SPEC 10005

Copper XHHW-2 Circuit Sizes (14, 12 & 10 AWG)

Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE).

...

Construction:

  1. Conductor:Solid or Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

APPLICATION
Southwire XHHW-2 copper conductors circuit sizes are primarily used in conduit, or other recognized raceways, and branch circuit wiring, as specified in the National Electrical Code. XHHW-2 copper conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW-2 conductors is 600 volts or 1000 volts. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified.


FEATURES
  • SIS - Sizes 14 AWG through 10 AWG
  • RoHS Compliant
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Federal Specification A-A-59544
  • NMX-J-451-ANCE Thermoset insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • Sample Print Legend:

    14 AWG thru 10 AWG
    SOUTHWIRE E30117 (UL) XX AWG (XXXmm2) CU TYPE XHHW-2 600V/1000V OR SIS 600 VOLTS NOM-ANCE

    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    55022012Solid0.081300.1411925
    55022212Solid0.081300.1411925
    55022412Solid0.081300.1411925
    55022112Solid0.081300.1411925
    55022712Solid0.081300.1411925
    55022612Solid0.081300.1411925
    55022512Solid0.081300.1411925
    55022312Solid0.081300.1411925
    13724010Solid0.102300.1623037
    55021310Solid0.102300.1623037
    55021510Solid0.102300.1623037
    55021210Solid0.102300.1623037
    55021810Solid0.102300.1623037
    55021710Solid0.102300.1623037
    55021610Solid0.102300.1623037
    55021410Solid0.102300.1623037
    1129201470.071300.1311217
    3709321470.071300.1311217
    3709401470.071300.1311217
    3709241470.071300.1311217
    3709811470.071300.1311217
    3709731470.071300.1311217
    3709571470.071300.1311217
    3710051470.071300.1311217
    3709651470.071300.1311217
    1129381270.089300.1472024
    3710391270.089300.1472024
    3710471270.089300.1472024
    3710211270.089300.1472024
    3710881270.089300.1472024
    3710701270.089300.1472024
    3710541270.089300.1472024
    3711041270.089300.1472024
    3710621270.089300.1472024
    1129461070.113300.1733236
    3711381070.113300.1733236
    3711461070.113300.1733236
    3711201070.113300.1733236
    3711871070.113300.1733236
    3711791070.113300.1733236
    3711531070.113300.1733236
    3712031070.113300.1733236
    3711611070.113300.1733236
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    550220120.5521.6622.0020.054202530
    550222120.5521.6622.0020.054202530
    550224120.5521.6622.0020.054202530
    550221120.5521.6622.0020.054202530
    550227120.5521.6622.0020.054202530
    550226120.5521.6622.0020.054202530
    550225120.5521.6622.0020.054202530
    550223120.5521.6622.0020.054202530
    137240100.6831.0401.2530.050303540
    550213100.6831.0401.2530.050303540
    550215100.6831.0401.2530.050303540
    550212100.6831.0401.2530.050303540
    550218100.6831.0401.2530.050303540
    550217100.6831.0401.2530.050303540
    550216100.6831.0401.2530.050303540
    550214100.6831.0401.2530.050303540
    112920140.5322.6313.1700.058152025
    370932140.5322.6313.1700.058152025
    370940140.5322.6313.1700.058152025
    370924140.5322.6313.1700.058152025
    370981140.5322.6313.1700.058152025
    370973140.5322.6313.1700.058152025
    370957140.5322.6313.1700.058152025
    371005140.5322.6313.1700.058152025
    370965140.5322.6313.1700.058152025
    112938120.5521.6622.0020.054202530
    371039120.5521.6622.0020.054202530
    371047120.5521.6622.0020.054202530
    371021120.5521.6622.0020.054202530
    371088120.5521.6622.0020.054202530
    371070120.5521.6622.0020.054202530
    371054120.5521.6622.0020.054202530
    371104120.5521.6622.0020.054202530
    371062120.5521.6622.0020.054202530
    112946100.6831.0401.2530.050303540
    371138100.6831.0401.2530.050303540
    371146100.6831.0401.2530.050303540
    371120100.6831.0401.2530.050303540
    371187100.6831.0401.2530.050303540
    371179100.6831.0401.2530.050303540
    371153100.6831.0401.2530.050303540
    371203100.6831.0401.2530.050303540
    371161100.6831.0401.2530.050303540
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Stock Code Colors and Standard Package

    SizePackageBlackRedBlueWhiteBrownOrangeYellowGrayGreen
    BlackRedBlueWhiteBrownOrangeYellowGrayGreen
    14 (7)Reel: 2500'
    Spool: 500'
    112920370932370940370924370981370973370957371005370965
    12 (Solid)Reel: 2500'
    Spool: 500'
    550220550222550224550221550227550226550225550223
    12 (7)Reel: 2500'
    Spool: 500'
    112938371039371047371021371088371070371054371104371062
    10 (Solid)Reel: 2500'
    Spool: 500'
    137240550213550215550212550218550217550216550214
    10 (7)Reel: 2500'
    Spool: 500'
    112946371138371146371120371187371179371153371203371161

    Revision: 1.000.038