ACSS
Aluminum Conductor, Steel Supported. Bare.
![...](https://d3sx0rvep9h73z.cloudfront.net/cable_image/SPEC80110.png)
Construction:
- Core:Steel strands form the central core of the conductor with two or more layers of aluminum 1350-O wire stranded around it.
- Stranding:ACSS is a composite concentric-lay stranded conductor.
- The steel core carries most or all of the mechanical load of the conductor due to the “O” temper (fully annealed or soft) aluminum.
- Steel core wires are protected from corrosion by a zinc-5% aluminum-mischmetal alloy coating.
- For aluminum-clad (AW) ACSS, please refer to the ACSS/AW catalog sheet.
Applications and Features:
Specifications:
Code Word | Size | Stranding | AL Strand Dia | Steel Strand Dia | Steel Core | Comp Cable | AL Weight | Steel Weight | Overall Weight |
---|---|---|---|---|---|---|---|---|---|
(AWG or kcmil) | (Al/Stl) | inch | inch | inch | inch | lbs/1,000' | lbs/1,000' | lbs/1,000' | |
Partridge/ACSS | 266.8 | 26/7 | 0.1013 | 0.0788 | 0.2363 | 0.642 | 251.3 | 115.5 | 366.8 |
Junco/ACSS | 266.8 | 30/7 | 0.0943 | 0.0943 | 0.2829 | 0.66 | 251.9 | 165.5 | 417.4 |
Ostrich/ACSS | 300 | 26/7 | 0.1074 | 0.0835 | 0.2506 | 0.68 | 282.6 | 129.9 | 412.5 |
Linnet/ACSS | 336.4 | 26/7 | 0.1137 | 0.0885 | 0.2654 | 0.72 | 316.8 | 145.7 | 462.5 |
Oriole/ACSS | 336.4 | 30/7 | 0.1059 | 0.1059 | 0.3177 | 0.741 | 317.6 | 208.7 | 526.3 |
Brant/ACSS | 397.5 | 24/7 | 0.1287 | 0.0858 | 0.2574 | 0.772 | 374.4 | 137 | 511.4 |
Ibis/ACSS | 397.5 | 26/7 | 0.1236 | 0.0962 | 0.2885 | 0.783 | 374.4 | 172.1 | 546.5 |
Lark/ACSS | 397.5 | 30/7 | 0.1151 | 0.1151 | 0.3453 | 0.806 | 375.3 | 246.5 | 621.8 |
Flicker/ACSS | 477 | 24/7 | 0.141 | 0.094 | 0.2819 | 0.846 | 449.3 | 164.4 | 613.7 |
Hawk/ACSS | 477 | 26/7 | 0.1354 | 0.1053 | 0.316 | 0.858 | 449.3 | 206.5 | 655.8 |
Hen/ACSS | 477 | 30/7 | 0.1261 | 0.1261 | 0.3783 | 0.883 | 450.4 | 295.9 | 746.3 |
Parakeet/ACSS | 556.5 | 24/7 | 0.1523 | 0.1015 | 0.3045 | 0.914 | 524 | 192 | 716 |
Dove/ACSS | 556.5 | 26/7 | 0.1463 | 0.1138 | 0.3413 | 0.927 | 524.2 | 240.9 | 765.1 |
Eagle/ACSS | 556.5 | 30/7 | 0.1362 | 0.1362 | 0.4086 | 0.953 | 525.4 | 345.2 | 870.6 |
Peacock/ACSS | 605 | 24/7 | 0.1588 | 0.1058 | 0.3175 | 0.953 | 569.8 | 208.5 | 778.3 |
Squab/ACSS | 605 | 26/7 | 0.1525 | 0.1186 | 0.3559 | 0.966 | 569.8 | 261.9 | 831.7 |
Wood Duck/ACSS | 605 | 30/7 | 0.142 | 0.142 | 0.426 | 0.994 | 571.2 | 375.3 | 946.5 |
Teal/ACSS | 605 | 30/19 | 0.142 | 0.0852 | 0.426 | 0.994 | 571.2 | 367.4 | 938.6 |
Rook/ACSS | 636 | 24/7 | 0.1628 | 0.1085 | 0.3256 | 0.977 | 599 | 219.2 | 818.2 |
Grosbeak/ACSS | 636 | 26/7 | 0.1564 | 0.1216 | 0.3649 | 0.991 | 599 | 275.4 | 874.4 |
Scoter/ACSS | 636 | 30/7 | 0.1456 | 0.1456 | 0.4368 | 1.019 | 600.5 | 394.5 | 995 |
Egret/ACSS | 636 | 30/19 | 0.1456 | 0.0874 | 0.4368 | 1.019 | 600.5 | 386.3 | 986.8 |
Flamingo/ACSS | 666.6 | 24/7 | 0.1667 | 0.1111 | 0.3333 | 1 | 627.9 | 229.7 | 857.6 |
Gannet/ACSS | 666.6 | 26/7 | 0.1601 | 0.1245 | 0.3736 | 1.014 | 627.8 | 288.6 | 916.4 |
Stilt/ACSS | 715.5 | 24/7 | 0.1727 | 0.1151 | 0.3453 | 1.036 | 673.9 | 246.5 | 920.4 |
Starling/ACSS | 715.5 | 26/7 | 0.1659 | 0.129 | 0.3871 | 1.051 | 673.9 | 309.8 | 983.7 |
Redwing/ACSS | 715.5 | 30/19 | 0.1544 | 0.0927 | 0.4633 | 1.081 | 675.6 | 434.6 | 1110.2 |
Cuckoo/ACSS | 795 | 24/7 | 0.182 | 0.1213 | 0.364 | 1.092 | 748.8 | 274 | 1022.8 |
Drake/ACSS | 795 | 26/7 | 0.1749 | 0.136 | 0.408 | 1.107 | 748.8 | 344.2 | 1093 |
Macaw/ACSS | 795 | 42/7 | 0.1376 | 0.0764 | 0.2293 | 1.055 | 748.8 | 108.7 | 857.5 |
Tern/ACSS | 795 | 45/7 | 0.1329 | 0.0886 | 0.2658 | 1.063 | 748.8 | 146.1 | 894.9 |
Condor/ACSS | 795 | 54/7 | 0.1213 | 0.1213 | 0.364 | 1.092 | 748.8 | 274 | 1022.8 |
Mallard/ACSS | 795 | 30/19 | 0.1628 | 0.0977 | 0.4884 | 1.139 | 750.6 | 482.8 | 1233.4 |
Ruddy/ACSS | 900 | 45/7 | 0.1414 | 0.0943 | 0.2828 | 1.131 | 847.7 | 165.4 | 1012.1 |
Canary/ACSS | 900 | 54/7 | 0.1291 | 0.1291 | 0.3873 | 1.162 | 847.7 | 310.1 | 1157.8 |
Redbird/ACSS | 954 | 24/7 | 0.1994 | 0.1329 | 0.3987 | 1.196 | 898.5 | 328.7 | 1227.2 |
Rail/ACSS | 954 | 45/7 | 0.1456 | 0.0971 | 0.2912 | 1.165 | 898.5 | 175.3 | 1073.8 |
Towhee/ACSS | 954 | 48/7 | 0.141 | 0.1097 | 0.329 | 1.175 | 898.5 | 223.7 | 1122.2 |
Cardinal/ACSS | 954 | 54/7 | 0.1329 | 0.1329 | 0.3987 | 1.196 | 898.6 | 328.7 | 1227.2 |
Canvasback/ACSS | 954 | 30/19 | 0.1783 | 0.107 | 0.535 | 1.248 | 900.7 | 579.4 | 1480.1 |
Snowbird/ACSS | 1033.5 | 42/7 | 0.1569 | 0.0871 | 0.2614 | 1.203 | 973.4 | 141.3 | 1114.7 |
Ortolan/ACSS | 1033.5 | 45/7 | 0.1515 | 0.101 | 0.3031 | 1.212 | 973.4 | 190 | 1163.4 |
Curlew/ACSS | 1033.5 | 54/7 | 0.1383 | 0.1383 | 0.415 | 1.245 | 973.4 | 356.2 | 1329.6 |
Bluejay/ACSS | 1113 | 45/7 | 0.1573 | 0.1048 | 0.3145 | 1.258 | 1048.3 | 204.5 | 1252.8 |
Finch/ACSS | 1113 | 54/19 | 0.1436 | 0.0861 | 0.4307 | 1.292 | 1053.4 | 375.5 | 1428.9 |
Bunting/ACSS | 1192.5 | 45/7 | 0.1628 | 0.1085 | 0.3256 | 1.302 | 1123.2 | 219.2 | 1342.4 |
Bittern/ACSS | 1272 | 45/7 | 0.1681 | 0.1121 | 0.3363 | 1.345 | 1198 | 234 | 1432 |
Pheasant/ACSS | 1272 | 54/19 | 0.1535 | 0.0921 | 0.4604 | 1.381 | 1203.9 | 429.2 | 1633.1 |
Dipper/ACSS | 1351 | 45/7 | 0.1733 | 0.1155 | 0.3465 | 1.386 | 1272.5 | 248.3 | 1520.8 |
Martin/ACSS | 1351 | 54/19 | 0.1582 | 0.0949 | 0.4745 | 1.424 | 1278.7 | 455.8 | 1734.5 |
Bobolink/ACSS | 1431 | 45/7 | 0.1783 | 0.1189 | 0.3566 | 1.427 | 1347.8 | 263 | 1610.8 |
Plover/ACSS | 1431 | 54/19 | 0.1628 | 0.0977 | 0.4884 | 1.465 | 1354.4 | 482.8 | 1837.2 |
Nuthatch/ACSS | 1510 | 45/7 | 0.1832 | 0.1221 | 0.3664 | 1.465 | 1422.2 | 277.5 | 1699.7 |
Parrot/ACSS | 1510 | 54/19 | 0.1672 | 0.1003 | 0.5017 | 1.505 | 1429.2 | 509.5 | 1938.7 |
Ratite/ACSS | 1590 | 42/7 | 0.1946 | 0.1081 | 0.3243 | 1.492 | 1497.6 | 217.4 | 1715 |
Lapwing/ACSS | 1590 | 45/7 | 0.188 | 0.1253 | 0.3759 | 1.504 | 1497.6 | 292.2 | 1789.8 |
Falcon/ACSS | 1590 | 54/19 | 0.1716 | 0.103 | 0.5148 | 1.544 | 1504.9 | 536.5 | 2041.4 |
Chukar/ACSS | 1780 | 84/19 | 0.1456 | 0.0873 | 0.4367 | 1.601 | 1684.7 | 386.1 | 2070.8 |
Mockingbird/ACSS | 2034.5 | 72/7 | 0.1681 | 0.1121 | 0.3362 | 1.681 | 1925.6 | 233.7 | 2159.3 |
Roadrunner/ACSS | 2057 | 76/19 | 0.1645 | 0.0768 | 0.3839 | 1.7 | 1946.9 | 298.3 | 2245.2 |
Bluebird/ACSS | 2156 | 84/19 | 0.1602 | 0.0961 | 0.4806 | 1.762 | 2040.6 | 467.6 | 2508.2 |
Kiwi/ACSS | 2167 | 72/7 | 0.1735 | 0.1157 | 0.347 | 1.735 | 2051 | 248.9 | 2299.9 |
Thrasher/ACSS | 2312 | 76/19 | 0.1744 | 0.0814 | 0.407 | 1.802 | 2188.2 | 335.3 | 2523.5 |
Joree/ACSS | 2515 | 76/19 | 0.1819 | 0.0849 | 0.4245 | 1.88 | 2380.4 | 364.7 | 2745.1 |
(2) Resistance and Ampacity based on an aluminum conductivity of 63%, IACS at 20°C, and a steel conductivity of 8%, IACS at 20°C.
(3) Ampacity based on a 200°C conductor temperature, 25°C ambient temperature, 2ft/sec. wind, in sun, with an emissivity of 0.5 and a coefficient of solar absorption of 0.5, at sea level.
(4) Rated strength for standard strength core based on Class A Galfan coated steel core wire in accordance with ASTM B802.
(5) Rated strength for high strength core based on a Class A Galfan coated high strength steel core wire in accordance with B803.
Code Word | Size | Rated Strength | High Strength* | HS285** Strength | DC Resistance @ 20C | AC Resistance @ 75C | Ampacity @ 200°C |
---|---|---|---|---|---|---|---|
(AWG or kcmil) | lbs | lbs | lbs | Ohms/1,000' | Ohms/1,000' | Amps | |
Partridge/ACSS | 266.8 | 8880 | 9730 | 11400 | 0.0619 | 0.0761 | 812 |
Junco/ACSS | 266.8 | 11700 | 13000 | 15200 | 0.0615 | 0.0756 | 822 |
Ostrich/ACSS | 300 | 10000 | 10900 | 12800 | 0.0551 | 0.0677 | 877 |
Linnet/ACSS | 336.4 | 11200 | 12300 | 14400 | 0.0491 | 0.0604 | 945 |
Oriole/ACSS | 336.4 | 14800 | 16300 | 19100 | 0.0488 | 0.06 | 957 |
Brant/ACSS | 397.5 | 11000 | 12100 | 14100 | 0.0417 | 0.0514 | 1047 |
Ibis/ACSS | 397.5 | 13000 | 14200 | 16500 | 0.0416 | 0.0512 | 1054 |
Lark/ACSS | 397.5 | 17500 | 19300 | 22600 | 0.0413 | 0.0508 | 1068 |
Flicker/ACSS | 477 | 13000 | 14200 | 16400 | 0.0348 | 0.0429 | 1180 |
Hawk/ACSS | 477 | 15600 | 17100 | 19800 | 0.0346 | 0.0427 | 1188 |
Hen/ACSS | 477 | 21000 | 22700 | 26700 | 0.0344 | 0.0424 | 1204 |
Parakeet/ACSS | 556.5 | 15200 | 16600 | 19100 | 0.0298 | 0.0368 | 1306 |
Dove/ACSS | 556.5 | 18200 | 19900 | 23200 | 0.0297 | 0.0366 | 1315 |
Eagle/ACSS | 556.5 | 24500 | 26500 | 31100 | 0.0295 | 0.0363 | 1331 |
Peacock/ACSS | 605 | 16500 | 18100 | 20800 | 0.0274 | 0.0339 | 1379 |
Squab/ACSS | 605 | 19700 | 21300 | 25200 | 0.0273 | 0.0337 | 1389 |
Wood Duck/ACSS | 605 | 26000 | 28300 | 33300 | 0.0271 | 0.0334 | 1407 |
Teal/ACSS | 605 | 26600 | 29300 | 34800 | 0.0272 | 0.0335 | 1406 |
Rook/ACSS | 636 | 17300 | 19000 | 21900 | 0.0261 | 0.0322 | 1425 |
Grosbeak/ACSS | 636 | 20700 | 22400 | 26000 | 0.026 | 0.0321 | 1435 |
Scoter/ACSS | 636 | 27400 | 29700 | 35000 | 0.0258 | 0.0318 | 1454 |
Egret/ACSS | 636 | 28000 | 30900 | 36600 | 0.0258 | 0.0319 | 1453 |
Flamingo/ACSS | 666.6 | 18200 | 19900 | 22900 | 0.0249 | 0.0308 | 1470 |
Gannet/ACSS | 666.6 | 21700 | 23400 | 27300 | 0.0248 | 0.0306 | 1480 |
Stilt/ACSS | 715.5 | 19500 | 21300 | 24600 | 0.0232 | 0.0287 | 1540 |
Starling/ACSS | 715.5 | 23300 | 25200 | 29800 | 0.0231 | 0.0286 | 1550 |
Redwing/ACSS | 715.5 | 30800 | 34000 | 39800 | 0.023 | 0.0284 | 1570 |
Cuckoo/ACSS | 795 | 21700 | 23300 | 26900 | 0.0209 | 0.0259 | 1650 |
Drake/ACSS | 795 | 25900 | 28000 | 32600 | 0.0209 | 0.0257 | 1662 |
Macaw/ACSS | 795 | 11800 | 12600 | 14300 | 0.0211 | 0.0262 | 1621 |
Tern/ACSS | 795 | 14200 | 15200 | 17400 | 0.021 | 0.0263 | 1618 |
Condor/ACSS | 795 | 21700 | 23300 | 26900 | 0.0209 | 0.0266 | 1618 |
Mallard/ACSS | 795 | 34300 | 37900 | 44300 | 0.0207 | 0.0255 | 1683 |
Ruddy/ACSS | 900 | 15800 | 17000 | 19200 | 0.0186 | 0.0233 | 1755 |
Canary/ACSS | 900 | 24600 | 26400 | 30500 | 0.0184 | 0.0236 | 1756 |
Redbird/ACSS | 954 | 26000 | 28000 | 32300 | 0.0174 | 0.0217 | 1859 |
Rail/ACSS | 954 | 16700 | 18000 | 20400 | 0.0175 | 0.022 | 1824 |
Towhee/ACSS | 954 | 19700 | 21300 | 24300 | 0.0175 | 0.0218 | 1842 |
Cardinal/ACSS | 954 | 26000 | 28000 | 32300 | 0.0174 | 0.0223 | 1825 |
Canvasback/ACSS | 954 | 41100 | 45400 | 53100 | 0.0172 | 0.0214 | 1897 |
Snowbird/ACSS | 1033.5 | 15400 | 16500 | 18500 | 0.0162 | 0.0204 | 1924 |
Ortolan/ACSS | 1033.5 | 18100 | 19500 | 22000 | 0.0162 | 0.0204 | 1921 |
Curlew/ACSS | 1033.5 | 28200 | 30300 | 35000 | 0.0161 | 0.0206 | 1924 |
Bluejay/ACSS | 1113 | 19500 | 21100 | 23800 | 0.015 | 0.019 | 2017 |
Finch/ACSS | 1113 | 30400 | 33200 | 38700 | 0.015 | 0.0193 | 2015 |
Bunting/ACSS | 1192.5 | 21400 | 23500 | 25400 | 0.014 | 0.0178 | 2110 |
Bittern/ACSS | 1272 | 22300 | 24000 | 27100 | 0.0131 | 0.0167 | 2201 |
Pheasant/ACSS | 1272 | 34100 | 37300 | 43000 | 0.0131 | 0.0169 | 2200 |
Dipper/ACSS | 1351 | 23700 | 25500 | 28800 | 0.0124 | 0.0158 | 2289 |
Martin/ACSS | 1351 | 36200 | 39600 | 45600 | 0.0123 | 0.016 | 2288 |
Bobolink/ACSS | 1431 | 25100 | 27000 | 30500 | 0.0117 | 0.015 | 2375 |
Plover/ACSS | 1431 | 38400 | 41900 | 48300 | 0.0117 | 0.0151 | 2375 |
Nuthatch/ACSS | 1510 | 26500 | 28100 | 31800 | 0.0111 | 0.0143 | 2459 |
Parrot/ACSS | 1510 | 40400 | 44200 | 51000 | 0.011 | 0.0144 | 2460 |
Ratite/ACSS | 1590 | 23400 | 25000 | 27900 | 0.0105 | 0.0136 | 2543 |
Lapwing/ACSS | 1590 | 27900 | 29600 | 33500 | 0.0105 | 0.0136 | 2543 |
Falcon/ACSS | 1590 | 42600 | 46600 | 53700 | 0.0105 | 0.0137 | 2545 |
Chukar/ACSS | 1780 | 35400 | 38200 | 43900 | 0.0094 | 0.0122 | 2751 |
Mockingbird/ACSS | 2034.5 | 27200 | 28900 | 32000 | 0.0083 | 0.011 | 2960 |
Roadrunner/ACSS | 2057 | 31700 | 33900 | 38300 | 0.0082 | 0.0108 | 2992 |
Bluebird/ACSS | 2156 | 42100 | 45500 | 51700 | 0.0078 | 0.0103 | 3106 |
Kiwi/ACSS | 2167 | 29000 | 30800 | 34100 | 0.0078 | 0.0104 | 3080 |
Thrasher/ACSS | 2312 | 35600 | 38100 | 43000 | 0.0073 | 0.0098 | 3218 |
Joree/ACSS | 2515 | 38700 | 41400 | 46800 | 0.0067 | 0.0092 | 3390 |
*Designated by “/HS” (e.g. Drake/ACSS/HS)
**Designated by “/HS285” (e.g. Drake/ACSS/HS285)
(1) Data Based on a nominal cable manufactured in accordance with ASTM B856.
(2) Resistance and Ampacity based on an aluminum conductivity of 63%, IACS at 20°C, and a steel conductivity of 8%, IACS at 20°C.
(3) Ampacity based on a 200°C conductor temperature, 25°C ambient temperature, 2ft/sec. wind, in sun, with an emissivity of 0.5 and a coefficient of solar absorption of 0.5, at sea level.
(4) Rated strength for standard strength core based on Class A Galfan coated steel core wire in accordance with ASTM B802.
(5) Rated strength for high strength core based on a Class A Galfan coated high strength steel core wire in accordance with B803.
Revision: 1.000.000
Updated On: July 3, 2024, 9:53 p.m. UTC