SPEC 10080

Bare Copper Solid, Compressed Class B and C

...

Construction:

  1. Conductor:Bare copper solid or compressed class B or C per ASTM B3 and ASTM B8

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand ClassStrand CountCond. CmilApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°C
    AWG/kcmilNo. of Strandscmilinchlb/1000ftΩ/1000ftΩ/1000ft
    10614614Solid141100.064122.6313.170
    10620312Solid165300.080201.6622.002
    10626010Solid1103800.101321.0401.253
    1063288Solid1165100.128500.6530.786
    TBA7Solid1208200.144640.5190.625
    1063856Solid1262400.162810.4110.495
    TBA5Solid1330900.1811020.3250.391
    1064434Solid1417400.2041280.2580.310
    TBA3Solid1526200.2291620.2050.246
    1065002Solid1663600.2572040.1620.195
    TBA1Solid1836900.2892580.1280.154
    1361681/0Solid11056000.3243250.1020.122
    TBA2/0Solid11331000.3644100.0810.097
    TBA3/0Solid11678000.4095180.0640.078
    TBA4/0Solid12116000.4606530.0510.062
    TBA14B741100.070122.6313.170
    TBA12B765300.088201.6622.002
    TBA10B7103800.113321.0401.253
    1065678B7165100.141500.6530.786
    TBA7B7208200.159640.5190.625
    1066586B7262400.177810.4110.495
    TBA5B7330900.2001020.3250.391
    1067404B7417400.2251280.2580.310
    TBA3B7526200.2521620.2050.246
    1068642B7663600.2822040.1620.195
    TBA1B19836900.3222580.1280.154
    TBA1/0B191056000.3613250.1020.122
    1445192/0B191331000.4054100.0810.097
    1445273/0B191678000.4565180.0640.078
    1367394/0B192116000.5126530.0510.062
    TBA250B372500000.5587710.0430.053
    TBA300B373000000.6109260.0360.045
    TBA350B373500000.66110810.0310.039
    TBA400B374000000.70512350.0270.035
    TBA450B374500000.74913890.0240.031
    107193500B375000000.81315440.0220.029
    TBA550B615500000.82816980.0200.026
    TBA600B616000000.86518530.0180.025
    TBA650B616500000.90120070.0170.023
    TBA700B617000000.93521610.0150.022
    107250750B617500000.96823160.0140.022
    TBA800B618000001.00024700.0130.021
    TBA900B619000001.06027790.0120.020
    1072841000B6110000001.11730880.0110.018
    TBA14C1941100.073122.6313.170
    TBA12C1965300.090201.6622.002
    TBA10C19103800.117321.0401.253
    TBA8C19165100.143500.6530.786
    TBA7C19208200.165640.5190.625
    TBA6C19262400.179810.4110.495
    TBA5C19330900.2081020.3250.391
    TBA4C19417400.2261280.2580.310
    TBA3C19526200.2541620.2050.246
    TBA2C19663600.2862040.1620.195
    TBA1C37836900.3332580.1280.154
    TBA1/0C371056000.3733250.1020.122
    TBA2/0C371331000.4204100.0810.097
    TBA3/0C371678000.4715180.0640.078
    1401524/0C372116000.5296530.0510.062
    TBA250C612500000.5757710.0430.053
    TBA300C613000000.6309260.0360.045
    207852350C613500000.68110810.0310.039
    TBA400C614000000.72812350.0270.035
    TBA450C614500000.77313890.0240.031
    TBA500C615000000.81415440.0220.029
    TBA550C915500000.85416980.0200.026
    TBA600C916000000.89318530.0180.025
    TBA650C916500000.92920070.0170.023
    TBA700C917000000.96421610.0150.022
    TBA750C917500000.99823160.0140.022
    TBA800C918000001.03124700.0130.021
    TBA900C919000001.09327790.0120.020
    TBA1000C9110000001.15230880.0110.018
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.019

    Updated On: Jan. 24, 2024, 5:59 p.m. UTC