SPEC 48004

CU 600V LSZH XHHW-2 SOLONONplus™ FT4, VW-1

SOLONONplus™ 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type XHHW-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8; Tinned copper per ASTM B33 available upon request
  2. Insulation:SOLONONplus™ Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type XHHW-2

Applications and Features:

APPLICATION
Southwire’s 600 Volt SOLONONplus™ Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

FEATURES
  • The conductors are available in tinned and flexible copper stranding upon request.
  • NEC compliant
  • The halogen content is less than 0.2% and Acid gas less than 2.0%
  • UL listed VW-1
  • UL listed FT4/IEEE 1202 and ST-1
  • UL listed for CT use on 1/0 and Larger
  • -40°C Cold impact and cold bend
  • Oil Resistant I and II
  • Gasoline Resistance I and II
  • Sunlight Resistant
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

    14 AWG thru 1 AWG
    SOUTHWIRE SOLONONplus{TM} LSZH XLPO E30117 (UL) XX AWG CU TYPE XHHW-2-HF VW-1 600V PRI PRII GRI GRII -40{D}C SR FT4 ST-1

    1/0 AWG and Larger
    {SQFTG} SOUTHWIRE SOLONONplus{TM} LSZH XLPO E30117 {UL} XX AWG/KCMIL CU TYPE XHHW-2-HF VW-1 600V PRI PRII GRI GRII -40{D}C SR FT4 ST-1 CT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand ClassStrand CountCond. CmilDiameter Over ConductorInsul. ThicknessJacket ColorApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMax Pull Tension
    AWG/kcmilNo. of Strandscmilinchmilinchlb/1000ftΩ/1000ftΩ/1000ftlb
    66607814B741100.07030WE0.133202.6313.17033
    66607914B741100.07030BN0.133202.6313.17033
    66608314B741100.07030OE0.133202.6313.17033
    66607714B741100.07030YW0.133202.6313.17033
    66608214B741100.07030GY0.133202.6313.17033
    66608014B741100.07030GN0.133202.6313.17033
    66608514B741100.07030PE0.133202.6313.17033
    66608114B741100.07030BK0.133202.6313.17033
    66608414B741100.07030RD0.133202.6313.17033
    66607614B741100.07030BE0.133202.6313.17033
    66608712B765300.08730BK0.151291.6622.00252
    66609312B765300.08830WE0.151291.6622.00252
    66608812B765300.08830BN0.151291.6622.00252
    66609112B765300.08830OE0.151291.6622.00252
    66609412B765300.08830YW0.151291.6622.00252
    66609012B765300.08830GY0.151291.6622.00252
    66608912B765300.08830GN0.151291.6622.00252
    66609212B765300.08830RD0.151291.6622.00252
    66608612B765300.08830BE0.151291.6622.00252
    13944210B7103800.11330WE0.177431.0401.25383
    13943710B7103800.11330BN0.177431.0401.25383
    13944010B7103800.11330OE0.177431.0401.25383
    13944310B7103800.11330YW0.177431.0401.25383
    13943910B7103800.11330GY0.177431.0401.25383
    13943810B7103800.11330GN0.177431.0401.25383
    13943610B7103800.11330BK0.177431.0401.25383
    13944110B7103800.11330RD0.177431.0401.25383
    13943510B7103800.11330BE0.177431.0401.25383
    1394948B7165100.14145WE0.236720.6530.786132
    1394898B7165100.14145BN0.236720.6530.786132
    1394928B7165100.14145OE0.236720.6530.786132
    1394958B7165100.14145YW0.236720.6530.786132
    1394918B7165100.14145GY0.236720.6530.786132
    1394908B7165100.14145GN0.236720.6530.786132
    1394938B7165100.14145RD0.236720.6530.786132
    1394878B7165100.14145BE0.236720.6530.786132
    1394888B7165100.14245BK0.236720.6530.786132
    1394836B7262400.17745WE0.2721060.4110.495209
    1394786B7262400.17745BN0.2721060.4110.495209
    1394816B7262400.17745OE0.2721060.4110.495209
    1394846B7262400.17745YW0.2721060.4110.495209
    1394806B7262400.17745GY0.2721060.4110.495209
    1394796B7262400.17745GN0.2721060.4110.495209
    1394826B7262400.17745RD0.2721060.4110.495209
    1394766B7262400.17745BE0.2721060.4110.495209
    1394776B7262400.17845BK0.2721060.4110.495210
    1394654B7417400.22545WE0.3191600.2580.310333
    1394604B7417400.22545BN0.3191600.2580.310333
    1394634B7417400.22545OE0.3191600.2580.310333
    1394664B7417400.22545YW0.3191600.2580.310333
    1394624B7417400.22545GY0.3191600.2580.310333
    1394614B7417400.22545GN0.3191600.2580.310333
    1394594B7417400.22545BK0.3191600.2580.310334
    1394644B7417400.22545RD0.3191600.2580.310333
    1394584B7417400.22545BE0.3191600.2580.310333
    1394543B7526200.25245BK0.3461970.2050.246421
    1394452B7663600.27745BK0.3712420.1620.154531
    1394442B7663600.28245BE0.3712420.1620.195530
    1394502B7663600.28245WE0.3712420.1620.195530
    1394462B7663600.28245BN0.3712420.1620.195530
    1394482B7663600.28245OE0.3712420.1620.195530
    1394512B7663600.28245YW0.3712420.1620.195530
    1394472B7663600.28245GN0.3712420.1620.195530
    1394492B7663600.28245RD0.3712420.1620.195530
    1394291B19836900.32255WE0.4383110.1280.154669
    1394281B19836900.32255GN0.4383110.1280.154669
    1394301B19836900.32255BK0.4383110.1280.154670
    1394311/0B191056000.36155WE0.4783850.1020.122844
    1394321/0B191056000.36155GN0.4783850.1020.122844
    1394331/0B191056000.36155RD0.4783850.1020.122844
    1394341/0B191056000.36255BK0.4783850.1020.122845
    1394522/0B191331000.40655BK0.5224760.0810.0971065
    1394553/0B191678000.45655BK0.5725910.0640.0791342
    1394694/0B192116000.49855BK0.6147320.0510.0621693
    1394674/0B192116000.51255WE0.6147320.0510.0621692
    1394684/0B192116000.51255GN0.6147320.0510.0621692
    139453250B372500000.54265BK0.6788710.0430.0532000
    139456300B373000000.59465BK0.73010340.0360.0452400
    139457350B373500000.64165BK0.77711970.0310.0382800
    139470400B374000000.68565BK0.82113590.0270.0333200
    139475500B375000000.76665BK0.90216810.0220.0324000
    139472500B375000000.78965OE0.90216810.0220.0294000
    139473500B375000000.78965YW0.90216810.0220.0294000
    139471500B375000000.78965GY0.90216810.0220.0294000
    139474500B375000000.78965GN0.90216810.0220.0294000
    139485600B616000000.84080BK1.00820380.0180.0254800
    139486750B617500000.96880BK1.13625270.0140.0216000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Table 3 - Stock Code Colors (Black in Table 1)

    Size (Strand)BlackRedBlueWhiteBrownOrangeYellowGrayGreenPurple
    14 (7)666081666084666076666078666079666083666077666082666080666085
    12 (7)666087666092666086666093666088666091666094666090666089
    10 (7)139436139441139435139442139437139440139443139439139438
    8 (7)139488139493139487139494139489139492139495139491139490
    6 (7)139477139482139476139483139478139481139484139480139479
    4 (7)139459139464139458139465139460139463139466139462139461
    3 (7)139454
    2 (7)139445139449139444139450139446139448139451139447
    1 (19)139430139429139428
    1/0 (19)139434139433139431139432
    2/0 (19)139452
    3/0 (19)139455
    4/0 (19)139469139467139468
    250 (37)139453
    300 (37)139456
    350 (37)139457
    400 (37)139470
    500 (37)139475139472139473139471139474
    600 (61)139485
    750 (61)139486

    Revision: 1.000.009