SPEC 80213
35kV AL 100% TRXLPE One-Third (Based on Short Circuit) HI-DRI-PLUS® Renewable (Solar or Wind)
Moisture Blocked Aluminum Conductors. TRXLP Insulation. One-Third Concentric Neutrals. XLPE Jacket
Construction:
- Conductor:Moisture Blocked 1350 H16/H26 Aluminum, Class B Compressed or Compressed Unilay Stranded
- Strand Shield:Semi-conducting Crosslinked Polyethylene
- Insulation:Tree Retardant Crosslinked Polyethylene (TRXLP)
- Insulation Shield:Strippable Semi-conducting Crosslinked Polyethylene
- Concentric Neutral:Annealed Copper Wires Helically Applied One-Third Concentric Neutral
- Overall Jacket & Water Block:HI-DRI-PLUS® Water Swellable Powder Black Crosslinked Polyethylene (XLPE) with Red Extruded Stripes
Applications and Features:
- Predominately used for renewable projects with wind or solar applications.
- Suitable for use in wet or dry locations, direct burial, underground ducts, and exposure to direct sunlight.
- To be used at conductor temperature not to exceed 105ºC normal operation.
- UL listed MV-105
- The concentric neutral counts and sizes listed in Table 1 are based on the ICEA P-45-482 short circuit calculation of an MV-90 design. The short circuit value in Table 1 is calculated using a higher thermal limit of a crosslinked XLPE jacket MV-105 design.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE(R) HI-DRI-PLUS(R) (UL) XXX KCMIL AL 345 MILS TRXLPE TYPE MV-105 35KV 100% INSUL LEVEL -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | inch | mil | inch | No. x AWG | Ω/1000ft | mil | inch | lb/1000ft | inch | lb | |
TBA | 4/0 (19) | 0.512 | 1.240 | 345 | 1.350 | 11x14 | 0.239 | 50 | 1.578 | 1129 | 12.6 | 1269 |
662685 | 350 (37) | 0.661 | 1.391 | 345 | 1.501 | 14x14 | 0.187 | 75 | 1.783 | 1410 | 14.3 | 2100 |
629794 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 18x14 | 0.146 | 75 | 1.911 | 1705 | 15.3 | 3000 |
626328 | 500 (37) | 0.789 | 1.519 | 345 | 1.629 | 12x12 | 0.138 | 75 | 1.944 | 1764 | 15.6 | 3000 |
626338 | 750 (61) | 0.968 | 1.708 | 345 | 1.848 | 18x12 | 0.092 | 75 | 2.163 | 2326 | 17.3 | 4500 |
607594 | 1000 (61) | 1.084 | 1.857 | 345 | 1.997 | 23x12 | 0.072 | 75 | 2.312 | 2791 | 18.5 | 6000 |
607763 | 1250 (91) | 1.250 | 2.001 | 345 | 2.141 | 18x10 | 0.057 | 75 | 2.498 | 3342 | 20.0 | 7500 |
456402 | 1250 (61) | 1.250 | 2.001 | 345 | 2.141 | 19x10 | 0.054 | 75 | 2.498 | 3370 | 20 | 7500 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance | Positive Sequence Impedance | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | A/1000ft | W/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
4/0 (19) | 0.084 | 0.105 | 0.055 | 0.048 | 0.365 | 2.2 | 0.159 + j0.732 | 0.105 + j0.048 | 5690 | 235 | 285 |
350 (37) | 0.050 | 0.065 | 0.046 | 0.045 | 0.438 | 2.7 | 0.119 + j0.722 | 0.065 + j0.045 | 7242 | 315 | 370 |
500 (37) | 0.035 | 0.046 | 0.040 | 0.042 | 0.496 | 3.0 | 0.100 + j0.714 | 0.046 + j0.043 | 9311 | 380 | 445 |
500 (37) | 0.035 | 0.046 | 0.040 | 0.042 | 0.496 | 3.0 | 0.100 + j0.712 | 0.046 + j0.043 | 9862 | 380 | 445 |
750 (61) | 0.024 | 0.033 | 0.034 | 0.040 | 0.580 | 3.5 | 0.087 + j0.705 | 0.033 + j0.041 | 14794 | 470 | 530 |
1000 (61) | 0.018 | 0.026 | 0.033 | 0.039 | 0.608 | 3.7 | 0.080 + j0.700 | 0.026 + j0.039 | 18903 | 530 | 585 |
1250 (91) | 0.014 | 0.023 | 0.028 | 0.038 | 0.700 | 4.2 | 0.077 + j0.692 | 0.023 + j0.038 | 23516 | ||
1250 (61) | 0.014 | 0.023 | 0.030 | 0.037 | 0.66 | 4.03 | 0.077 + j0.693 | 0.023 + j0.038 | 24823 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Neutral DC Resistance 25°C | Jacket Thickness | Approx. OD | Approx. Weight | Min Bending Radius | Max Pull Tension |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | mm | mm | mm | No. x AWG | Ω/km | mm | mm | kg/km | mm | newton | |
TBA | 4/0 (19) | 13.00 | 31.50 | 8.76 | 34.29 | 11x14 | 0.78 | 1.27 | 40.08 | 1680 | 320.04 | 5647 |
662685 | 350 (37) | 16.79 | 35.33 | 8.76 | 38.13 | 14x14 | 0.61 | 1.91 | 45.29 | 2098 | 363.22 | 9345 |
629794 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 18x14 | 0.48 | 1.91 | 48.54 | 2537 | 388.62 | 13350 |
626328 | 500 (37) | 20.04 | 38.58 | 8.76 | 41.38 | 12x12 | 0.45 | 1.91 | 49.38 | 2625 | 396.24 | 13350 |
626338 | 750 (61) | 24.59 | 43.38 | 8.76 | 46.94 | 18x12 | 0.30 | 1.91 | 54.94 | 3461 | 439.42 | 20025 |
607594 | 1000 (61) | 27.53 | 47.17 | 8.76 | 50.72 | 23x12 | 0.24 | 1.91 | 58.72 | 4153 | 469.90 | 26700 |
607763 | 1250 (91) | 31.75 | 50.83 | 8.76 | 54.38 | 18x10 | 0.19 | 1.91 | 63.45 | 4973 | 508.00 | 33375 |
456402 | 1250 (61) | 31.75 | 50.83 | 8.76 | 54.38 | 19x10 | 0.18 | 1.91 | 63.45 | 5015 | 508.00 | 33375 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Pulling tension based on pulling eye directly connected to conductor
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Charging Current | Dielectric Loss | Zero Sequence Impedance* | Positive Sequence Impedance* | Short Circuit Current @ 30 Cycle | Allowable Ampacity in Duct 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/km | Ω/km | MΩ*km | Ω/km | A/km | W/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
4/0 (19) | 0.2756 | 0.34 | 0.0168 | 0.1575 | 1.198 | 7.2178 | 0.159 + j0.732 | 0.105 + j0.048 | 5690 | 235 | 285 |
350 (37) | 0.1640 | 0.21 | 0.0140 | 0.1476 | 1.437 | 8.8583 | 0.119 + j0.722 | 0.065 + j0.045 | 7242 | 315 | 370 |
500 (37) | 0.1148 | 0.15 | 0.0122 | 0.1378 | 1.627 | 9.8425 | 0.100 + j0.714 | 0.046 + j0.043 | 9311 | 380 | 445 |
500 (37) | 0.1148 | 0.15 | 0.0122 | 0.1378 | 1.627 | 9.8425 | 0.100 + j0.712 | 0.046 + j0.043 | 9862 | 380 | 445 |
750 (61) | 0.0787 | 0.11 | 0.0104 | 0.1312 | 1.903 | 11.4829 | 0.087 + j0.705 | 0.033 + j0.041 | 14794 | 470 | 530 |
1000 (61) | 0.0591 | 0.09 | 0.0101 | 0.1280 | 1.995 | 12.1391 | 0.080 + j0.700 | 0.026 + j0.039 | 18903 | 530 | 585 |
1250 (91) | 0.0459 | 0.08 | 0.0085 | 0.1247 | 2.297 | 13.7795 | 0.077 + j0.692 | 0.023 + j0.038 | 23516 | ||
1250 (61) | 0.0459 | 0.08 | 0.0091 | 0.1214 | 2.165 | 13.2218 | 0.077 + j0.693 | 0.023 + j0.038 | 24823 |
*Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
*Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
*Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
Revision: 1.000.019
Updated On: July 3, 2024, 10:13 p.m. UTC
Concentric Neutral Calculator