SPEC 83354

Covered Line Wire With Thermoplastic Polyethylene (PE)

Aluminum Conductor Covered with Black Polyethylene (PE)

...

Construction:

  1. Conductor:Conductors are solid or stranded compressed aluminum
  2. Covering:Black Polyethylene (PE)

Applications and Features:

Aluminum alloy 1350-H19 or 6201 concentrically stranded. Covered with Black Polyethylene (PE). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Black Polyethylene (PE) covered line wires have the below temperature ratings:

  • Normal Service temperature of 75ºC
  • Emergency Overload of 95ºC
  • Short Circuit temperature of 150ºC
  • Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCode WordPhase Cond. SizePhase StrandPhase Insul. ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.milinchlb/1000ft
    TBAApple6Solid300.22231
    TBAPlum67300.23856
    TBAPear4Solid300.26447
    102145Apricot47300.28551
    102442Hornbeam47300.31060
    TBACherry2Solid450.34878
    102152Peach27450.37384
    TBALinden27450.40699
    TBANectarine17450.408104
    102160Quince1/07600.477136
    102467Oilnut1/07600.518159
    TBAOrange2/07600.522167
    TBAWaterash2/07600.567195
    102186Fig3/07600.570205
    TBAShellbark3/07600.622240
    102194Olive4/07600.626253
    TBAPomegranate4/019600.632247
    102491Planetree4/07600.683297
    TBAMulberry266.819600.694305
    102228Annona336.419600.765377
    621974Annona336.419600.765377
    102236Molles397.519800.861462
    102244Huckleberry47737800.931538
    TBAPaw Paw556.537800.992619
    TBABreadfruit63661951.081715
    102269Persimmon79561951.186877
    TBAGrapefruit1033.561951.326--
    All dimensions are nominal and subject to normal manufacturing tolerances
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Code WordPhase Cond. SizeNeutral Rated Breaking StrengthAllowable Ampacity In Air 90°C
    AWG/KcmillbAmp
    Apple644583
    Plum651084
    Pear4710110
    Apricot4790111
    Hornbeam41360116
    Cherry21100146
    Peach21220146
    Linden22160152
    Nectarine11470169
    Quince1/01790193
    Oilnut1/03440201
    Orange2/02260223
    Waterash2/04160231
    Fig3/02740256
    Shellbark3/05240266
    Olive4/03450295
    Pomegranate4/03620296
    Planetree4/06610306
    Mulberry266.84470340
    Annona336.45540392
    Annona336.45540392
    Molles397.56400429
    Huckleberry4777820479
    Paw Paw556.58950526
    Breadfruit63610500565
    Persimmon79512900646
    Grapefruit1033.516500755
    * Ampacity ratings based on 75ºC conductor temperature 40ºC ambient temperature. Wind speed 2 ft./sec. in sun.
    * Diameter equivalent to ACSR construction or 1350 aluminum equivalent.