SPEC 22064

1/C CU 1000V RWU90

Single Copper Conductors, XLPE Insulation, 1000V / -40ºC MIN, 90ºC MAX, Sunlight Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Southwire’s RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground. The minimum recommended installation temperature is minus 40°C (with suitable handling procedures). Maximum conductor temperature is 90°C. Note: Standard black is sunlight resistant and marked "SR". Standard coloured insulation is not sunlight resistant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA AWM I A/B FT1
  • Sample Print Legend:

    SOUTHWIRE® LL90458 {CSA} XXX AWG (XXX{mm2}) CU RWU90 XLPE 1000 VOLTS -40°C SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    556979127600.217340.8521.6622.0020.05430
    556983107600.239480.9831.041.2530.0540
    61668267800.3461101.32090.4110.4950.05175
    60661927800.4512471.85300.1620.1950.045130
    556378119950.52231326690.1280.1540.046145
    5563791/019950.5523832.28440.1020.1220.044170
    5563802/019950.5964802.310640.0810.0970.043195
    5563823/019950.6545912.613420.0640.0780.042225
    5563834/019950.717442.816920.0510.0620.041260
    578307250371100.7788673.120000.0430.0530.041290
    575227350371100.88111913.528000.0310.0390.04350
    577680500371101.0091673540000.0220.0290.039430
    577681600611251.1320195.648000.0180.0250.039475
    577682750611251.2182489660000.0140.0220.038535
    5776831000611251.36732856.880000.0110.0190.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2021 Canadian Electrical Code Table 1 for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 °C)
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    5569791271.525.515120.322315.456.570.177230
    5569831071.526.077122.863693.414.110.164040
    616682672.038.7916433.029301.351.620.167375
    606619272.0311.4636845.7223590.530.640.1476130
    5563781192.4113.2646650.8029770.420.510.1509145
    5563791/0192.4114.0257055.8837560.330.400.1444170
    5563802/0192.4115.1471458.4247350.270.320.1411195
    5563823/0192.4116.6188066.0459720.210.260.1378225
    5563834/0192.4118.03110771.1275290.170.200.1345260
    578307250372.7919.76129078.7489000.140.170.1345290
    575227350372.7922.38177288.90124600.100.130.1312350
    577680500372.7925.632490127.00178000.070.100.1280430
    577681600613.1828.703005142.24213600.060.080.1280475
    577682750613.1830.943704152.40267000.050.070.1247535
    5776831000613.1834.724889172.72356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2021 Canadian Electrical Code Table 1 for not more than three insulated copper conductors, rated not more than 5000 V and unshielded, in raceway or cable (based on an ambient temperature of 30 °C)

    Color Code

    Cond. Size (Strand)Stock Number (Color)
    GreenWhiteRedBlueYellowOrangeBrownGrayPurple
    14 (7)578364563253646740647607566577
    12 (7)556980556982556981556600580822556601556602556603556604
    10 (7)556598556984556986556987579338
    6 (7)604517604516587595
    3 (7)585016
    1/0 (19)557008
    2/0 (19)578090557010
    3/0 (19)557011
    4/0 (19)583440557012