SPEC 45251
3/C CU 600V PVC THHN PVC Jacket Power Cable With Ground. Silicone Free
Type TC-ER Power Cable 600Volt Three Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XX AWG (XX.X{mm2}) CU 3 CDRS TYPE TC-ER THHN OR THWN CDRS GW 1 X X AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
443390◊ | 8 | 7 | 0.141 | 30 | 1 x 10 GG | 60 | 0.640 | 186 | 306 |
443408◊ | 6 | 7 | 0.177 | 30 | 1 x 8 GG | 60 | 0.734 | 297 | 451 |
443416◊ | 4 | 7 | 0.225 | 40 | 1 x 8 | 60 | 0.804 | 441 | 618 |
443424◊ | 2 | 7 | 0.282 | 40 | 1 x 6 | 80 | 0.986 | 702 | 971 |
443432◊ | 1 | 19 | 0.322 | 50 | 1 x 6 | 80 | 1.116 | 864 | 1180 |
443440◊ | 1/0 | 19 | 0.361 | 50 | 1 x 6 | 80 | 1.183 | 1069 | 1406 |
443457◊ | 2/0 | 19 | 0.405 | 50 | 1 x 6 | 80 | 1.278 | 1326 | 1689 |
443465◊ | 3/0 | 19 | 0.456 | 50 | 1 x 4 | 80 | 1.386 | 1699 | 2100 |
443473◊ | 4/0 | 19 | 0.512 | 50 | 1 x 4 | 80 | 1.481 | 2109 | 2603 |
443481◊ | 250 | 37 | 0.558 | 60 | 1 x 4 | 80 | 1.659 | 2469 | 3091 |
443507◊ | 350 | 37 | 0.661 | 60 | 1 x 3 | 110 | 1.941 | 3438 | 4186 |
443523◊ | 500 | 37 | 0.789 | 60 | 1 x 2 | 110 | 2.168 | 4884 | 5733 |
679965 | 600 | 61 | 0.865 | 70 | 1 x 1/0 | 110 | 2.431 | 5942 | 7074 |
604777 | 600 | 61 | 0.865 | 70 | 1 x 2 | 110 | 2.431 | 5820 | 6850 |
602094◊ | 750 | 61 | 0.968 | 70 | 1 x 1 | 110 | 2.652 | 7277 | 8635 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ Brown, orange, and yellow insulation color
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
443390◊ | 8 | 2.5 | 396 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
443408◊ | 6 | 2.9 | 629 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
443416◊ | 4 | 3.2 | 1001 | 0.258 | 0.31 | 0.048 | 70 | 85 | 95 |
443424◊ | 2 | 3.9 | 1592 | 0.162 | 0.195 | 0.045 | 95 | 115 | 130 |
443432◊ | 1 | 5.5 | 2008 | 0.128 | 0.154 | 0.046 | 110 | 130 | 145 |
443440◊ | 1/0 | 5.9 | 2534 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
443457◊ | 2/0 | 6.3 | 3194 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
443465◊ | 3/0 | 6.9 | 4027 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
443473◊ | 4/0 | 7.4 | 5078 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
443481◊ | 250 | 8.2 | 6000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
443507◊ | 350 | 9.7 | 8400 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
443523◊ | 500 | 13.0 | 12000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
679965 | 600 | 14.5 | 14400 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
604777 | 600 | 14.5 | 14400 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
602094◊ | 750 | 15.9 | 18000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C