SPEC 60215

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Isolated Ground 120/208V Colors

Copper THHN/THWN Insulated Singles. Two Insulated Grounding Conductors. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3 or 19-strand class C compressed copper and ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Grounds:Two insulated green and green/yellow grounds. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Isolated Ground Cable is suitable for use as follow:
• Applications requiring redundant, dedicated or isolated grounding paths
• Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Type THHN/THWN rated 90ºC dry

Southwire Armorlite® Type MC Isolated Ground Cable meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    12 AWG | Solid
    556323◊122RD,WE0.080Solid202x120.50579132
    556325◊122BE,WE0.080Solid202x120.50579132
    695965◊122BK,WE0.080Solid202x120.50579132
    695973◊123BK,RD,WE0.080Solid202x120.54199159
    560950◊123BK,BE,WE0.080Solid202x120.55099159
    695981◊124BK,RD,BE,WE0.080Solid202x120.586119187
    562419◊124BK,RD,BE,WE0.080Solid202x120.577119187
    587697◊126See Table0.080Solid202x120.625159238
    10 AWG | Solid
    695999◊102BK,WE0.101Solid252x100.581123192
    555636◊102BE,WE0.101Solid252x100.590123192
    555634102RD,WE,GN,GN/YW0.101Solid202x100.58123191
    696005◊103BK,RD,WE0.101Solid252x100.625154233
    696013◊104BK,RD,BE,WE0.101Solid252x100.671185274
    58408014BK,RD,BE/WE,GN,GN/YW0.32219502x61.40612061597
    12 AWG | 19 Strands
    551104◊122BK,WE0.09019202x120.53080138
    551106◊123BK,RD,WE0.09019202x120.565100159
    551296◊124BK,RD,BE,WE0.09019202x120.604120197
    10 AWG | 19 Strands
    551298◊102BK,WE0.11719252x100.618129206
    551302◊103BK,RD,WE0.11719252x100.675161250
    555184◊82BK,WE0.14319352x100.682167260
    555189◊84BK,RD,BE,WE0.14319352x100.869270433
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutrals. Does not include green and green/yellow ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    12 AWG | Solid
    1223.61.6622.0020.0542530
    1223.61.6622.0020.0542530
    1223.61.6622.0020.0542530
    1233.81.6622.0020.0542530
    1233.81.6622.0020.0542530
    1244.11.6622.0020.0542024
    1244.11.6622.0020.0542024
    1264.41.6622.0020.0542024
    10 AWG | Solid
    1024.11.0401.2530.0503540
    1024.11.0401.2530.0503540
    1024.11.041.2530.053540
    1034.41.0401.2530.0503540
    1044.81.0401.2530.0502832
    149.80.1280.1540.046104116
    12 AWG | 19 Strands
    1223.81.6622.0020.0542530
    1234.01.6622.0020.0542530
    1244.31.6622.0020.0542024
    10 AWG | 19 Strands
    1024.41.0401.2530.0503540
    1034.71.0401.2530.0503540
    824.80.6530.7860.0525055
    846.10.6530.7860.0524044
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table - Conductor number = number of phase conductors plus neutrals. Does not include green and green/yellow ground ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond. NumberStock CodeColor
    12 (Solid)2695965BK, WE, GN, GN/YW
    12 (Solid)2556323RD, WE, GN, GN/YW
    12 (Solid)2556325BE, WE, GN, GN/YW
    12 (Solid)3695973BK, WE, RD, GN, GN/YW
    12 (Solid)3560950BK, BE, WE, GN, GN/YW
    12 (Solid)4695981BK, WE, RD, BE, GN, GN/YW
    12 (Solid)4562419BK, WE, WE/BK, BK/WE, GN, GN/YW
    12 (Solid)6587697BK, RD, BE, PK, PE, WE, GN, GN/YW
    10 (Solid)2695999BK, WE, GN, GN/YW
    10 (Solid)2555636BE, WE, GN, GN/YW
    10 (Solid)3696005BK, WE, RD, GN, GN/YW
    10 (Solid)4696013BK, WE, RD, BE, GN, GN/YW
    12 (19)2551104BK, WE, GN, GN/YW
    12 (19)3551106BK, WE, RD, GN, GN/YW
    12 (19)4551296BK, WE, RD, BE, GN, GN/YW
    10 (19)2551298BK, WE, GN, GN/YW
    10 (19)3551302BK, WE, RD, GN, GN/YW
    8 (19)2555184BK, WE, GN GND, GN/YW GND
    8 (19)4555189BK, WE, RD, BE, GN GND, GN/YW GND

    Revision: 1.000.012