SPEC 22068

SIMpull® RWU90 Aluminum 1000 Volt

Single 8000 Series Aluminum Conductor, 1000V Alumaflex Strand, No. 6 AWG to 1000 Kcmil, 90°C MAX -40°C MIN, Sunlight Resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801 or Single Input Wire (SIW) Compact AL per ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Southwire’s RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground. The minimum recommended installation temperature is minus 40°C (with suitable handling procedures). Maximum conductor temperature is 90°C. Note: Standard black is sunlight resistant and marked "SR". Standard coloured insulation is not sunlight resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE{R} LL90458 {CSA} XXX AWG (XX.X{mm2}) COMPACT AL. --- {ALUMAFLEX}{R} AA8176 RWU90 XLPE 1000 VOLTS -40{D}C SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    661721◊6780RD0.339561.41570.6740.840.05155
    568942◊6780BK0.339561.41570.6740.840.05155
    568943◊4780BK0.383761.52500.4240.5280.04875
    662964◊4780WE0.383761.52500.4240.5280.04875
    568944◊2680BK0.4381061.83980.2660.3310.045100
    568945◊11895BK0.49913025020.2110.2630.046115
    568794◊1/01895BK0.5261532.16330.1670.2080.044135
    662482◊1/01895BK0.5361622.16330.1670.2080.044135
    570875◊2/01295BK0.5761872.37980.1330.1660.043150
    663133◊2/01295BK0.5761952.37980.1330.1660.043150
    570772◊3/01695BK0.6232272.510060.1050.1310.042175
    663134◊3/01595BK0.6232342.510060.1050.1310.042175
    568793◊4/01995BK0.6752752.712690.0840.1050.041205
    663135◊4/01995BK0.6752842.712690.0840.1050.041205
    568792◊25022110BK0.74326315000.070.0870.041230
    663136◊25022110BK0.752342315000.070.0870.041230
    665531◊35035110BK0.8484533.421000.0510.0640.04280
    568791◊35035110BK0.8484413.421000.0510.0640.04280
    665428◊40035110BK0.8915083.624000.0440.0550.04305
    665429◊50034110BK0.9686163.930000.0360.0450.039350
    568789◊50034110BK0.976023.930000.0360.0450.039350
    593373◊60037125BK1.0777475.436000.030.0380.039385
    138703◊75061125BK1.1729075.945000.0230.030.038435
    568788◊75061125BK1.1728885.945000.0230.030.038435
    604121◊100058125BK1.32411536.660000.0170.0230.037500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    661721◊672.03RD8.618335.566992.212.760.167355
    568942◊672.03BK8.618335.566992.212.760.167355
    568943◊472.03BK9.7311338.1011131.391.730.157575
    662964◊472.03WE9.7311338.1011131.391.730.157575
    568944◊262.03BK11.1315845.7217710.871.090.1476100
    568945◊1182.41BK12.6719350.8022340.690.860.1509115
    568794◊1/0182.41BK13.3622853.3428170.550.680.1444135
    662482◊1/0182.41BK13.6124153.3428170.550.680.1444135
    570875◊2/0122.41BK14.6327858.4235510.440.540.1411150
    663133◊2/0122.41BK14.6329058.4235510.440.540.1411150
    570772◊3/0162.41BK15.8233863.5044770.340.430.1378175
    663134◊3/0152.41BK15.8234863.5044770.340.430.1378175
    568793◊4/0192.41BK17.1540968.5856470.280.340.1345205
    663135◊4/0192.41BK17.1542368.5856470.280.340.1345205
    568792◊250222.79BK18.8048576.2066750.230.290.1345230
    663136◊250222.79BK19.1050976.2066750.230.290.1345230
    665531◊350352.79BK21.5467486.3693450.170.210.1312280
    568791◊350352.79BK21.5465686.3693450.170.210.1312280
    665428◊400352.79BK22.6375691.44106800.140.180.1312305
    665429◊500342.79BK24.5991799.06133500.120.150.1280350
    568789◊500342.79BK24.6489699.06133500.120.150.1280350
    593373◊600373.18BK27.361112137.16160200.100.120.1280385
    138703◊750613.18BK29.771350149.86200250.080.100.1247435
    568788◊750613.18BK29.771321149.86200250.080.100.1247435
    604121◊1000583.18BK33.631716167.64267000.060.080.1214500
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM

    Revision: 1.000.013

    Updated On: May 5, 2026, 6:35 p.m. UTC