SPEC 10050

Aluminum Service Entrance (SE) Cable Type SEU. XHHW-2

Service Entrance Cable, Type SE. Style SEU. Service Entrance Cable, 600 Volt. Individual Conductors Rated XHHW-2. Jacket and Individual Conductors Sunlight Resistant.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum Alumaflex® per ASTM B800 and ASTM B801
  2. Insulation:All phases are insulated with Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Neutral:Bare soft annealed aluminum neutral
  4. Binder:Reinforcement binder
  5. Jacket:Gray Polyvinyl Chloride PVC jacket. Sunlight resistant.

Applications and Features:

Southwire® Type SE, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. SEU may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts. SE cables are not permitted underground, with or without a raceway, per NEC 338.12(A)(2).

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC National Electrical Code NFPA 70
  • Federal Specification A-A-59544
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 {UL} 2 CDR XX AWG 1 CDR 6 AWG COMPACT AL. --- {ALUMAFLEX}® AA8176 TYPE SE CABLE STYLE U TYPE XHHW-2 CDRS 600 VOLTS MADE IN USA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberConductor StrandingInsulation ThicknessNum x Neutral SizeJacket ThicknessApprox. ODOverall Weight
    AWG/KcmilmilsNo. x AWGmilinchlbs/1000ft
    130864627451x6300.419 x 0.138137
    130948427451x6300.483 x 0.181180
    130872427451x4300.508 x 0.197197
    130955227451x4300.563 x 0.258258
    130880227451x2300.578 x 0.284283
    1309632/0219551x1300.731 x 0.469468
    1309142/0219551x2/0300.733 x 0.512512
    1309714/0219551x2/0300.847 x 0.693692
    1309304/0219551x4/0300.890 x 0.767766
    1310522/0319551x1301.277659
    1310603/0319551x1/0301.391801
    1310784/0319551x2/0301.516976
    552504250335651x3/0301.6731168
    277186247451x4301.067456
    3274452/0419551x1301.418834
    2799684/0419551x2/0301.6851237
    555869250435651x3/0301.8611480
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    620.63140.6740.8120.0515055
    420.75000.4240.5100.0486575
    420.85000.4240.5100.0486575
    221.07960.2670.3210.04590100
    221.17960.2670.3210.04590100
    2/021.915970.1330.1600.043135150
    2/022.015970.1330.1600.043135150
    4/022.825390.0840.1000.041180205
    4/023.125390.0840.1000.041180205
    2/036.423950.1330.1600.043135150
    3/037.030200.1050.1260.042155175
    4/037.638080.0840.1000.041180205
    25038.445000.0710.0860.041205230
    245.312740.2670.3210.0457280
    2/047.125550.1330.1600.043108120
    4/048.440620.0840.1000.041144164
    25049.348000.0710.0860.041164184
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.