SPEC 45201
2/C 3/C or 4/C CU 600V XLPE XHHW-2 Aluminum Interlocked Armor PVC Control Cable With Ground
Type MC Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground

Construction:
- Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
- Grounding Conductor:Class B compressed stranded bare copper
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE MASTER-DESIGN {UL} X/C (XX AWG) X.XXmm2 CU XX MILS XLP 600 VOLTS GW 1 X XX AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90{D}C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||
14 AWG | |||||||||||||||||||
555413* | 14 | 3 | 7 | 0.070 | 30 | 1 x 10 | 0.480 | 50 | 0.580 | 54 | 175 | 2.630 | 3.288 | 4.1 | 15 | 15 | 15 | ||
TBA | 14 | 4 | 7 | 0.070 | 30 | 1 x 10 | 0.530 | 50 | 0.630 | 66 | 204 | 2.630 | 3.288 | 4.4 | 14 | 15 | 15 | ||
12 AWG | |||||||||||||||||||
578426 | 12 | 2 | 7 | 0.087 | 30 | 1 x 12 | 0.528 | 50 | 0.628 | 61 | 203 | 1.660 | 2.075 | 4.4 | 20 | 20 | 20 | ||
555149 | 12 | 3 | 7 | 0.087 | 30 | 1 x 12 | 0.565 | 50 | 0.665 | 81 | 239 | 1.660 | 2.075 | 4.7 | 16 | 20 | 20 | ||
573502 | 12 | 4 | 7 | 0.087 | 30 | 1 x 12 | 0.607 | 50 | 0.707 | 102 | 277 | 1.660 | 2.075 | 5.0 | 16 | 20 | 20 | ||
10 AWG | |||||||||||||||||||
568457 | 10 | 2 | 7 | 0.111 | 30 | 1 x 10 | 0.579 | 50 | 0.679 | 97 | 257 | 1.040 | 1.300 | 4.8 | 30 | 30 | 30 | ||
568458 | 10 | 3 | 7 | 0.111 | 30 | 1 x 10 | 0.622 | 50 | 0.722 | 130 | 308 | 1.040 | 1.300 | 5.1 | 24 | 28 | 30 | ||
573500 | 10 | 4 | 7 | 0.111 | 30 | 1 x 10 | 0.671 | 50 | 0.771 | 162 | 362 | 1.040 | 1.300 | 5.4 | 24 | 28 | 30 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
* Green insulated ground.
* Green insulated ground.
Revision: 3.0.00C