SPEC 45105
3/C or 4/C CU 600V XLPE XHHW-2 LSZH-TP Control Cable With Green Ground
Type TC-ER Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Insulated Green CU Ground, Control Cable Conductor Identification Method 1 Table 2

Construction:
- Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
- Grounding Conductor:Class B compressed stranded copper with green insulation
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Table 1 – Physical and Electrical Data
Cond. Size | Cond. Number | Cond. Strands | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | mil | No. x AWG | mil | inch | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
14 AWG | |||||||||||||||||||
14 | 3 | 7 | 30 | 1 x 14 | 45 | 0.370 | 96 | 2.631 | 3.170 | 1.4 | 15 | 20 | 25 | ||||||
14 | 4 | 7 | 30 | 1 x 14 | 45 | 0.404 | 113 | 2.631 | 3.170 | 1.6 | 12 | 16 | 20 | ||||||
12 AWG | |||||||||||||||||||
12 | 3 | 7 | 30 | 1 x 12 | 45 | 0.409 | 136 | 1.662 | 2.002 | 1.6 | 20 | 25 | 30 | ||||||
12 | 4 | 7 | 30 | 1 x 12 | 45 | 0.448 | 159 | 1.662 | 2.002 | 1.7 | 16 | 20 | 24 | ||||||
10 AWG | |||||||||||||||||||
10 | 3 | 7 | 30 | 1 x 10 | 45 | 0.463 | 196 | 1.040 | 1.253 | 1.8 | 30 | 35 | 40 | ||||||
10 | 4 | 7 | 30 | 1 x 10 | 45 | 0.508 | 230 | 1.040 | 1.253 | 2.0 | 24 | 28 | 32 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C