SPEC 45054

CU 600V XLPE Insulation Thermoplastic LSZH-TP Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2 for cables 14 AWG or larger, 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. 16 AWG wire is made in accordance with UL 66 Fixture Wire. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 66 Fixture Wire
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    For 16 AWG:
    SOUTHWIRE {UL} AWG XX 7 CDRS TYPE TC-ER XLPE CDRS SOLONON 90C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    For 14 AWG and larger:
    SOUTHWIRE {UL} AWG XX 7 CDRS TYPE TC-ER XHHW-2 CDRS SOLONON 90C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    TBA!167725450.416561124.1815.2820.0361.6-12
    14 AWG
    561312142730450.34925672.6313.1700.0581.42025
    890159143730450.37338932.6313.1700.0581.52025
    561313144730450.402511112.6313.1700.0581.61620
    563383145730450.443641352.6313.1700.0581.81620
    561314147730450.478891712.6313.1700.0581.91417
    TBA146730450.482891572.6313.1700.0581.91620
    TBA148730600.5521152122.6313.1700.0582.21417
    561315149730600.5871152332.6313.1700.0582.31417
    5975241410730600.6491272622.6313.1700.0582.61012
    5631941419730600.7742424402.6313.1700.0583.11012
    TBA1420730600.8122684552.6313.1700.0583.21012
    TBA1425730800.9423325912.6313.1700.0583.8911
    TBA1430730800.9953966882.6313.1700.0584.0911
    12 AWG
    574615122730450.38440891.6622.0020.0541.52530
    890122123730450.412611211.6622.0020.0541.62530
    561319124730450.445811521.6622.0020.0541.82024
    574612125730450.4871011801.6622.0020.0541.92024
    TBA126730600.5661422371.6622.0020.0542.32024
    574613127730600.5671422571.6622.0020.0542.31721
    TBA128730600.6121822941.6622.0020.0542.41721
    TBA129730600.6562033261.6622.0020.0542.61721
    TBA1210730600.7142233591.6622.0020.0542.91215
    5746141212730600.7322444111.6622.0020.0542.91215
    TBA1215730600.8193255021.6622.0020.0543.31215
    TBA1220730800.9484266791.6622.0020.0543.81215
    TBA1225730801.0505288261.6622.0020.0545.31113
    TBA1230730801.1116309671.6622.0020.0545.61113
    TBA1237730801.19877211631.6622.0020.0546.01012
    10 AWG
    577144103730450.472971691.0401.2530.0501.93540
    566720104730450.5471292351.0401.2530.0502.22832
    TBA105730600.5891932911.0401.2530.0502.42832
    TBA106730600.6412263371.0401.2530.0502.62832
    TBA107730600.6412583761.0401.2530.0502.62428
    TBA108730600.6952904211.0401.2530.0502.82428
    TBA1010730600.8143555141.0401.2530.0503.31720
    5746191012730800.9043886401.0401.2530.0503.61720
    TBA1015730800.9775177641.0401.2530.0503.91720
    TBA1019730801.0276469291.0401.2530.0505.11720
    TBA1020730801.0816789761.0401.2530.0505.41720
    TBA1025730801.20084011931.0401.2530.0506.01518
    TBA1030730801.271100214011.0401.2530.0506.41518
    TBA1037730801.373122816931.0401.2530.0506.91416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    ! not UL listed
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.008

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC