SPEC 87010

Cable-in-Conduit (CIC) CU 600V THHN SCH 40

...

Construction:

• Conductors: Copper SIMpull THHN/THWN-2® per SPEC 10000
• Conduit: High-Density Polyethylene (HDPE)

Applications and Features:

Southwire’s SIMpull® CIC has been utilized by end users in various applications, including the US Department of Transportation (DOT), the US Department of Energy (DOE), commercial constructions, EV infrastructure expansions, Utility grid-hardening efforts, airports, mass transit, renewables, petrochemical, agriculture, and data centers. Manufactured by continuously extruding HDPE loosely around the cable assembly with no adhesion between the conduit and the cable, thus leaving the cables free in the conduit. Lubrication is applied to the cable, allowing for cables to be pulled out and replaced if necessary.

Specifications:

  • ASTM D3350 Standard Specification for Polyethylene Plastics Pipe and Fittings Materials
  • ASTM D3485 Standard Specification for Coilable High Density Polyethylene (HDPE) Cable in Conduit (CIC)
  • ASTM F2160 Standard Specification for Solid Wall High Density Polyethylene (HDPE) Conduit Based on Controlled Outside Diameter (OD)
  • UL 1990 Standard for Nonmetallic Underground Conduit with Conductors
  • CSA CSA marking is available upon request
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • NEMA TC-7 Smooth-Wall Coilable Electrical Polyethylene Conduit
  • Sample Print Legend:

    {SQFTG} FEET (LOGO) SOUTHWIRE CABLE IN CONDUIT (UL) HDPE X" SCH40 NEMA TC 7 / ASTM F2160 (NESC) {MMM/DD/YYYY} {MACH/SHFT/OP}
    Table 1 – Physical and Electrical Data
    Stock NumberDescriptionCable ColorDuct Nominal SizeDuct Nominal Outside Dia.Duct Min. Wall ThicknessDuct Nominal Inside Dia.Duct Min. Bending RadiusDuct Max. Pull TensionDuct ColorApprox. Cable and Duct Weight
    inchinchinchinchinchlblb/1000ft
    63237410X3 (BK/WE/GN) CU THHN 3/4" SCH40 BLACK HDPE CICBK, WE, GN0.751.0500.1130.80412710BK305
    63126310X4 (BK/WE/RD/GN) CU THHN 3/4" SCH40 BLACK HDPE CICBK, WE, RD GN0.751.0500.1130.80412710BK305
    63237510X4 (BN/OE/YW/GN) CU THHN 3/4" SCH40 BLACK HDPE CICBN, OE, YW, GY0.751.0500.1130.80412710BK305
    63238710X5 (BN/OE/YW/GY/GN) CU THHN 3/4" SCH40 BLACK HDPE CICBN, OE, YW, GY, GN0.751.0500.1130.80412710BK345
    6323628X4 (BN/OE/YW/GN) CU THHN 1" SCH40 BLACK HDPE CICBN, OE, YW, GN1.001.3150.1331.029141050BK475
    6325456X4 (BN/OE/YW/GN) CU THHN 1" SCH40 BLACK HDPE CICBN, OE, YW, GN1.001.3150.1331.029141050BK607
    6334714X4 (BN/OE/YW/GN) CU THHN 1-1/4" SCH40 BLACK HDPE CICBN, OE, YW, GN1.251.6600.1401.360181420BK917
    6344491/0X4 (BN/OE/YW/GY) 2 (GN) 3E AL THHN 1-1/2" SCH40 BLACK HDPE CICBN, OE, YW, GY1.501.9000.1451.590211700RD1029
    6346002X4 (BN/OE/YW/GY) 4 (GN) CU THHN 2-1/2" SCH40 BLACK HDPE CICBN, OE, YW, GY, GN2.502.8750.2032.445323615BK1855
    6345983/0X4 (BN/OE/YW/GY) 4 (GN) CU THHN 2-1/2" SCH40 BLACK HDPE CICBN, OE, YW, GY, GN2.502.8750.2032.445323615BK3240
    6345991X4 (BN/OE/YW/GY) 4 (GN) CU THHN 2-1/2" SCH40 BLACK HDPE CICBN, OE, YW, GY, GN2.502.8750.2032.445323615BK2120
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Cell Classification for HDPE Conduit

    PropertyTest MethodValue
    DensityD48830.953 g/cc
    Melt IndexD12380.25 g/10 min
    Flexural ModulusD790168,000 psi
    Tensile StrengthD6383900 yield @ 2 in/min
    SP-NCLS ESCRF2136>1000 hrs
    Hydrostatic Design BasisD2837N/A

  • (PE436580C-BK), (PE436580E-Colors)
  • Revision: 1.000.016

    Updated On: Feb. 8, 2025, 2:35 p.m. UTC

    CIC Labor Saving Calculator
    QR Code