SPEC 44020

DLO TCU 2000V EPDM Insulation Thermoset CPE Jacket. RHH/RHW-2/RW90 MSHA Approved.

UL Listed as 2kV Heavy Duty Flexible Power Cable (HDFPC) DLO, Rated 90°C Dry or Wet. 2kV Type RHH/RHW-2 Flexible Power Cable Rated for Dry or Wet. CSA Listed as 2kV Type RW90. Composite Thermoset Wall EPDM Insulation Thermoset CPE Jacket. Silicone-Free. MSHA Approved

...

Construction:

  1. Conductor:Flexible Stranded Rope-Lay Class I Tinned Copper per ASTM B33 and B172 (As Applicable)
  2. Binder Tape:Mylar Tape
  3. Insulation:Black Thermoset Ethylene Propylene Diene Monomer (EPDM)
  4. Jacket:Thermoset Chlorinated Polyethylene (CPE). Other colors available (see table below)

Applications and Features:

HDFPC-DLO is a 2kV flexible power cable with a variety of possible applications such as but not limited to: Drilling rigs, railroad and transit car wiring, mining and other industrial equipment, and as flexible motor leads and wind turbine applications. The cable is suited for use in wet and dry areas, conduits, ducts, troughs, trays, and where superior electrical properties are desired. HDFPC-DLO is oil, heat, flame, abrasion, and sunlight resistant. Approved for use per the NEC® as Type RHH/RHW-2 and per the CE Code as 2kV Type RW90. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Sizes 1/0 and Larger Rated For CT Use.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors (As Applicable)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2806 Heavy Duty Flexible Power Cable (HDFPC-DLO)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • MSHA Approved
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    Sizes 12 AWG and 10 AWG
    {SQFTG} SOUTHWIRE® ROYAL® XX AWG (XXmm2) E30117 (UL) TYPE RHH/RHW-2 90°C DRY 90°C WET 2KV (-40°C) PRI PRII SR --- EPR/CPE DLO --- P-07-KA100013-MSHA---RoHS

    Sizes 8 AWG to 1 AWG
    SOUTHWIRE® ROYAL® XX AWG (XX{mm2}) E30117 {UL} TYPE HDFPC EPR/CPE 2KV DL0 90°C DRY 90°C WET OR TYPE RHH/RHW-2 90°C DRY 90°C WET 2KV -40°C PRI PRII SR VW-1 -- {CSA} 156205 RW90 90°C DRY 90°C WET 2KV -40°C PRI PRII FT1 SR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Sizes 1/0 AWG and larger
    {SQFTG} SOUTHWIRE® ROYAL® XX AWG XX STRAND CLASS XX (XX{mm2}) E30117 {UL} TYPE HDFPC EPR/CPE 2KV DLO 90°C DRY 90°C WET OR TYPE RHH/RHW-2 90°C DRY 90°C WET 2KV -40°C PRI PRII SR FOR CT USE FT4 -- {CSA} 156205 RW90 90°C DRY 90°C WET TC-ER 2KV -40C° PRI PRII FT1 FT4 SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorMin. Avg. Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    66546512190.09145150.2102036
    66546612190.09145150.2102036
    66546712190.09145150.2102036
    57125312190.09145150.2102036
    66546812190.09145150.2102036
    66544612190.09145150.2102036
    66546910190.12555250.2653258
    66547010190.12555250.2653258
    66547110190.12555250.2653258
    66547210190.12555250.2653258
    56005710190.12555250.2653258
    66547310190.12555250.2653258
    1670148410.14555300.3305292
    6654748410.14555300.3305292
    6654758410.14555300.3305292
    6654768410.14555300.3305292
    6654778410.14555300.3305292
    TBA8410.14555300.3305292
    6654786650.18650300.37081127
    6654796650.18650300.37081127
    6654806650.18650300.37081127
    6654816650.18650300.37081127
    1670156650.18650300.37081127
    6654826650.18650300.37081127
    66548341050.23560350.440133196
    66548441050.23560350.440133196
    66548541050.23560350.440133196
    16701741050.23560350.440133196
    65362741050.23560350.440133196
    13823821610.29060350.500210282
    13823921610.29060350.500210282
    13824021610.29060350.500210282
    16701921610.29060350.500210282
    13824121610.29060350.500210282
    16702012100.33085600.635267400
    13828212100.33085600.635267400
    13828312100.33085600.635267400
    13828712100.33085600.635267400
    13828812100.33085600.635267400
    13828912100.33085600.635267400
    1382421/02660.37975550.645327450
    1382431/02660.37975550.645327450
    1382441/02660.37975550.645327450
    1382451/02660.37975550.645327450
    1670211/02660.37975550.645327450
    1382461/02660.37975550.645327450
    1382472/03420.40080500.690423566
    1382482/03420.40080500.690423566
    1382492/03420.40080500.690423566
    1670222/03420.40080500.690423566
    1382512/03420.40080500.690423566
    5620643/04180.48080550.760518676
    1382523/04180.48080550.760518676
    1382533/04180.48080550.760518676
    1382543/04180.48080550.760518676
    1382553/04180.48080550.760518676
    1670233/04180.48080550.760518676
    1382563/04180.48080550.760518676
    1382574/05320.53080600.815638815
    1382584/05320.53080600.815638815
    1382594/05320.53080600.815638815
    1670244/05320.53080600.815638815
    1382604/05320.53080600.815638815
    641176262.26460.56580600.845740974
    665452262.26460.56580600.845740974
    665453262.26460.56580600.845740974
    665454262.26460.56580600.845740974
    167026262.26460.56580600.845740974
    665455262.26460.56580600.845740974
    665456313.37790.65090700.9808961139
    665457313.37790.65090700.9808961139
    665458313.37790.65090700.9808961139
    665459313.37790.65090700.9808961139
    167027313.37790.65090700.9808961139
    665460313.37790.65090700.9808961139
    655203373.79310.70195701.04010761343
    678900373.79310.70195701.04010761343
    576729373.79310.70195701.04010761343
    678901373.79310.70195701.04010761343
    167029373.79310.70195701.04010761343
    678902373.79310.70195701.04010761343
    167030444.411210.78290651.10513781654
    678975444.411210.78290651.10513781654
    665461444.411210.78290651.10513781654
    665462444.411210.78290651.10513781654
    665463444.411210.78290651.10513781654
    665464444.411210.78290651.10513781654
    138211535.313300.843105751.21215491889
    138212535.313300.843105751.21215491889
    138213535.313300.843105751.21215491889
    167031535.313300.843105751.21215491889
    677552535.313300.843105751.21215491889
    138229646.416280.890115801.29018982292
    138215646.416280.890115801.29018982292
    138216646.416280.890115801.29018982292
    138217646.416280.890115801.29018982292
    167032646.416280.890115801.29018982292
    138218646.416280.890115801.29018982292
    640980777.719240.966120901.40522462727
    640981777.719240.966120901.40522462727
    640982777.719240.966120901.40522462727
    167033777.719240.966120901.40522462727
    138219777.719240.966120901.40522462727
    640983777.719240.966120901.40522462727
    664206929.923001.11390651.47027453171
    138220111127451.168115951.64035604161
    138221111127451.168115951.64035604161
    138222111127451.168115951.64035604161
    138223111127451.168115951.64035604161
    167035111127451.168115951.64035604161
    138224111127451.168115951.64035604161
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    665465120.8521.7742.3010.0542530
    665466120.8521.7742.3010.0542530
    665467120.8521.7742.3010.0542530
    571253120.8521.7742.3010.0542530
    665468120.8521.7742.3010.0542530
    665446120.8521.7742.3010.0542530
    665469101.1831.0811.3020.0503540
    665470101.1831.0811.3020.0503540
    665471101.1831.0811.3020.0503540
    665472101.1831.0811.3020.0503540
    560057101.1831.0811.3020.0503540
    665473101.1831.0811.3020.0503540
    16701481.31320.6790.8180.0525055
    66547481.31320.6790.8180.0525055
    66547581.31320.6790.8180.0525055
    66547681.31320.6790.8180.0525055
    66547781.31320.6790.8180.0525055
    TBA81.31320.6790.8180.0525055
    66547861.52090.4350.5240.0516575
    66547961.52090.4350.5240.0516575
    66548061.52090.4350.5240.0516575
    66548161.52090.4350.5240.0516575
    16701561.52090.4350.5240.0516575
    66548261.52090.4350.5240.0516575
    66548341.83330.2740.3300.0488595
    66548441.83330.2740.3300.0488595
    66548541.83330.2740.3300.0488595
    16701741.83330.2740.3300.0488595
    65362741.83330.2740.3300.0488595
    13823822.05300.1720.2070.045115130
    13823922.05300.1720.2070.045115130
    13824022.05300.1720.2070.045115130
    16701922.05300.1720.2070.045115130
    13824122.05300.1720.2070.045115130
    16702012.56700.1430.1860.046130145
    13828212.56700.1430.1860.046130145
    13828312.56700.1430.1860.046130145
    13828712.56700.1430.1860.046130145
    13828812.56700.1430.1860.046130145
    13828912.56700.1430.1860.046130145
    1382421/02.68440.1090.1310.044150170
    1382431/02.68440.1090.1310.044150170
    1382441/02.68440.1090.1310.044150170
    1382451/02.68440.1090.1310.044150170
    1670211/02.68440.1090.1310.044150170
    1382461/02.68440.1090.1310.044150170
    1382472/02.810640.0870.1040.043175195
    1382482/02.810640.0870.1040.043175195
    1382492/02.810640.0870.1040.043175195
    1670222/02.810640.0870.1040.043175195
    1382512/02.810640.0870.1040.043175195
    5620643/03.013420.0690.0830.042200225
    1382523/03.013420.0690.0830.042200225
    1382533/03.013420.0690.0830.042200225
    1382543/03.013420.0690.0830.042200225
    1382553/03.013420.0690.0830.042200225
    1670233/03.013420.0690.0830.042200225
    1382563/03.013420.0690.0830.042200225
    1382574/03.316920.0550.0670.041230260
    1382584/03.316920.0550.0670.041230260
    1382594/03.316920.0550.0670.041230260
    1670244/03.316920.0550.0670.041230260
    1382604/03.316920.0550.0670.041230260
    641176262.23.420970.0260.0330.031264301
    665452262.23.420970.0260.0330.031264301
    665453262.23.420970.0260.0330.031264301
    665454262.23.420970.0260.0330.031264301
    167026262.23.420970.0260.0330.031264301
    665455262.23.420970.0260.0330.031264301
    665456313.33.925060.0390.0480.031298332
    665457313.33.925060.0390.0480.031298332
    665458313.33.925060.0390.0480.031298332
    665459313.33.925060.0390.0480.031298332
    167027313.33.925060.0390.0480.031298332
    665460313.33.925060.0390.0480.031298332
    655203373.75.229890.0330.0420.031323365
    678900373.75.229890.0330.0420.031323365
    576729373.75.229890.0330.0420.031323365
    678901373.75.229890.0330.0420.031323365
    167029373.75.229890.0330.0420.031323365
    678902373.75.229890.0330.0420.031323365
    167030444.45.535550.0260.0400.029358405
    678975444.45.535550.0260.0400.029358405
    665461444.45.535550.0260.0400.029358405
    665462444.45.535550.0260.0400.029358405
    665463444.45.535550.0260.0400.029358405
    665464444.45.535550.0260.0400.029358405
    138211535.36.142820.0210.0280.030394446
    138212535.36.142820.0210.0280.030394446
    138213535.36.142820.0210.0280.030394446
    167031535.36.142820.0210.0280.030394446
    677552535.36.142820.0210.0280.030394446
    138229646.46.551710.0180.0250.030439496
    138215646.46.551710.0180.0250.030439496
    138216646.46.551710.0180.0250.030439496
    138217646.46.551710.0180.0250.030439496
    167032646.46.551710.0180.0250.030439496
    138218646.46.551710.0180.0250.030439496
    640980777.77.062210.0160.0240.030483543
    640981777.77.062210.0160.0240.030483543
    640982777.77.062210.0160.0240.030483543
    167033777.77.062210.0160.0240.030483543
    138219777.77.062210.0160.0240.030483543
    640983777.77.062210.0160.0240.030483543
    664206929.97.474330.0120.0190.028527593
    13822011118.288880.0110.0160.029570648
    13822111118.288880.0110.0160.029570648
    13822211118.288880.0110.0160.029570648
    13822311118.288880.0110.0160.029570648
    16703511118.288880.0110.0160.029570648
    13822411118.288880.0110.0160.029570648
    * Ampacities in raceway are based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities for non-standard sizes were extrapolated
    * Ampacities in air are based upon 2023 NEC Table 310.17. Ampacities for non-standard sizes were extrapolated
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * #12 and #10 AWG are not approved for CSA RW90

    Other Insulation Colors

    Cond. SizeBlackRedBrownOrangeYellowGreenGray
    AWG/kcmilBlackRedBrownOrangeYellowGreenGray
    12571253665446665465665466665467665468 
    10560057665469665470665471665472665473 
    8TBA167014665474665475665476665477 
    6167015665478665479665480665481665482 
    4167017167017665483665484665485653627 
    2167019167019138238138239138240138241 
    1167020138282138283138287138288138289 
    1/0167021138242138243138244138245138246 
    2/0167022167022138247138248138249138251 
    3/0167023138252138253138254138255138256 
    4/0167024167024138257138258138259138260 
    262.6167026641176665452665453665454665455 
    313.3167027665456665457665458665459665460 
    373.7167029655203678900576729678901678902 
    444.4167030678975665461665462665463665464 
    535.3167031167031138211138212138213677552 
    646.4167032138229138215138216138217138218 
    777.7167033167033640980640981640982138219640983
    1111167035138220138221138222138223138224