SPEC 45007
1/C AL 600 or 1000V XLPE XHHW-2 Power Cable
Power Cable 600 or 1000 Volt Single Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
Applications and Features:
Southwire’s 600 or 1000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.
Specifications:
Sample Print Legend:
SOUTHWIRE E30117 MASTER-DESIGN {UL} XXX AWG 8000 COMPACT AL.--- TRIPLE E ALLOY AA8176 TYPE XHHW-2 VW-1 FOR CT USE SUN. RES. 600V OR 1000V {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
560397 | 1/0 | 19 | 0.336 | 55 | 0.452 | 99 | 142 |
TBA | 2/0 | 19 | 0.376 | 55 | 0.486 | 125 | 163 |
560395 | 3/0 | 19 | 0.422 | 55 | 0.539 | 158 | 211 |
560361 | 4/0 | 19 | 0.474 | 55 | 0.591 | 199 | 258 |
560362 | 250 | 35 | 0.520 | 65 | 0.656 | 235 | 311 |
562832 | 300 | 35 | 0.569 | 65 | 0.707 | 282 | 365 |
560363 | 350 | 35 | 0.615 | 65 | 0.752 | 329 | 418 |
563044 | 600 | 58 | 0.812 | 80 | 0.973 | 565 | 707 |
560381 | 750 | 58 | 0.908 | 80 | 1.076 | 706 | 866 |
560382 | 1000 | 58 | 1.060 | 80 | 1.228 | 942 | 1129 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
560397 | 1/0 | 1.8 | 633 | 0.168 | 0.201 | 0.044 | 100 | 120 | 135 |
TBA | 2/0 | 1.9 | 798 | 0.133 | 0.160 | 0.043 | 115 | 135 | 150 |
560395 | 3/0 | 2.1 | 1006 | 0.105 | 0.126 | 0.042 | 130 | 155 | 175 |
560361 | 4/0 | 2.3 | 1269 | 0.084 | 0.100 | 0.041 | 150 | 180 | 205 |
560362 | 250 | 2.6 | 1500 | 0.071 | 0.086 | 0.041 | 170 | 205 | 230 |
562832 | 300 | 2.8 | 1800 | 0.059 | 0.071 | 0.041 | 195 | 230 | 260 |
560363 | 350 | 3.0 | 2100 | 0.050 | 0.062 | 0.040 | 210 | 250 | 280 |
563044 | 600 | 3.8 | 3600 | 0.029 | 0.037 | 0.039 | 285 | 340 | 385 |
560381 | 750 | 5.3 | 4500 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
560382 | 1000 | 6.1 | 6000 | 0.018 | 0.025 | 0.037 | 375 | 445 | 500 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Revision: 3.0.00C