690.0640.0780.042132160180
    5544444/08.667710.0510.0620.041156184208
    6020522509.280000.0430.0530.041172204232
    67571335012.4112000.0310.0390.040208248280
    64454735012.5112000.0310.0390.040208248280
    60207835012.5112000.0310.0390.040208248280
    TBA35012.8112000.0310.0390.040208248280
    67223750014.2160000.0220.0290.039256304344
    67571150014.2160000.0220.0290.039256304344
    67223550014.2160000.0220.0290.039256304344
    55446950014.2160000.0220.0290.039256304344
    67224050015.0160000.0220.0290.039256304344
    67570660016.5192000.0180.0250.039280336380
    64964960017.4192000.0180.0250.039280336380
    67570860017.4192000.0180.0250.039280336380
    57096175018.0240000.0140.0220.038320380428
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.

    Revision: 3.0.00C