SPEC 22061

RW90 Copper Circuit Sizes (14, 12 & 10 AWG)

Copper Conductor, 600V, 90°C MAX, -40°C MIN. Sunlight Resistant in Black Only.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant in black only. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA SUN RES - for Sunlight Resistant rating
  • Sample Print Legend:

    SOUTHWIRE& LL90458 (CSA) 12 AWG CU RW90 XLPE 600 VOLTS (-40°C) SR
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    95611014Solid30BK0.128160.500322.6313.1700.05825
    95617714Solid30RD0.128160.500322.6313.1700.05825
    55791714Solid30OE0.128160.500322.6313.1700.05825
    95614414Solid30WE0.128160.500322.6313.1700.05825
    95625014Solid30BN0.128160.500322.6313.1700.05825
    95623514Solid30BE0.128160.500322.6313.1700.05825
    95620114Solid30GN0.128160.500322.6313.1700.05825
    95627614Solid30YW0.128160.500322.6313.1700.05825
    95566614730BE0.135170.500322.6313.1700.05825
    95524514730RD0.135170.500322.6313.1700.05825
    95561714730GN0.135170.500322.6313.1700.05825
    95570814730YW0.135170.500322.6313.1700.05825
    95173114730BK0.135170.500322.6313.1700.05825
    55792414730OE0.135170.500322.6313.1700.05825
    95568214730BN0.135170.500322.6313.1700.05825
    95535114730WE0.135170.5322.6313.1700.05825
    95622712Solid30BE0.144240.600521.6622.0020.05430
    95624312Solid30BN0.144240.600521.6622.0020.05430
    95616912Solid30RD0.144240.600521.6622.0020.05430
    95610212Solid30BK0.144240.600521.6622.0020.05430
    95626812Solid30YW0.144240.600521.6622.0020.05430
    95613612Solid30WE0.144240.600521.6622.0020.05430
    95619312Solid30GN0.144240.600521.6622.0020.05430
    55786112Solid30OE0.144240.600521.6622.0020.05430
    95569012730YW0.153250.600521.6622.0020.05430
    95174912730BK0.153250.600321.6622.0020.05430
    95565812730BE0.153250.600521.6622.0020.05430
    95567412730BN0.153250.600521.6622.0020.05430
    95523712730RD0.153250.600521.6622.0020.05430
    55792312730OE0.153250.600521.6622.0020.05430
    95560912730GN0.153250.600521.6622.0020.05430
    95534412730WE0.153250.6521.6622.0020.05430
    55793110Solid30YW0.165370.700831.0401.2530.05040
    95621910Solid30BE0.165370.700831.0401.2530.05040
    95618510Solid30GN0.165370.700831.0401.2530.05040
    95612810Solid30WE0.165370.700831.0401.2530.05040
    55792910Solid30BN0.165370.700831.0401.2530.05040
    95609410Solid30BK0.165370.700831.0401.2530.05040
    55793010Solid30OE0.165370.700831.0401.2530.05040
    95615110Solid30RD0.165370.700831.0401.2530.05040
    95175610730BK0.175380.700521.0401.2530.05040
    95559110730GN0.177390.700831.0401.2530.05040
    55792110730OE0.177390.700831.0401.2530.05040
    95564110730BE0.177390.700831.0401.2530.05040
    55792010730BN0.177390.700831.0401.2530.05040
    55792210730YW0.177390.700831.0401.2530.05040
    95522910730RD0.177390.700831.0401.2530.05040
    95533610730WE0.177390.7831.0401.2530.05040
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessInsulation ColorApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    95611014Solid0.76BK3.252412.701428.6310.400.190325
    95617714Solid0.76RD3.252412.701428.6310.400.190325
    55791714Solid0.76OE3.252412.701428.6310.400.190325
    95614414Solid0.76WE3.252412.701428.6310.400.190325
    95625014Solid0.76BN3.252412.701428.6310.400.190325
    95623514Solid0.76BE3.252412.701428.6310.400.190325
    95620114Solid0.76GN3.252412.701428.6310.400.190325
    95627614Solid0.76YW3.252412.701428.6310.400.190325
    9556661470.76BE3.432512.701428.6310.400.190325
    9552451470.76RD3.432512.701428.6310.400.190325
    9556171470.76GN3.432512.701428.6310.400.190325
    9557081470.76YW3.432512.701428.6310.400.190325
    9517311470.76BK3.432512.701428.6310.400.190325
    5579241470.76OE3.432512.701428.6310.400.190325
    9556821470.76BN3.432512.701428.6310.400.190325
    9553511470.76WE3.432512.701428.6310.400.190325
    95622712Solid0.76BE3.663615.242315.456.570.177230
    95624312Solid0.76BN3.663615.242315.456.570.177230
    95616912Solid0.76RD3.663615.242315.456.570.177230
    95610212Solid0.76BK3.663615.242315.456.570.177230
    95626812Solid0.76YW3.663615.242315.456.570.177230
    95613612Solid0.76WE3.663615.242315.456.570.177230
    95619312Solid0.76GN3.663615.242315.456.570.177230
    55786112Solid0.76OE3.663615.242315.456.570.177230
    9556901270.76YW3.893715.242315.456.570.177230
    9517491270.76BK3.893715.241425.456.570.177230
    9556581270.76BE3.893715.242315.456.570.177230
    9556741270.76BN3.893715.242315.456.570.177230
    9552371270.76RD3.893715.242315.456.570.177230
    5579231270.76OE3.893715.242315.456.570.177230
    9556091270.76GN3.893715.242315.456.570.177230
    9553441270.76WE3.893715.242315.456.570.177230
    55793110Solid0.76YW4.195517.783693.414.110.164040
    95621910Solid0.76BE4.195517.783693.414.110.164040
    95618510Solid0.76GN4.195517.783693.414.110.164040
    95612810Solid0.76WE4.195517.783693.414.110.164040
    55792910Solid0.76BN4.195517.783693.414.110.164040
    95609410Solid0.76BK4.195517.783693.414.110.164040
    55793010Solid0.76OE4.195517.783693.414.110.164040
    95615110Solid0.76RD4.195517.783693.414.110.164040
    9517561070.76BK4.445717.782313.414.110.164040
    9555911070.76GN4.505817.783693.414.110.164040
    5579211070.76OE4.505817.783693.414.110.164040
    9556411070.76BE4.505817.783693.414.110.164040
    5579201070.76BN4.505817.783693.414.110.164040
    5579221070.76YW4.505817.783693.414.110.164040
    9552291070.76RD4.505817.783693.414.110.164040
    9553361070.76WE4.505817.783693.414.110.164040
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    †Ampacities derived from the 2015 Canadian Electrical Code - Table 1 - For single conductor in free air and based on an ambient temperature of 30°C. - Table 2 - for Cable in Conduit. Not more than 3 aluminum conductors in a conduit and based on an ambient temperature of 30°C.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Table 3 - Stock Code Colors

    Size (Strand)BlackRedBlueWhiteBrownOrangeYellowGreen
    14 (Solid)956110956177956235956144956250557917956276956201
    14 (7)951731955245955666955351955682557924955708955617
    12 (Solid)956102956169956227956136956243557861956268956193
    12 (7)951749955237955658955344955674557923955690955609
    10 (Solid)956094956151956219956128557929557930557931956185
    10 (7)951756955229955641955336557920557921557922955591

    Revision: 1.000.017

    Updated On: Oct. 20, 2025, 1:45 p.m. UTC