SPEC 45041

MachineFLEX™ Tray Control Cable Cu 600/1000V PVC THHN TPE Jacket

Type TC-ER Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Sunlight Resistant Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s MachineFLEX™ control tray cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s machine tray cable is ideal for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind ener- gy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 66 Fixture Wire Type TFFN (for sizes 18 and 16 AWG)
  • UL 83 Thermoplastic Insulated Wire and Cables (sizes 14 AWG to 1000 kcmil)
  • UL 758 AWM Style 2587
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2277 Type WTTC
  • UL 13 Type PLTC-ER sizes 18-12AWG
  • UL 2250 Type ITC-ER on sizes 18-12 AWG
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Sample Print Legend:

    Print Legend 1:
    Southwire XXAWG (XXmm2) XX/C PVC/Nylon Type TC-ER EXXXXX (UL) 600V 90°C Dry 75C Wet Sun Res Oil Res I/II DIR BUR - 40°C OR MTW Flexing OR DP-1 OR WTTC 1000V OR AWM 2587 -- LLXXXXXX CSA AWM I/II A/B 105°C 1000V -40°C FT4 -- CSA FT4 CE RoHS -2 Made in USA

    Print Legend 2:
    SOUTHWIRE{R} XX AWG (X.XXmm2) X/C PVC/NYLON TYPE TC-ER E75755 MASTER-DESIGN (UL) 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC-ER OR ITC-ER OR AWM 2587 -- LL90458 CSA CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 -- NOM-ANCE 90{D}C PVC/NYLON PVC-TPE THHN/THWN FT4 600V -- {CE} RoHS-2 MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    6770711821620450.26610357.1488.6131.00014
    5815111831620450.28115427.1488.6131.10014
    5826421841620450.30620547.1488.6131.20011
    5826441851620450.33225637.1488.6131.30011
    5815131871620450.35835797.1488.6131.4009
    5826451891620450.411451017.1488.6131.6009
    58264618121620450.456601287.1488.6131.8007
    58264718181620450.554902257.1488.6132.2007
    64626218191620450.560952007.1488.6132.2007
    58151418251620600.6351252537.1488.6132.5006
    16 AWG
    6770721622620500.29416454.4875.4061.10018
    5815151632620500.31124584.4875.4061.20018
    5826481642620500.33932714.4875.4061.30014
    5826491652620500.37040864.4875.4061.40014
    5815161672620500.400561074.4875.4061.60012
    TBA1682620500.429721264.4875.4061.70012
    5826511692620500.462721374.4875.4061.80012
    58265216122620500.509971744.4875.4062.0009
    58265316182620650.6231452624.4875.4062.4009
    64626316192620650.6301542724.4875.4062.5009
    58151716252620650.7172023454.4875.4062.8008
    14 AWG
    6770731424120500.32425582.8143.3911.2152025
    5815191434120500.34238772.8143.3911.3152025
    5826541444120500.37551962.8143.3911.5121620
    5826551454120500.411631142.8143.3911.6121620
    5815211474120500.445891492.8143.3911.7101417
    6737951484120500.4951021752.8143.3911.9101417
    5826561494120500.5161151882.8143.3912.0101417
    58265714124120650.6081532572.8143.3912.471012
    58265814184120650.6972303632.8143.3912.771012
    58152214254120650.8063184862.8143.3913.26911
    12 AWG
    6770741226520500.36240801.7742.1371.4202530
    6771881236520500.389601081.7742.1371.5202530
    5826591246520500.420811361.7742.1371.6162024
    5826601256520500.5021011701.7742.1372.0162024
    5826611276520500.5021412191.7742.1372.0141721
    10 AWG
    67707510210525500.430641191.1111.3391.7303540
    67718910310525500.462971591.1111.3391.8303540
    58152310410525500.5021292011.1111.3392.0242832
    58266210510525500.5791612911.1111.3392.3242832
    58266310710525650.6282263361.1111.3392.5212428
    6771908316835680.6261573140.7150.8612.5405055
    6433678416835600.6802103610.7150.8612.7324044
    6737978516835700.7662634500.7150.8613.0324044
    6771916325935700.7252684400.450.5412.9556575
    6433696425935600.8173585620.4500.5413.2445260
    6771924341350800.8893996490.2820.3403.5708595
    6433714441350800.9695328290.2820.3403.8566876
    67719323651501001.0706379880.1790.2165.395115130
    6433732465150801.19684912620.1790.2165.97692104
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Notes:

    Revision: 3.0.00M