SPEC 45351
CU 600/1000V XLPE Insulation ARMOR-X® PVC Jacket XHHW-2. VFD Cable - CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC-HL Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with 3 Bare CU Ground

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Filler: Polypropylene filler
- Binder:Polypropylene tape
- Armor:ARMOR-X® Continuous Corrugated Welded Armor
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE ARMOR-X® {UL} TYPE MC-HL 3/C XXX KCMIL (XXX{mm2}) CU XHHW-2 GW 3 X X AWG 90°C JACKET -40°C SUN. RES. DIR. BUR. FOR CT USE 600V IEEE1202/FT4 -- {CSA} RA90-HL AG14 XLPE -40°C 600V FT4 SR 90°C -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 -- VFD USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | ||
550593◊ | 8 | 3 | 7 | 0.141 | 45 | 3 x 14 | 0.750 | 50 | 0.856 | 192 | 407 |
890513◊ | 6 | 3 | 7 | 0.177 | 45 | 3 x 12 | 0.840 | 50 | 0.946 | 306 | 547 |
890514◊ | 4 | 3 | 7 | 0.225 | 45 | 3 x 12 | 0.920 | 50 | 1.026 | 449 | 714 |
890515◊ | 2 | 3 | 7 | 0.282 | 45 | 3 x 10 | 1.060 | 50 | 1.166 | 717 | 1070 |
890516◊ | 1/0 | 3 | 19 | 0.361 | 55 | 3 x 10 | 1.350 | 50 | 1.456 | 1085 | 1745 |
890517◊ | 2/0 | 3 | 19 | 0.405 | 55 | 3 x 10 | 1.470 | 50 | 1.576 | 1342 | 1935 |
890518 | 3/0 | 3 | 19 | 0.456 | 55 | 3 x 8 | 1.540 | 60 | 1.666 | 1724 | 2420 |
890519◊ | 4/0 | 3 | 19 | 0.512 | 55 | 3 x 8 | 1.590 | 60 | 1.716 | 2134 | 2837 |
890520◊ | 250 | 3 | 37 | 0.558 | 65 | 3 x 8 | 1.845 | 60 | 1.971 | 2493 | 3351 |
890521◊ | 350 | 3 | 37 | 0.661 | 65 | 3 x 6 | 2.040 | 60 | 2.166 | 3520 | 4535 |
890522◊ | 500 | 3 | 37 | 0.789 | 65 | 3 x 6 | 2.290 | 75 | 2.448 | 4923 | 5990 |
646751 | 600 | 3 | 61 | 0.865 | 80 | 3 x 6 | 2.670 | 75 | 2.828 | 5858 | 7243 |
890523◊ | 750 | 3 | 61 | 0.968 | 80 | 3 x 4 | 3.000 | 75 | 3.158 | 7406 | 9645 |
TBA | 1000 | 3 | 61 | 1.117 | 80 | 3 x 4 | 3.220 | 85 | 3.390 | 9673 | 11993 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Amp | Amp | ||
550593◊ | 8 | 3 | 6.0 | 396 | 0.653 | 0.786 | 0.033 | 0.052 | 50 | 55 |
890513◊ | 6 | 3 | 6.6 | 629 | 0.411 | 0.495 | 0.027 | 0.051 | 65 | 75 |
890514◊ | 4 | 3 | 7.2 | 1001 | 0.258 | 0.310 | 0.022 | 0.048 | 85 | 95 |
890515◊ | 2 | 3 | 8.2 | 1592 | 0.162 | 0.195 | 0.018 | 0.045 | 115 | 130 |
890516◊ | 1/0 | 3 | 10.2 | 2534 | 0.102 | 0.122 | 0.017 | 0.044 | 150 | 170 |
890517◊ | 2/0 | 3 | 11.0 | 3194 | 0.081 | 0.097 | 0.016 | 0.043 | 175 | 195 |
890518 | 3/0 | 3 | 11.7 | 4027 | 0.064 | 0.078 | 0.014 | 0.042 | 200 | 225 |
890519◊ | 4/0 | 3 | 12.0 | 5078 | 0.051 | 0.062 | 0.013 | 0.041 | 230 | 260 |
890520◊ | 250 | 3 | 13.8 | 6000 | 0.043 | 0.053 | 0.014 | 0.041 | 255 | 290 |
890521◊ | 350 | 3 | 15.2 | 8400 | 0.031 | 0.039 | 0.012 | 0.040 | 310 | 350 |
890522◊ | 500 | 3 | 17.1 | 12000 | 0.022 | 0.029 | 0.010 | 0.039 | 380 | 430 |
646751 | 600 | 3 | 19.8 | 14400 | 0.018 | 0.025 | 0.011 | 0.039 | 420 | 475 |
890523◊ | 750 | 3 | 22.1 | 18000 | 0.014 | 0.022 | 0.010 | 0.038 | 475 | 535 |
TBA | 1000 | 3 | 23.7 | 24000 | 0.011 | 0.018 | 0.009 | 0.037 | 545 | 615 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.012
Updated On: Dec. 31, 2024, 11:07 p.m. UTC