SPEC 45059
Multi-Conductor TCU 600V EPR XHHW-2 Thermoplastic CPE-TP Control Cable Color Method 1 Table 1
Type TC-ER Control Cable 600Volt Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. VW-1 rated

Construction:
- Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) XHHW-2, 30 Mils thick for all cable sizes
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} XX AWG (X.XX{mm2}) XX/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 MASTER-DESIGN {UL} 600V 90{D}C DRY/90{D}C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90{D}C USA
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
14 AWG | |||||||||||||||||||
TBA | 14 | 2 | 7 | 30 | 45 | 0.350 | 37 | 78 | 2.631 | 3.170 | 1.4 | 15 | 20 | 25 | |||||
599457 | 14 | 3 | 7 | 30 | 45 | 0.388 | 37 | 86 | 2.631 | 3.170 | 1.5 | 15 | 20 | 25 | |||||
599458 | 14 | 4 | 7 | 30 | 45 | 0.423 | 50 | 107 | 2.631 | 3.170 | 1.6 | 12 | 16 | 20 | |||||
599459 | 14 | 5 | 7 | 30 | 45 | 0.461 | 62 | 129 | 2.631 | 3.170 | 1.8 | 12 | 16 | 20 | |||||
595479 | 14 | 7 | 7 | 30 | 45 | 0.502 | 87 | 170 | 2.631 | 3.170 | 2.0 | 10 | 14 | 17 | |||||
599460 | 14 | 9 | 7 | 30 | 60 | 0.616 | 112 | 232 | 2.631 | 3.170 | 2.4 | 10 | 14 | 17 | |||||
599461 | 14 | 12 | 7 | 30 | 60 | 0.692 | 150 | 299 | 2.631 | 3.170 | 2.7 | 7 | 10 | 12 | |||||
TBA | 14 | 15 | 7 | 30 | 60 | 0.744 | 203 | 357 | 2.631 | 3.170 | 2.9 | 7 | 10 | 12 | |||||
595475 | 14 | 19 | 7 | 30 | 60 | 0.804 | 237 | 434 | 2.631 | 3.170 | 3.2 | 7 | 10 | 12 | |||||
TBA | 14 | 25 | 7 | 30 | 80 | 0.952 | 331 | 590 | 2.631 | 3.170 | 3.8 | 6 | 9 | 11 | |||||
TBA | 14 | 30 | 7 | 30 | 80 | 1.005 | 395 | 688 | 2.631 | 3.170 | 5.0 | 6 | 9 | 11 | |||||
TBA | 14 | 37 | 7 | 30 | 80 | 1.082 | 485 | 824 | 2.631 | 3.170 | 5.4 | 6 | 8 | 10 | |||||
12 AWG | |||||||||||||||||||
595635 | 12 | 2 | 7 | 30 | 45 | 0.466 | 40 | 86 | 1.662 | 2.002 | 1.8 | 20 | 25 | 30 | |||||
595472 | 12 | 3 | 7 | 30 | 45 | 0.466 | 61 | 115 | 1.662 | 2.002 | 1.8 | 20 | 25 | 30 | |||||
595636 | 12 | 4 | 7 | 30 | 45 | 0.466 | 81 | 148 | 1.662 | 2.002 | 1.8 | 16 | 20 | 24 | |||||
595477 | 12 | 12 | 7 | 30 | 60 | 0.466 | 244 | 410 | 1.662 | 2.002 | 1.8 | 10 | 12 | 15 | |||||
592111 | 12 | 5 | 7 | 30 | 45 | 0.543 | 101 | 198 | 1.662 | 2.002 | 2.1 | 16 | 20 | 24 | |||||
TBA | 12 | 7 | 7 | 30 | 60 | 0.576 | 162 | 263 | 1.662 | 2.002 | 2.3 | 14 | 17 | 21 | |||||
596919 | 12 | 9 | 7 | 30 | 60 | 0.589 | 183 | 319 | 1.662 | 2.002 | 2.3 | 14 | 17 | 21 | |||||
TBA | 12 | 15 | 7 | 30 | 80 | 0.869 | 325 | 535 | 1.662 | 2.002 | 3.4 | 10 | 12 | 15 | |||||
TBA | 12 | 19 | 7 | 30 | 80 | 0.912 | 406 | 647 | 1.662 | 2.002 | 3.6 | 10 | 12 | 15 | |||||
TBA | 12 | 25 | 7 | 30 | 80 | 1.060 | 528 | 827 | 1.662 | 2.002 | 5.3 | 9 | 11 | 13 | |||||
TBA | 12 | 30 | 7 | 30 | 80 | 1.120 | 630 | 967 | 1.662 | 2.002 | 5.6 | 9 | 11 | 13 | |||||
TBA | 12 | 37 | 7 | 30 | 80 | 1.208 | 772 | 1164 | 1.662 | 2.002 | 6.0 | 8 | 10 | 12 | |||||
10 AWG | |||||||||||||||||||
595632 | 10 | 2 | 7 | 30 | 45 | 0.466 | 64 | 116 | 1.040 | 1.253 | 1.8 | 30 | 35 | 40 | |||||
645726 | 10 | 12 | 7 | 30 | 80 | 0.466 | 388 | 615 | 1.040 | 1.253 | 1.8 | 15 | 17 | 20 | |||||
595556 | 10 | 3 | 7 | 30 | 45 | 0.478 | 97 | 161 | 1.040 | 1.253 | 1.9 | 30 | 35 | 40 | |||||
595633 | 10 | 4 | 7 | 30 | 45 | 0.556 | 129 | 223 | 1.040 | 1.253 | 2.2 | 24 | 28 | 32 | |||||
TBA | 10 | 5 | 7 | 30 | 60 | 0.599 | 193 | 291 | 1.040 | 1.253 | 2.3 | 24 | 28 | 32 | |||||
TBA | 10 | 7 | 7 | 30 | 60 | 0.651 | 258 | 377 | 1.040 | 1.253 | 2.6 | 21 | 24 | 28 | |||||
TBA | 10 | 9 | 7 | 30 | 60 | 0.756 | 323 | 468 | 1.040 | 1.253 | 3.0 | 21 | 24 | 28 | |||||
TBA | 10 | 15 | 7 | 30 | 80 | 0.986 | 517 | 765 | 1.040 | 1.253 | 3.9 | 15 | 17 | 20 | |||||
TBA | 10 | 19 | 7 | 30 | 80 | 1.037 | 646 | 930 | 1.040 | 1.253 | 5.1 | 15 | 17 | 20 | |||||
TBA | 10 | 25 | 7 | 30 | 80 | 1.210 | 840 | 1193 | 1.040 | 1.253 | 6.0 | 13 | 15 | 18 | |||||
TBA | 10 | 30 | 7 | 30 | 80 | 1.280 | 1002 | 1401 | 1.040 | 1.253 | 6.4 | 13 | 15 | 18 | |||||
TBA | 10 | 37 | 7 | 30 | 80 | 1.383 | 1228 | 1693 | 1.040 | 1.253 | 6.9 | 12 | 14 | 16 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C