SPEC 60208

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Neutral Per Phase

Copper THHN/THWN Insulated Singles. Dedicated Neutral Conductor for Each Phase Conductor. Green Insulated Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid copper per ASTM B3 or 19-strands class C compressed copper per ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green Polyvinyl Chloride with Nylon Sheath Type THHN/THWN insulated ground conductor
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable Neutral-per-phase products comply with NEC 200.4 requirements (added in the 2011 NEC) for the installation and marking of neutral conductors. Neutrals are not to be used for more than one circuit (branch, multiwire branch, or ungrounded feeder). See NEC 200.4 for complete requirements.

Southwire Armorlite® Type MC Cable (neutral per phase) is suitable for use as follow:
• Applications affected by harmonics generated from non-linear switching loads, such as computers, variable frequency drives, electrical test equipment, and office equipment
• Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings
• Fished or embedded in plaster
• Concealed or exposed installations
• Environmental air-handling spaces per NEC 300.22 (C)
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations
• Binder tape with print legend wrapped around assembly
• Unjacketed Type MC cables are rated for dry, indoor locations only per NEC 330.10(A)(10)
• Type THHN/THWN rated 90ºC dry

Southwire Armorlite® Type MC Cable (neutral per phase) meets or exceeds the following requirements:
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
• Federal Specification A-A59544 (formerly J-C-30B)
• NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeNum x Neutral SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGNo. x AWGinchlbs/1000ftlbs/1000ft
    14 AWG | Solid
    674349142BK,RD,WE/BK,WE/RD,GN0.064Solid201x142x140.562116
    12 AWG | Solid
    554994121RD,WE/RD,GN0.08Solid201x121x120.47459105
    580818122BN,YW,GY/BN,GY/YW,GN0.08Solid201x122x120.54199158
    552795122BK,RD,WE/BK,WE/RD,GN0.08Solid201x122x120.5599159
    554669122BE,RD,WE/BE,WE/RD,GN0.08Solid201x122x120.5499159
    554992122BE,RD,WE/BE,WE/RD,GN0.08Solid201x122x120.54199158
    554993122BK,BE,WE/BK,WE/BE,GN0.08Solid201x122x120.54199158
    610666122See Table0.08Solid202x122x120.577119187
    580816122OE,YW,GY/OE,GY/YW,GN0.08Solid201x122x120.54199158
    583558122RD,BE,WE/RD,WE/BE,GN0.08Solid201x122x120.5499159
    554991122BK,RD,GN,WE/BK,WE/RD0.08Solid201x122x120.54199159
    556287122BK,RD,WE/BK,WE/RD,GN0.08Solid151x122x120.5599236
    610669123See Table0.08Solid202x123x120.616159238
    554990123See Table0.08Solid201x123x120.577139211
    643572124BN,OE,YW,PE,GY/BN,GY/OE,GY/YW,GY/PE,GN0.08Solid201x124x120.661179266
    568571124BK,RD,BE,OR,GN,GN/YW,WT,WT/BK,WT/RD,WT/BE0.08Solid202x124x120.7199293
    566811124See Table0.08Solid201x124x120.652179266
    643570124See Table0.08Solid201x124x120.661179266
    674321126BK,RD,BE,BN,OE,YW,WT/BK,WT/RD,WT/BE,WT/BN0.08Solid201x126x120.856332495
    580850126See Table0.08Solid201x126x120.81259401
    643654126See Table0.08Solid201x126x120.81259402
    674313127See Table0.08Solid201x127x120.846299453
    10 AWG | Solid
    578270102RD,BE,WE/RD,WE/BE,GN0.101Solid251x102x100.624154232
    552996102See Table0.101Solid252x102x100.671185274
    573933102OE,YW,GN,GY/OE,GY/YW0.101Solid251x102x100.624154231
    586593102BK,BE,WE/BK,WE/BE,GN0.101Solid251x102x100.624154231
    567063102BK,RD,WE/BK,WE/RD,GN0.101Solid251x102x100.625154232
    641220102See Table0.101Solid252x102x100.671185274
    643903102BK,RD,WE/BK,WE/RD,GN0.101Solid201x102x100.634154322
    556259103See Table0.101Solid251x103x100.671216311
    610673103See Table0.101Solid252x103x100.777247382
    643574104BK,RD,BE,PE,WE/BK,WE/RD,WE/BE,WE/PE,GN0.101Solid251x104x100.823278425
    674302104BK,RD,BE,PK,WE/BK,WE/RD,WE/BE,WE/PK,GN0.101Solid251x104x100.823278425
    592357104BN,OE,YW,PE,GY/BN,GY/OE,GY/YW,GY/PE,GN0.101Solid251x104x100.823278424
    567269104See Table0.101Solid251x104x100.824278425
    554852104See Table0.101Solid252x104x100.884309469
    641911105BK,RD,BE,BK/WT,RD/BK,WT,WT/BK,WT/RD,WT/BE,WT/YW,GN0.101Solid251x105x100.883340506
    585848105See Table0.101Solid251x105x100.884342508
    677655105See Table0.101Solid251x105x100.884340506
    590115105See Table0.101Solid251x105x100.884340506
    674364106BN,BN,OR,OR,YW,YW,GY/BN,GY/BN,GY/OR,GY/OR,GY/YW,GY0.101Solid251x106x100.946402587
    679826106BK,BK,RD,RD,BE,BE,WT/BK,WT/BK,WT/RD,WT/RD,WT/BE,WT0.101Solid251x106x100.946402590
    588881106BK,RD,BE,OR,YW,BN,WT/BK,WT/RD,WT/BE,WT/OR,WT/YW,WT0.101Solid252x106x100.946434626
    566546106See Table0.101Solid251x106x100.947403588
    679158107See Table0.101Solid251x107x100.933468669
    12 AWG | 19 Strands
    586628122RD,BE,GN,GN/YW,WE/BE,WE/RD0.08819202x122x120.608120194
    566806122BK,BE,WE/BK,WE/BE,GN0.08819201x122x120.567100166
    566804122BE,RD,WE/BE,WE/RD,GN0.08819201x122x120.567100166
    589310122BN,OE,GN,GY/BN,GY/OE0.08819201x122x120.567100166
    643872122BN,YW,GY/BN,GY/YW,GN0.08819201x122x120.567100166
    643875122OE,YW,GY/OE,GY/YW,GN0.08819201x122x120.567100166
    586630122BK,BE,GN,GN/YW,WE/BE,WE/BK0.08819202x122x120.608120194
    551322122See Table0.0919202x122x120.607120195
    566801122BK,RD,GN,WE/BK,WE/RD0.0919201x122x120.568100167
    562687123See Table0.0919201x123x120.607140220
    551324123See Table0.0919202x123x120.649160249
    567272124BK,RD,BE,BK/WE,WE/BK,WE/RD,WE/BE,WE,GN0.08819201x124x120.688180275
    10 AWG | 19 Strands
    646774101PK,GY/PK,GN0.11319251x101x100.57197161
    646772101TAN,GY/TAN,GN0.11319251x101x100.57197161
    646770101PE,GY/PE,GN0.11319251x101x100.57497162
    587544101OE,GY/OE,GN0.11319251x101x100.57497162
    587542101YW,GY/YW,GN0.11319251x101x100.57497162
    587183102OE,YW,GY/OE,GY/YW,GN0.11319251x102x100.665161250
    587185102BN,YW,GY/BN,GY/YW,GN0.11319251x102x100.665161250
    597925102BK,BE,GN,WE/BK,WE/BE0.11319251x102x100.665161250
    597927102RD,BE,GN,WE/RD,WE/BE0.11319251x102x100.665161250
    563822102BK,RD,GN,WE/BK,WE/RD0.11719251x102x100.666161251
    586636102See Table0.11719252x102x100.776194325
    551336103See Table0.11719252x103x100.828258411
    562456103See Table0.11719251x103x100.776226365
    553238103See Table0.11719251x103x100.776226365
    566698104See Table0.11719251x104x100.879291457
    649588105BK,RD,BK/WT,BK/RD,RD/WT,WT,WT/RD,WT/BE,WT/BK,WT/PK0.11319251x105x100.944355544
    647335108See Table0.11719251x108x101.117549804
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors. Does not include neutrals and green ground.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberNeutral StrandingMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | Solid
    14223.62.6313.170.0581620
    12 AWG | Solid
    12113.41.6622.0020.0542530
    12223.81.6622.0020.0542024
    12223.81.6622.0020.0542024
    12223.81.6622.0020.0542024
    12223.81.6622.0020.0542024
    12223.81.6622.0020.0542024
    12224.11.6622.0020.0542024
    12223.81.6622.0020.0542024
    12223.81.6622.0020.0542024
    12223.81.6622.0020.0542024
    12224.61.6622.0020.0542024
    12334.41.6622.0020.0542024
    12334.11.6622.0020.0542024
    12444.61.6622.0020.0541215
    12444.91.6622.0020.0541215
    12444.61.6622.0020.0541721
    12444.61.6622.0020.0541721
    12666.01.6622.0020.0541215
    12665.71.6622.0020.0541215
    12665.71.6622.0020.0541215
    12775.91.6622.0020.0541215
    10 AWG | Solid
    10224.41.041.2530.052832
    10224.81.041.2530.052832
    10224.41.041.2530.052832
    10224.41.041.2530.052832
    10224.41.041.2530.052832
    10224.81.041.2530.052832
    10225.21.041.2530.052832
    10334.81.041.2530.052832
    10335.41.041.2530.052832
    10445.81.041.2530.051720
    10445.81.041.2530.051720
    10445.81.041.2530.051720
    10445.81.041.2530.052428
    10446.21.041.2530.052428
    10556.21.041.2530.051720
    10556.21.041.2530.051720
    10556.21.041.2530.051720
    10556.21.041.2530.051720
    10666.61.041.2530.051720
    10666.61.041.2530.051720
    10666.61.041.2530.051720
    10666.21.041.2530.051720
    10776.51.041.2530.051720
    12 AWG | 19 Strands
    12224.31.6622.0020.0542024
    122241.6622.0020.0542024
    122241.6622.0020.0542024
    122241.6622.0020.0542024
    122241.6622.0020.0542024
    122241.6622.0020.0542024
    12224.31.6622.0020.0542024
    12224.31.6622.0020.0542024
    122241.6622.0020.0542024
    12334.31.6622.0020.0542024
    12334.61.6622.0020.0542024
    12444.81.6622.0020.0541215
    10 AWG | 19 Strands
    101141.041.2530.053540
    101141.041.2530.053540
    101141.041.2530.053540
    101141.041.2530.053540
    101141.041.2530.053540
    10224.71.041.2530.052832
    10224.71.041.2530.052832
    10224.71.041.2530.052832
    10224.71.041.2530.052832
    10224.71.041.2530.052832
    10225.41.041.2530.052832
    10335.81.041.2530.052832
    10335.41.041.2530.052832
    10335.41.041.2530.052832
    10446.11.041.2530.052428
    10556.61.041.2530.051720
    10887.21.041.2530.051720
    Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Color Table - Conductor number = number of phase conductors. Does not include neutrals and green ground. ( / means stripe RD/WE is Red with White Stripe)

    Size (Strand)Cond NumberStock CodeColor
    14 (Solid)2674349BK, RD, WE/BK, WE/RD, GN
    12 (Solid)1554994RD, WE/RD, GN
    12 (Solid)2554991BK, RD, GN, WE/BK, WE/RD
    12 (Solid)2610666BK, RD, GN, GN/YW, WE/BK, WE/RD
    12 (Solid)2552795BK, RD, WE/BK, WE/RD, GN
    12 (Solid)3554990BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    12 (Solid)3610669BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    12 (Solid)4566811BK, RD, BE, BK/WE, WE, WE/RD, WE/BE, WE/BK, GN
    12 (Solid)4643570BK, RD, BE, PE, WE/BK, WE/RD, WE/BE, WE/PE, GN
    12 (Solid)6643654BK, RD, BE, PK, PE, YW, GN, WE/BK, WE/RD, WE/BE, WE/PK, WE/PE, WE/YW
    12 (Solid)6580850BK, RD, BE, BK/RD, RD/BE, BE/BK, GN, WE, WE/BK, WE/RD, WE/BE, WE/BK, WE/RD
    12 (Solid)6674321BK, RD, BE, BN, OE, YW, WE/BK, WE/RD, WE/BE, WE/BN, WE/OE, WE/YW, BK, WE/BK, GN
    12 (Solid)7674313BK, RD, BE, BK/YW, RD/YW, BE/YW, BK/RD, WE, WE/BK, WE/RD, WE/BE, WE/BK, WE/RD, WE/BE, GN
    10 (Solid)2567063BK, RD, WE/BK, WE/RD, GN
    10 (Solid)2641220BK, RD, GN, GN/YW, WE/BK, WE/RD
    10 (Solid)2552996BK, RD, WE, WE/BE, GN, GN/YW
    10 (Solid)3556259BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (Solid)3610673BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (Solid)4567269BK, RD, BE, BK/WE, GN, WE/BK, WE/RD, WE/BE, WE
    10 (Solid)4554852BK, RD, BE, BK/RD, WE, WE/BK, WE/RD, GN, GN/YW, WE/BE
    10 (Solid)5590115BK, BK, RD, RD, BE, WE/BK, WE/BK, WE/RD, WE/RD, WE/BE, GN
    10 (Solid)5677655BK, RD, BE, BK/RD, RD/BK, WE, WE/BK, WE/RD, WE/BE, WE/PK, GN
    10 (Solid)6566546BK, BK/WE, BE, BE/WE, RD, RD/WE, WE/RD, WE/RD, WE/BE, WE/BE, WE/BK, WE/BK, GN
    12 (19)2566801BK, RD, GN, WE/BK, WE/RD
    12 (19)2551322BK, RD, GN, GN/YW, WE/BK, WE/RD
    12 (19)3562687BK, RD, BE, WE/BK, WE/RD, WE/BE, GN
    12 (19)3551324BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (19)2563822BK, RD, GN, WE/BK, WE/RD
    10 (19)2586636BK, RD, GN, GN/YW, WE/BK, WE/RD
    10 (19)3553238BK, RD, BE, WE, WE/BK, GN, WE/RD
    10 (19)3562456BK, RD, BE, GN, WE/BK, WE/RD, WE/BE
    10 (19)3551336BK, RD, BE, GN, GN/YW, WE/BK, WE/RD, WE/BE
    10 (19)4566698BK, BK/WE, RD, BE, GN, WE, WE/BK, WE/RD, WE/BE
    10 (19)8647335BK, BK, BK, BK, BK, BK, BK, BK, WE, WE, WE, WE, WE, WE, WE, WE, GN

    Revision: 1.000.027

    Updated On: Sept. 18, 2026, 2:33 p.m. UTC