SPEC 45054

Multi-Conductor CU 600V XLPE XHHW-2 LSZH-TP Control Cable

Type TC-ER Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2 for cables 14 AWG or larger, 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. 16 AWG wire is made in accordance with UL 66: Fixture Wire.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 66 Fixture Wire
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    For 16 AWG:
    SOUTHWIRE MASTER-DESIGN {UL} AWG XX 7 CDRS TYPE TC-ER XLPE CDRS SOLONON 90C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    For 14 AWG and larger:
    SOUTHWIRE MASTER-DESIGN {UL} AWG XX 7 CDRS TYPE TC-ER XHHW-2 CDRS SOLONON 90C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    14 AWG
    561312142730450.34925672.6313.1701.3152025
    TBA143730450.37050962.6313.1701.4152025
    561313144730450.402511112.6313.1701.6121620
    563383145730450.443641352.6313.1701.7121620
    561314147730450.478891712.6313.1701.9101417
    TBA146730450.492881562.6313.1701.9121620
    TBA148730600.5621142122.6313.1702.2101417
    561315149730600.5871152332.6313.1702.3101417
    5975241410730600.6491272622.6313.1702.571012
    5631941419730600.7742424402.6313.1703.071012
    TBA1420730800.8622674882.6313.1703.471012
    TBA1425730800.9523315902.6313.1703.86911
    TBA1430730801.0053956882.6313.1705.06911
    5746171437730801.07571912092.6313.1705.36810
    12 AWG
    574615122730450.38440891.6622.0021.5202530
    890122123730450.412611211.6622.0021.6202530
    561319124730450.445811521.6622.0021.7162024
    574612125730450.4871011801.6622.0021.9162024
    574613127730600.5671422571.6622.0022.2141721
    TBA126730600.5761422371.6622.0022.3162024
    TBA128730600.6211822941.6622.0022.4141721
    TBA129730600.6662033261.6622.0022.6141721
    TBA1210730600.7242233581.6622.0022.8101215
    5746141212730600.7322444111.6622.0022.9101215
    TBA1215730800.8693255351.6622.0023.4101215
    TBA1220730800.9574266791.6622.0023.8101215
    TBA1225730801.0605288271.6622.0025.391113
    TBA1230730801.1206309671.6622.0025.691113
    TBA1237730801.20877211641.6622.0026.081012
    10 AWG
    577144103730450.459971661.0401.2531.8303540
    566720104730450.5021292141.0401.2532.0242832
    TBA105730600.5991932911.0401.2532.3242832
    TBA106730600.6512263381.0401.2532.6242832
    TBA107730600.6512583771.0401.2532.6212428
    TBA108730600.7042904221.0401.2532.8212428
    TBA1010730800.8643555491.0401.2533.4151720
    5746191012730800.8793886291.0401.2533.5151720
    TBA1015730800.9865177651.0401.2533.9151720
    TBA1019730801.0376469301.0401.2535.1151720
    TBA1020730801.0906789771.0401.2535.4151720
    TBA1025730801.21084011931.0401.2536.0131518
    TBA1030730801.280100214011.0401.2536.4131518
    TBA1037730801.383122816931.0401.2536.9121416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.