SPEC 45003
1/C CU 600V XLPE RHH/RHW-2 USE-2 Silicone-Free Power Cable
Power Cable 600Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2 CT Rated

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2 Silicone-Free
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE E32071 {UL} XXX AWG (XX.X{mm2}) CU TYPE USE-2 OR RHH OR RHW-2 XX MILS XLP FOR CT USE SUN. RES. VW-1 600 VOLTS {NOM}-ANCE RHH/RHW-2 600V 90C
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
890105◊ | 1/0 | 19 | 0.361 | 80 | 0.530 | 325 | 394 |
890106◊ | 2/0 | 19 | 0.405 | 80 | 0.572 | 410 | 485 |
890631◊ | 3/0 | 19 | 0.456 | 80 | 0.624 | 518 | 602 |
890107◊ | 4/0 | 19 | 0.512 | 80 | 0.680 | 653 | 747 |
890632◊ | 250 | 37 | 0.558 | 95 | 0.742 | 771 | 888 |
890108◊ | 350 | 37 | 0.661 | 95 | 0.861 | 1081 | 1221 |
890109◊ | 500 | 37 | 0.789 | 95 | 0.966 | 1544 | 1704 |
890633◊ | 750 | 61 | 0.968 | 110 | 1.002 | 2316 | 2547 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
890105◊ | 1/0 | 2.1 | 844 | 0.102 | 0.122 | 0.0300 | 125 | 150 | 170 |
890106◊ | 2/0 | 2.2 | 1064 | 0.081 | 0.097 | 0.0293 | 145 | 175 | 195 |
890631◊ | 3/0 | 2.4 | 1342 | 0.064 | 0.078 | 0.0286 | 165 | 200 | 225 |
890107◊ | 4/0 | 2.7 | 1692 | 0.051 | 0.062 | 0.0279 | 195 | 230 | 260 |
890632◊ | 250 | 2.9 | 2000 | 0.043 | 0.053 | 0.0284 | 215 | 255 | 290 |
890108◊ | 350 | 3.4 | 2800 | 0.031 | 0.039 | 0.0274 | 260 | 310 | 350 |
890109◊ | 500 | 3.8 | 4000 | 0.022 | 0.029 | 0.0266 | 320 | 380 | 430 |
890633◊ | 750 | 6.0 | 6000 | 0.014 | 0.022 | 0.0263 | 400 | 475 | 535 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Revision: 3.0.00C