SPEC 45265

AL 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XXX AWG (XX{mm2}) 3E AL 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG 3E AL 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA8470.134451 x 8600.66477202
    TBA6470.169451 x 8600.749114259
    TBA4470.212451 x 6800.893182387
    TBA2470.268451 x 6801.028276518
    TBA14190.298551 x 4801.149356652
    TBA1/04190.336551 x 4801.241439764
    TBA2/04190.376551 x 4801.338542896
    6722513/04160.422551 x 4801.4466781177
    5837274/04190.474551 x 2801.5728681406
    5821232504220.520651 x 11101.78910311745
    6722523004210.569651 x 21101.93312041995
    5821243504350.615651 x 1/01102.04514322327
    5785374004350.659651 x 11102.12416012520
    5821214004350.659651 x 3/01102.23716812615
    5785365004350.735651 x 11102.31019822972
    5821255004350.735651 x 2/01102.35020293096
    5965495004350.735651 x 3/01102.43420623210
    6650385004350.735651 x 4/0 GG1102.44021043173
    5821265004350.735651 x 2501102.46721403327
    5822506004580.812801 x 4/01102.69524843837
    5821276004580.812801 x 3501102.71826163998
    5785387504580.908801 x 1/01402.85829544296
    TBA9004610.999801 x 1/01403.08735154896
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    TBA842.73161.0721.2900.0523236
    TBA643.05030.6740.8120.0514044
    TBA443.68010.4240.5100.0485260
    TBA245.112740.2670.3210.0457280
    TBA145.716060.2110.2540.0468092
    TBA1/046.220270.1680.2010.04496108
    TBA2/046.725550.1330.1600.043108120
    6722513/047.232210.1050.1260.042124140
    5837274/047.940620.0840.1000.041144164
    58212325048.948000.0710.0860.041164184
    67225230049.757600.0590.0710.041184208
    582124350412.367200.0500.0620.040200224
    578537400412.776800.0440.0540.040216244
    582121400413.476800.0440.0540.040216244
    578536500413.996000.0350.0440.039248280
    582125500414.196000.0350.0440.039248280
    596549500414.696000.0350.0440.039248280
    665038500414.696000.0350.0440.039248280
    582126500414.896000.0350.0440.039248280
    582250600416.2115200.0290.0370.039272308
    582127600416.3115200.0290.0370.039272308
    578538750417.1144000.0240.0310.038308348
    TBA900418.5172800.0200.0270.037340384
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.005

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC