SPEC 45254

CU 600/1000V XLPE Insulation Thermoplastic LSZH-TP. XHHW-2

Type TC-ER Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Bare CU Ground.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU SOLONON{R} 90{D}C JACKET SUN RES OIL RES I FOR DIRECT BURIAL 600V
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    5615688370.141451 x 10 GG450.700186339
    5615676370.177451 x 8 GG450.795297480
    5513782370.282451 x 6600.980702979
    TBA13190.322551 x 6801.1058631179
    TBA1/03190.361551 x 6801.18910671416
    5615642/03190.405551 x 6801.30213261719
    5658153/03190.456551 x 4801.40616992132
    9597184/03190.512551 x 4801.53121092615
    TBA2503370.558651 x 4801.65824663041
    TBA3503370.661651 x 31101.94034364233
    5649385003370.789651 x 21102.18348845745
    5523625003370.789653 x 61102.23349235965
    TBA7503610.968801 x 11102.66872708572
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    561568832.83960.6530.7860.052405055
    561567633.16290.4110.4950.051556575
    551378233.915920.1620.1950.04595115130
    TBA135.520080.1280.1540.046110130145
    TBA1/035.925340.1020.1220.044125150170
    5615642/036.531940.0810.0970.043145175195
    5658153/037.040270.0640.0780.042165200225
    9597184/037.650780.0510.0620.041195230260
    TBA25038.260000.0430.0530.041215255290
    TBA35039.784000.0310.0390.040260310350
    564938500313.0100000.0220.0290.039320380430
    552362500313.3100000.0220.0290.039320380430
    TBA750316.0100000.0140.0220.038400475535
    *Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.002

    Updated On: Aug. 18, 2023, 2:40 p.m. UTC