SPEC 45043

MachineFLEX™ Tray Control Cable Cu 600/1000V PVC THHN TPE Jacket

Type TC-ER Machine Tray Power Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Black Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s MachineFLEX™ tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Standard for Power-Limited Circuit Cables
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2277 Type WTTC
  • UL 13 Type PLTC-ER sizes 18-12AWG
  • UL 2250 Type ITC-ER on sizes 18-12 AWG
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Sample Print Legend:

    SOUTHWIRE{R} XX AWG (X.XXmm2) X/C PVC/NYLON TYPE TC-ER E75755 MASTER-DESIGN (UL) 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC-ER OR ITC-ER OR AWM 2587 -- LL90458 CSA CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 -- {NOM}-ANCE PLTC -- {CE} RoHS-2 MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessGroundJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsmilNo. x AWGmilinchlb/1000ftinchAmpAmpAmp
    18 AWG
    67731518316201 x450.281431.12777
    67753018416201 x450.306591.22777
    67731618516201 x450.322631.33777
    66509018616201 x450.348851.40777
    67753118716201 x450.358851.43777
    66508918816201 x450.4011111.60777
    67753218916201 x450.4111071.64777
    665091181016201 x450.43811371.75777
    677533181216201 x450.4561351.82777
    665092181416201 x450.4691401.88777
    665093181616201 x450.4951651.98777
    665094181916201 x650.5602372.24777
    677317182516201 x650.6352541.33666
    665095183716201 x650.7324232.93777
    16 AWG
    67753616226201 x500.311481.24101010
    67753516326201 x500.311601.24101010
    67753616426201 x500.339761.36101010
    67731816526201 x450.370861.48101010
    66509816726201 x500.4001231.60101010
    66509916826201 x500.4311431.72777
    66509716626201 x500.4621401.85777
    67732016926201 x500.4621381.85101010
    665100161026201 x500.5091542.04777
    677321161226201 x500.5091752.04999
    665101161626201 x650.6012422.40777
    665102161926201 x650.6303162.52777
    665103162426201 x650.7173402.87777
    665104163026201 x850.8114393.24777
    665105163726201 x850.8705283.48777
    14 AWG
    67725814341201 x500.342821.37151515
    67725914441201 x500.3751061.50151515
    66510614641201 x500.4451341.78121620
    65300514841201 x500.4811611.92141414
    67726114941201 x500.5162052.06141414
    665107141041201 x650.6022272.41151515
    677322141241201 x650.6162612.46141414
    665108141641201 x650.6663322.66151515
    677262141841201 x650.6974022.79101010
    677263142541201 x650.8065653.22999
    12 AWG
    67725612365201 x500.3891081.56202020
    67753712465201 x500.4201471.68202020
    67753812565201 x500.4621761.85202020
    66510912665201 x500.5021942.01202020
    67725712765201 x500.5022272.01171717
    66510912865201 x650.5742612.01202020
    665111121265201 x650.6874262.75202020
    10 AWG
    653009103105251 x500.4621612.01303030
    677539104105251 x500.5022062.01282828
    677254105105251 x500.5302552.01282828
    677255107105251 x600.6083642.43242424
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00M