SPEC 25250

CU XLPE Type RPVU90 2000V

Single Copper Conductors, 1000V/2000V, 90°C MAX - 40°C MIN, Sunlight Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE)

Applications and Features:

Single copper conductor with low temperature, moisture resisting XLPE (cross linked polyethylene) insulation. Sunlight Resistant. This product meets the current RoHS requirements. No lead is added or used in manufacturing.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • RoHS Compliant Lead-Free, Silicone-Free
  • CSA Standard C22.2 No. 271 Photovoltaic Cables
  • Sample Print Legend:

    SOUTHWIRE LL90458 {CSA} AWG XX (XX.X{mm2}) CU XLPE RPVU90 1000V/2000V -40°C SR DIRECT BURIAL --- {MM/DD/YYYY} --- RoHS {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA147600.190240.7332.6313.1700.05825
    TBA127600.208340.8521.6622.0020.05430
    5836701019600.233460.9831.0401.2530.05040
    584430!1019600.233460.9831.0401.2530.05040
    TBA87800.301781.21320.6530.7860.05255
    585502^819800.316781.21320.6530.7860.05255
    TBA67800.3371141.32090.4110.4950.05175
    TBA47800.3851671.53330.2580.3100.04895
    TBA27800.4422511.75300.1620.1950.045130
    TBA119950.5123222.06690.1280.1540.046145
    TBA1/019950.5513952.28440.1020.1220.044170
    TBA2/019950.5954872.310640.0810.0970.043195
    TBA3/019950.6466032.513420.0640.0780.042225
    TBA4/019950.7027472.816920.0510.0620.041260
    TBA250371100.7788913.120000.0430.0530.041290
    TBA350371100.88112193.528000.0310.0390.040350
    TBA500371101.00917055.040000.0220.0290.039430
    TBA600611251.11520555.548000.0180.0250.039475
    TBA750611251.21825396.060000.0140.0220.038535
    TBA1000611251.36733426.880000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities based on 2017 NEC Table 310.15(B)(16): Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
    ! Bunch unilay 19 strand tinned copper
    ^ Combination Unilay per ASTM B787
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA1471.524.833617.781478.6310.400.190325
    TBA1271.525.285120.322315.456.570.177230
    58367010191.525.926822.863693.414.110.164040
    584430!10191.525.926822.863693.414.110.164040
    TBA872.037.6511630.485872.142.580.170655
    585502^8192.038.0311630.485872.142.580.170655
    TBA672.038.5617033.029301.351.620.167375
    TBA472.039.7824938.1014820.851.020.157595
    TBA272.0311.2337443.1823590.530.640.1476130
    TBA1192.4113.0047950.8029770.420.510.1509145
    TBA1/0192.4114.0058855.8837560.330.400.1444170
    TBA2/0192.4115.1172558.4247350.270.320.1411195
    TBA3/0192.4116.4189763.5059720.210.260.1378225
    TBA4/0192.4117.83111271.1275290.170.200.1345260
    TBA250372.7919.76132678.7489000.140.170.1345290
    TBA350372.7922.38181488.90124600.100.130.1312350
    TBA500372.7925.632537127.00178000.070.100.1280430
    TBA600613.1828.323058139.70213600.060.080.1280475
    TBA750613.1830.943778152.40267000.050.070.1247535
    TBA1000613.1834.724973172.72356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Ampacities based on 2017 NEC Table 310.15(B)(16): Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
    ! Bunch unilay 19 strand tinned copper
    ^ Combination Unilay per ASTM B787
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Stock Code and Color (other than Black)

    Stock CodeSize AWGColor
    58367110Red

    Revision: 1.000.002

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC