SPEC 85021

Multi-Conductor CU 600 V FR-XLPE LCT Shielded PVC Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shield:5 mils copper Longitudinally-Applied Corrugated Tape (LCT) shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE {UL} XX AWG X/C FRXLP SHIELDED TYPE TC 600V PVC SUN. RES. DIRECT BURIAL YEAR{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FRXLP SHIELDED TYPE TC 600V PVC SUN. RES. DIRECT BURIAL YEAR{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    TBA14270.07030450.34926682.6303.2880.0584.22025
    TBA14370.07030450.37038872.6303.2880.0584.42025
    604059^14470.07030450.498841652.6313.1700.05861620
    TBA14570.07030600.579641322.6303.2880.0586.91620
    604057^14770.07030600.6041282492.6313.1700.0587.21417
    TBA14670.07030600.618771552.6303.2880.0587.41620
    TBA14870.07030600.6581021952.6303.2880.0587.91417
    TBA14970.07030600.6971152362.6303.2880.0588.41417
    TBA141070.07030600.7481282662.6303.2880.05891012
    604056^141270.07030600.7602033832.6313.1700.0589.11012
    TBA141970.07030600.7682434462.6303.2880.0589.21012
    TBA141570.07030800.8801923712.6303.2880.05810.61012
    TBA142070.07030800.9582564752.6303.2880.05811.51012
    TBA142570.07030801.0483206192.6303.2880.05812.6911
    TBA143070.07030801.1013847192.6303.2880.05813.2911
    TBA143770.07030801.1784748622.6303.2880.05814.1810
    12 AWG
    TBA12270.08830450.49441901.6602.0750.0545.92530
    TBA12370.08830600.547611181.6602.0750.0546.62530
    TBA12470.08830600.586811481.6602.0750.05472024
    TBA12570.08830600.6271021811.6602.0750.0547.52024
    TBA12670.08830600.6721222141.6602.0750.0548.12024
    TBA12770.08830600.6721432371.6602.0750.0548.11821
    TBA12870.08830600.7171632881.6602.0750.0548.61821
    TBA12970.08830600.7621833241.6602.0750.0549.11821
    TBA121070.08830800.8602043651.6602.0750.05410.31215
    624457^121270.08830800.8762995431.6622.0020.05410.51215
    TBA121570.08830800.9653055161.6602.0750.05411.61215
    TBA121970.08830801.0083876571.6602.0750.05412.11215
    TBA122070.08830801.0534076991.6602.0750.05412.61215
    TBA122570.08830801.1565098601.6602.0750.05413.91113
    TBA123070.08830801.21661110051.6602.0750.05414.61113
    TBA123770.08830801.30475312111.6602.0750.05415.61012
    10 AWG
    629383^10270.11330600.572951921.0401.2530.0506.93540
    62088610370.11330600.5891352511.0401.2530.0507.13540
    604091^10470.11330600.6381733091.0401.2530.0507.72832
    619380!10470.11330600.6571733101.0401.2530.0507.92832
    629381^10570.11330600.6912003411.0401.2530.0508.32832
    TBA10670.11330600.7311943231.0401.3000.0508.82428
    604096^10770.11330600.7342594291.0401.2530.0508.82428
    TBA10870.11330600.8002594101.0401.3000.0509.62428
    629379^10970.11330800.8853415701.0401.2530.05010.62428
    TBA101070.11330600.9203245191.0401.3000.050111720
    604093^101270.11330800.9754217011.0401.2530.05011.71720
    TBA101570.11330801.0824867771.0401.3000.050131720
    TBA101970.11330801.1336159411.0401.3000.05013.61720
    TBA102070.11330801.18664810011.0401.3000.05014.21720
    TBA102570.11330801.30681012361.0401.3000.05015.71518
    TBA103070.11330801.37697114501.0401.3000.05016.51518
    TBA103770.11330801.479119817551.0401.3000.05017.71416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! Tinned copper conductor per ASTM B33
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.001

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC