SPEC 45301
CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.
Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} 3/C (1 AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | ||
606939 | 8 | 3 | 7 | 0.141 | 45 | 1 x 10 | 0.721 | 50 | 0.821 | 186 | 404 |
606947 | 6 | 3 | 7 | 0.177 | 45 | 1 x 8 | 0.788 | 50 | 0.888 | 297 | 545 |
606954◊ | 4 | 3 | 7 | 0.225 | 45 | 1 x 8 | 0.898 | 50 | 0.998 | 441 | 713 |
671892 | 3 | 3 | 7 | 0.252 | 45 | 1 x 6 | 0.945 | 50 | 1.045 | 574 | 891 |
560466◊ | 2 | 3 | 7 | 0.282 | 45 | 1 x 6 | 1.019 | 50 | 1.119 | 702 | 1046 |
550801 | 1 | 3 | 19 | 0.322 | 55 | 1 x 6 | 1.151 | 50 | 1.251 | 864 | 1264 |
560474◊ | 1/0 | 3 | 19 | 0.361 | 55 | 1 x 6 | 1.233 | 50 | 1.333 | 1069 | 1499 |
560482◊ | 2/0 | 3 | 19 | 0.405 | 55 | 1 x 6 | 1.328 | 50 | 1.428 | 1326 | 1816 |
890339◊ | 3/0 | 3 | 19 | 0.456 | 55 | 1 x 4 | 1.436 | 50 | 1.536 | 1699 | 2256 |
383679◊ | 4/0 | 3 | 19 | 0.512 | 55 | 1 x 4 | 1.631 | 60 | 1.751 | 2109 | 2786 |
601377 | 250 | 3 | 37 | 0.558 | 65 | 1 x 4 | 1.769 | 60 | 1.889 | 2469 | 3379 |
383646◊ | 350 | 3 | 37 | 0.661 | 65 | 1 x 3 | 1.983 | 60 | 2.103 | 3438 | 4551 |
380618◊ | 500 | 3 | 37 | 0.789 | 65 | 1 x 2 | 2.253 | 75 | 2.403 | 4884 | 6180 |
582274 | 500 | 3 | 37 | 0.789 | 65 | 1 x 4/0 | 2.341 | 75 | 2.491 | 5337 | 6691 |
890391 | 600 | 3 | 61 | 0.865 | 80 | 1 x 4/0 | 2.507 | 75 | 2.657 | 6272 | 7604 |
890405 | 750 | 3 | 61 | 0.968 | 80 | 1 x 1 | 2.758 | 75 | 2.908 | 7277 | 9227 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Amp | Amp | ||
606939 | 8 | 3 | 5.7 | 396 | 0.653 | 0.786 | 0.033 | 0.052 | 50 | 55 |
606947 | 6 | 3 | 6.2 | 629 | 0.411 | 0.495 | 0.027 | 0.051 | 65 | 75 |
606954◊ | 4 | 3 | 7.0 | 1001 | 0.258 | 0.310 | 0.022 | 0.048 | 85 | 95 |
671892 | 3 | 3 | 7.3 | 1262 | 0.205 | 0.246 | 0.020 | 0.047 | 100 | 115 |
560466◊ | 2 | 3 | 7.8 | 1592 | 0.162 | 0.195 | 0.018 | 0.045 | 115 | 130 |
550801 | 1 | 3 | 8.8 | 2008 | 0.128 | 0.154 | 0.019 | 0.046 | 130 | 145 |
560474◊ | 1/0 | 3 | 9.3 | 2534 | 0.102 | 0.122 | 0.017 | 0.044 | 150 | 170 |
560482◊ | 2/0 | 3 | 10.0 | 3194 | 0.081 | 0.097 | 0.016 | 0.043 | 175 | 195 |
890339◊ | 3/0 | 3 | 10.8 | 4027 | 0.064 | 0.078 | 0.014 | 0.042 | 200 | 225 |
383679◊ | 4/0 | 3 | 12.3 | 5078 | 0.051 | 0.062 | 0.013 | 0.041 | 230 | 260 |
601377 | 250 | 3 | 13.2 | 6000 | 0.043 | 0.053 | 0.014 | 0.041 | 255 | 290 |
383646◊ | 350 | 3 | 14.7 | 8400 | 0.031 | 0.039 | 0.012 | 0.040 | 310 | 350 |
380618◊ | 500 | 3 | 16.8 | 12000 | 0.022 | 0.029 | 0.010 | 0.039 | 380 | 430 |
582274 | 500 | 3 | 17.4 | 12000 | 0.022 | 0.029 | 0.010 | 0.039 | 380 | 430 |
890391 | 600 | 3 | 18.6 | 14400 | 0.018 | 0.025 | 0.011 | 0.039 | 420 | 475 |
890405 | 750 | 3 | 20.4 | 18000 | 0.014 | 0.022 | 0.010 | 0.038 | 475 | 535 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.006
Updated On: Dec. 31, 2024, 11:07 p.m. UTC