SPEC 45257
CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN/THWN-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8 (cable size 8 & 6 AWG has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 AWG uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in wet and dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
SOUTHWIRE® {UL} XX AWG (XX.X{mm2}) CU 4 CDRS TYPE TC-ER THHN OR THWN-2 CDRS GW 1 X X AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 557694◊ | 8 | 4 | 7 | 0.141 | 30 | 1 x 10 GG | 60 | 0.701 | 238 | 383 | Black |
| 553438◊ | 6 | 4 | 7 | 0.177 | 30 | 1 x 8 GG | 60 | 0.789 | 378 | 559 | Black |
| 601989◊ | 4 | 4 | 7 | 0.225 | 40 | 1 x 8 | 80 | 0.933 | 572 | 876 | Black |
| 601997◊ | 2 | 4 | 7 | 0.282 | 40 | 1 x 6 | 80 | 1.082 | 909 | 1230 | Black |
| 602003 | 1 | 4 | 19 | 0.322 | 50 | 1 x 6 | 80 | 1.218 | 1125 | 1545 | Black |
| 554568◊ | 1/0 | 4 | 19 | 0.361 | 50 | 1 x 6 | 80 | 1.304 | 1399 | 1851 | Black |
| 556720◊ | 2/0 | 4 | 19 | 0.405 | 50 | 1 x 6 | 80 | 1.410 | 1742 | 2252 | Black |
| 602029◊ | 3/0 | 4 | 19 | 0.456 | 50 | 1 x 4 | 80 | 1.531 | 2223 | 2801 | Black |
| 444745◊ | 4/0 | 4 | 19 | 0.512 | 50 | 1 x 4 | 80 | 1.637 | 2769 | 3286 | Black |
| 602045◊ | 250 | 4 | 37 | 0.558 | 60 | 1 x 4 | 110 | 1.895 | 3248 | 4113 | Black |
| 580495 | 250 | 4 | 37 | 0.558 | 60 | 1 x 2 | 110 | 1.895 | 3325 | 4181 | Black |
| 602060◊ | 350 | 4 | 37 | 0.661 | 60 | 1 x 3 | 110 | 2.144 | 4530 | 5482 | Black |
| 563180 | 350 | 4 | 37 | 0.661 | 60 | 1 x 3/0 | 110 | 2.257 | 4889 | 5892 | Black |
| TBA | 400 | 4 | 37 | 0.705 | 70 | 1 x 3 | 110 | 2.272 | 5148 | 5973 | Black |
| 552513◊ | 500 | 4 | 37 | 0.789 | 60 | 1 x 2 | 110 | 2.397 | 6443 | 7485 | Black |
| 593375 | 500 | 4 | 37 | 0.789 | 60 | 1 x 250 | 110 | 2.485 | 7016 | 8077 | Black |
| 604819 | 600 | 4 | 61 | 0.865 | 70 | 1 x 2 | 110 | 2.643 | 7691 | 8924 | Black |
| 456241 | 600 | 4 | 61 | 0.865 | 80 | 1 x 1/0 | 110 | 2.655 | 7813 | 9089 | Black |
| 604827 | 750 | 4 | 61 | 0.968 | 70 | 1 x 1 | 140 | 2.998 | 9616 | 11402 | Black |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 557694◊ | 8 | 4 | 2.8 | 422 | 0.653 | 0.786 | 0.052 | 40 | 44 |
| 553438◊ | 6 | 4 | 3.2 | 671 | 0.411 | 0.495 | 0.051 | 52 | 60 |
| 601989◊ | 4 | 4 | 3.7 | 1068 | 0.258 | 0.310 | 0.048 | 68 | 76 |
| 601997◊ | 2 | 4 | 5.4 | 1698 | 0.162 | 0.195 | 0.045 | 92 | 104 |
| 602003 | 1 | 4 | 6.1 | 2142 | 0.128 | 0.154 | 0.046 | 104 | 116 |
| 554568◊ | 1/0 | 4 | 6.5 | 2703 | 0.102 | 0.122 | 0.044 | 120 | 136 |
| 556720◊ | 2/0 | 4 | 7.1 | 3407 | 0.081 | 0.097 | 0.043 | 140 | 156 |
| 602029◊ | 3/0 | 4 | 7.7 | 4295 | 0.064 | 0.078 | 0.042 | 160 | 180 |
| 444745◊ | 4/0 | 4 | 8.2 | 5416 | 0.051 | 0.062 | 0.041 | 184 | 208 |
| 602045◊ | 250 | 4 | 9.5 | 6400 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 580495 | 250 | 4 | 9.5 | 6400 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 602060◊ | 350 | 4 | 12.9 | 8960 | 0.031 | 0.039 | 0.040 | 248 | 280 |
| 563180 | 350 | 4 | 13.5 | 8960 | 0.031 | 0.039 | 0.040 | 248 | 280 |
| TBA | 400 | 4 | 13.6 | 12800 | 0.027 | 0.035 | 0.040 | 268 | 304 |
| 552513◊ | 500 | 4 | 14.4 | 12800 | 0.022 | 0.029 | 0.039 | 304 | 344 |
| 593375 | 500 | 4 | 14.9 | 12800 | 0.022 | 0.029 | 0.039 | 304 | 344 |
| 604819 | 600 | 4 | 15.9 | 15360 | 0.018 | 0.025 | 0.039 | 336 | 380 |
| 456241 | 600 | 4 | 15.9 | 15360 | 0.018 | 0.025 | 0.039 | 336 | 380 |
| 604827 | 750 | 4 | 18.0 | 19200 | 0.014 | 0.022 | 0.038 | 380 | 428 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.007
Updated On: Sept. 19, 2025, 6:03 p.m. UTC


