SPEC 22060

SIMpull® T90 Copper

SIMpull® THHN THWN-2 MTW / c(UL) T90 Nylon TWN75 Copper Conductor, 600V, Thermoplastic-Insulated Cable, All Sizes Rated TWN75

...

Construction:

  1. Conductor:Solid per ASTM B3 or Combination unilay-stranded copper conductors per ASTM B787.
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath
  3. Jacket:Polyvinyl Chloride PVC jacket utilizing SIMpull® Technology.

Applications and Features:

SIMpull® THHN, THWN-2, MTW - (UL)- Suitable for dry locations not exceeding 90°C. For Gasoline and Oil Resistant II applications not to exceed 75°C. MTW (UL) - suitable for dry locations not exceeding 90°C. For wet locations, Gasoline and Oil Resistant II applications not to exceed 60°C. T90 Nylon c(UL) - cables are primarily intended for installation in conduit (raceways) as exposed wiring in dry locations not exceeding 90°C. TWN75 c(UL) - suitable for wet or dry locations at not more than 75°C. The maximum voltage rating for all intended applications is 600 volts. Minimum installation handling temperature is limited to -25°C. Minimum operating temperature limited to -40°C. Non-SIMpull Silicone Free size 14, 12, 10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA Certified LL90458
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • Canadian Electrical Code
  • CSA FT-1 Flame Test
  • Sample Print Legend:

    SOUTHWIRE SIMpull{TM} E51583 {UL} (XX AWG) XX.X{mm2} CU TYPE MTW OR THWN-2 OR THHN OR GASOLINE AND OIL RESISTANT II OR AWM 600 VOLTS VW-1 --- {CSA} T90 NYLON OR TWN75 600 VOLTS FT1 {NOM}-ANCE 90°C - (X AWG) ---RoHS PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    50766514Solid0.0641550.1061215
    67805014Solid0.0641550.1061215
    50769914Solid0.0641550.1061215
    50767314Solid0.0641550.1061215
    50772314Solid0.0641550.1061215
    61048314Solid0.0641550.1061215
    50770714Solid0.0641550.1061215
    55309614Solid0.0641550.1061215
    50768114Solid0.0641550.1061215
    67265914190.0731550.1131216
    47201914190.0731550.1131216
    47202714190.0731550.1131216
    68751714190.0731550.1131216
    47204314190.0731550.1131216
    47203514190.0731550.1131216
    50771514190.0731550.1131216
    49577012Solid0.0801550.1221923
    50763212Solid0.0801550.1221923
    49581212Solid0.0801550.1221923
    49580412Solid0.0801550.1221923
    50764012Solid0.0801550.1221923
    49578812Solid0.0801550.1221923
    49579612Solid0.0801550.1221923
    50765712Solid0.0801550.1221923
    47206812190.0901550.1322024
    67267512190.0901550.1322024
    47209212190.0901550.1322024
    47207612190.0901550.1322024
    47208412190.0901550.1322024
    55266012190.0901550.1322024
    67266712190.0901550.1322024
    48462610Solid0.1012050.1533137
    50775610Solid0.1012050.1533137
    50773110Solid0.1012050.1533137
    67268310Solid0.1012050.1533137
    50774910Solid0.1012050.1533137
    55266310190.1172050.1653238
    61048610190.1172050.1653238
    47213410190.1172050.1653238
    47211810190.1172050.1653238
    55266210190.1172050.1653238
    47212610190.1172050.1653238
    47214210190.1172050.1653238
    6114628190.1433050.2175063
    4721758190.1433050.2175063
    4721678190.1433050.2175063
    4721918190.1433050.2175063
    4721838190.1433050.2175063
    4722176190.1793050.2538195
    4722256190.1793050.2538195
    4722416190.1793050.2538195
    4722336190.1793050.2538195
    4722824190.2264050.324128154
    6840683190.2544050.352162190
    4846753190.2544050.352162190
    6840762190.2864050.384204236
    6723942190.2864050.384204236
    6880512/0190.4205050.524410465
    6724022/0190.4205050.524410464
    4719953/0190.4715050.574518578
    47200114190.0701550.1131216
    47205012190.0881550.1322024
    47210010190.1132050.1653238
    4721598190.1413060.2175063
    4722096190.1773060.2538195
    4722584190.2254070.322128153
    4846673190.2524070.350162190
    6723862190.2824070.382204235
    6840841190.3225080.439258301
    4719791/0190.3615080.480326374
    4719873/0190.4565080.574518579
    6778204/0190.5125080.630655723
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    507665140.400322.6313.1700.0582025
    678050140.400322.6313.1700.0582025
    507699140.400322.6313.1700.0582025
    507673140.400322.6313.1700.0582025
    507723140.400322.6313.1700.0582025
    610483140.400322.6313.1700.0582025
    507707140.400322.6313.1700.0582025
    553096140.400322.6313.1700.0582025
    507681140.400322.6313.1700.0582025
    672659140.500322.6313.1700.0582025
    472019140.500322.6313.1700.0582025
    472027140.500322.6313.1700.0582025
    687517140.500322.6313.1700.0582025
    472043140.500322.6313.1700.0582025
    472035140.500322.6313.1700.0582025
    507715140.500322.6313.1700.0582025
    495770120.400521.6622.0020.0542530
    507632120.500521.6622.0020.0542530
    495812120.500521.6622.0020.0542530
    495804120.500521.6622.0020.0542530
    507640120.500521.6622.0020.0542530
    495788120.500521.6622.0020.0542530
    495796120.500521.6622.0020.0542530
    507657120.500521.6622.0020.0542530
    472068120.500521.6622.0020.0542530
    672675120.500521.6622.0020.0542530
    472092120.500521.6622.0020.0542530
    472076120.500521.6622.0020.0542530
    472084120.500521.6622.0020.0542530
    552660120.500521.6622.0020.0542530
    672667120.500521.6622.0020.0542530
    484626100.600831.0401.2530.0503540
    507756100.600831.0401.2530.0503540
    507731100.600831.0401.2530.0503540
    672683100.600831.0401.2530.0503540
    507749100.600831.0401.2530.0503540
    552663100.700831.0401.2530.0503540
    610486100.700831.0401.2530.0503540
    472134100.700831.0401.2530.0503540
    472118100.700831.0401.2530.0503540
    552662100.700831.0401.2530.0503540
    472126100.700831.0401.2530.0503540
    472142100.700831.0401.2530.0503540
    61146280.9001320.6530.7860.0525055
    47217580.9001320.6530.7860.0525055
    47216780.9001320.6530.7860.0525055
    47219180.9001320.6530.7860.0525055
    47218380.9001320.6530.7860.0525055
    47221761.0002090.4110.4950.0516575
    47222561.0002090.4110.4950.0516575
    47224161.0002090.4110.4950.0516575
    47223361.0002090.4110.4950.0516575
    47228241.3003330.2580.3100.0488595
    68406831.4004200.2050.2460.047100115
    48467531.4004200.2050.2460.047100115
    68407621.5005300.1620.1950.045115130
    67239421.5005300.1620.1950.045115130
    6880512/02.10010640.0810.0970.043175195
    6724022/02.10010640.0810.0970.043175195
    4719953/02.30013420.0640.0780.042200225
    472001140.400322.6313.1700.0582025
    472050120.500521.6622.0020.0542530
    472100100.600831.0401.2530.0503540
    47215980.8001320.6530.7860.0525055
    47220961.0002090.4110.4950.0516575
    47225841.2003330.2580.3100.0488595
    48466731.4004200.2050.2460.047100115
    67238621.5005300.1620.1950.045115130
    68408411.7006690.1280.1540.046130145
    4719791/01.9008440.1020.1220.044150170
    4719873/02.20013420.0640.0780.042200225
    6778204/02.50016920.0510.0620.041230260
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * Non-SIMpull Silicone Free sizes: 14, 12, 10.

    Table 3 - Stock Code Colors ( / means stripe. Blue/White: Blue with White Stripe)

    Size (Strand)ColorStock Number
    14 (Solid)BK507665
    14 (Solid)RD507699
    14 (Solid)WE507673
    14 (Solid)YW507723
    14 (Solid)OE610483
    14 (Solid)BE507707
    14 (Solid)BN553096
    14 (Solid)GN507681
    14 (19)BK472001
    14 (19)WE/BE678050
    14 (19)YW672659
    14 (19)WE472019
    14 (19)RD472027
    14 (19)OE687517
    14 (19)BE472043
    14 (19)GN472035
    14 (19)BN507715
    12 (Solid)BK495770
    12 (Solid)OE507632
    12 (Solid)BE495812
    12 (Solid)GN495804
    12 (Solid)BN507640
    12 (Solid)WE495788
    12 (Solid)RD495796
    12 (Solid)YW507657
    12 (19)BK472050
    12 (19)WE472068
    12 (19)YW672675
    12 (19)BE472092
    12 (19)RD472076
    12 (19)GN472084
    12 (19)OE552660
    12 (19)BN672667
    10 (Solid)RD484626
    10 (Solid)BE507756
    10 (Solid)BK507731
    10 (Solid)GN672683
    10 (Solid)WE507749
    10 (19)BK472100
    10 (19)YW552663
    10 (19)OE610486
    10 (19)GN472134
    10 (19)WE472118
    10 (19)BN552662
    10 (19)RD472126
    10 (19)BE472142
    8 (19)BK472159
    8 (19)RD611462
    8 (19)RD472175
    8 (19)WE472167
    8 (19)BE472191
    8 (19)GN472183
    6 (19)BK472209
    6 (19)WE472217
    6 (19)RD472225
    6 (19)BE472241
    6 (19)GN472233
    4 (19)BK472258
    4 (19)GN472282
    3 (19)WE484667
    3 (19)GN684068
    3 (19)BK484675
    2 (19)BK672386
    2 (19)GN684076
    2 (19)WE672394
    1 (19)BK684084
    1/0 (19)BK471979
    2/0 (19)GN688051
    2/0 (19)BK672402
    3/0 (19)WE471987
    3/0 (19)BK471995
    4/0 (19)WE677820

    Revision: 1.000.019

    Updated On: Jan. 17, 2025, 2:57 p.m. UTC