SPEC 26531

HVTECK AL 1/C 280TRXLPE TS PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:280 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 280 TRXLPE AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    1190.2980.8962800.956801.468501.568938
    1/0190.3360.9342800.994801.506601.6261029
    2/0190.3760.9742801.034801.546601.6661094
    3/0190.4221.0202801.080801.592601.7121173
    4/0190.4741.0722801.132801.668601.7881299
    250370.5201.1262801.186801.722601.8421393
    350370.6151.2212801.281801.817601.9371584
    500370.7351.3412801.401801.937602.0571944
    750610.9081.5242801.5841102.180602.3002511
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    118.85020.2110.2660.0700.0600.624 + j0.3670.267 + j0.0582992193194
    1/019.56330.1680.2110.0650.0580.567 + j0.3520.212 + j0.0563110221219
    2/020.07980.1330.1670.0610.0560.521 + j0.3380.168 + j0.0543234253246
    3/020.510060.1050.1330.0560.0540.484 + j0.3220.134 + j0.0523377288275
    4/021.512690.0840.1050.0520.0520.451 + j0.3060.106 + j0.0513538327305
    25022.115000.0710.0900.0490.0510.432 + j0.2900.091 + j0.0493705367343
    35023.221000.0500.0650.0440.0480.399 + j0.2650.066 + j0.0463999443399
    50024.730000.0350.0460.0380.0450.369 + j0.2370.047 + j0.0444371529451
    75027.645000.0240.0330.0330.0430.338 + j0.2020.034 + j0.0414938633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    1197.5722.767.1124.282.0337.291.2739.831396
    1/0198.5323.727.1125.252.0338.251.5241.301531
    2/0199.5524.747.1126.262.0339.271.5242.321628
    3/01910.7225.917.1127.432.0340.441.5243.481746
    4/01912.0427.237.1128.752.0342.371.5245.421933
    2503713.2128.607.1130.122.0343.741.5246.792073
    3503715.6231.017.1132.542.0346.151.5249.202357
    5003718.6734.067.1135.592.0349.201.5252.252893
    7506123.0638.717.1140.232.7955.371.5258.423737
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1477.5222340.69230.870.02130.19690.624 + j0.3670.267 + j0.0582992193194
    1/0495.3028170.55120.690.01980.19030.567 + j0.3520.212 + j0.0563110221219
    2/0508.0035510.43640.550.01860.18370.521 + j0.3380.168 + j0.0543234253246
    3/0520.7044770.34450.440.01710.17720.484 + j0.3220.134 + j0.0523377288275
    4/0546.1056470.27560.340.01580.17060.451 + j0.3060.106 + j0.0513538327305
    250561.3466750.23290.300.01490.16730.432 + j0.2900.091 + j0.0493705367343
    350589.2893450.16400.210.01340.15750.399 + j0.2650.066 + j0.0463999443399
    500627.38133500.11480.150.01160.14760.369 + j0.2370.047 + j0.0444371529451
    750701.04200250.07870.110.01010.14110.338 + j0.2020.034 + j0.0414938633505
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000