SPEC 44030

1/C CU EPR Medium Voltage Non-Shielded Jumper & Switchgear Cable

Single Conductor Flexible Conductor with an EPR Insulation Non-Shielded Jumper Cable

...

Construction:

  1. Conductor:Flexible rope lay stranded annealed bare or tinned copper
  2. Conductor Shield:Nylon semi-conducting tape, helically applied
  3. Insulation:Heat, moisture, and ozone resistant Ethylene Propylene Rubber(EPR)

Applications and Features:

Southwire’s medium voltage non-shielded jumper and switchgear cable is a flexible power cable that is intended for use in substations installed on insulators and inside switchgear isolated from ground and where a non-shielded flexible cable is desired. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C.

This cable is rated up to 40KV and is not UL listed. See Table 2 for installation guidelines

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • Sample Print Legend:

    SOUTHWIRE® XXX SIZE NON-SHIELDED FLEXIBLE JUMPER AND SWITCHGEAR CABLE NON-UL
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    56942421680.2902100.753169177
    58752922590.3152000.770169424
    5694231/02590.3792100.840320548
    5694252/03240.4002200.883406674
    5694874/05320.5302100.979651960
    6743224/05320.5303601.2806381244
    5694273508930.6702301.16010841475
    56942850012210.8582301.35015141970
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities based upon 2023 NEC Table 310.16. Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmillbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    56942425300.1720.2070.045115130
    58752925300.1720.2070.045115130
    5694231/08440.1090.1310.044150170
    5694252/010640.0870.1040.043175195
    5694874/016920.0550.0670.041230260
    6743224/016920.0550.0670.041230260
    56942735028000.0330.0420.040310350
    56942850040000.0230.0310.039380430

    Revision: 1.000.004

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC