SPEC 46321
CU Compact 15kV NLEPR Insulation 100% IL Black SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Compact Copper, 175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% Insulation Level, Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA
Construction:
- Conductor:Class B compact stranded per ASTM B496
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:175 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% Insulation Level,
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE SIMpull® POWER CABLE {UL} XXX KCMIL CPT CU 175 MILS NL-EPR 15KV 100% INS LEVEL 25%TS MV-105 SUN. RES. {NESC} PAT www.patentSW.com
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb/1000ft | lb | inch | inch | |
TBA | 2 | 7 | 0.268 | 0.656 | 0.716 | 80 | 0.896 | 219 | 526 | 530 | 10.7 | 2.5 |
TBA | 1 | 19 | 0.298 | 0.686 | 0.746 | 80 | 0.926 | 273 | 596 | 669 | 11.1 | 3.0 |
TBA | 1/0 | 19 | 0.336 | 0.724 | 0.784 | 80 | 0.964 | 341 | 684 | 844 | 11.5 | 3.0 |
TBA | 2/0 | 19 | 0.376 | 0.764 | 0.824 | 80 | 1.004 | 427 | 791 | 1064 | 12.0 | 3.0 |
TBA | 3/0 | 19 | 0.422 | 0.810 | 0.870 | 80 | 1.050 | 535 | 922 | 1342 | 12.6 | 3.0 |
TBA | 4/0 | 19 | 0.474 | 0.862 | 0.922 | 80 | 1.102 | 671 | 1085 | 1692 | 13.2 | 3.5 |
TBA | 250 | 37 | 0.520 | 0.916 | 0.976 | 80 | 1.156 | 791 | 1237 | 2000 | 13.8 | 3.5 |
TBA | 350 | 37 | 0.615 | 1.011 | 1.071 | 80 | 1.251 | 1101 | 1597 | 2800 | 15.0 | 3.5 |
583511 | 500 | 35 | 0.735 | 1.162 | 1.222 | 80 | 1.402 | 1641 | 2206 | 4000 | 16.8 | 4.0 |
TBA | 750 | 61 | 0.908 | 1.314 | 1.374 | 80 | 1.554 | 2343 | 3007 | 6000 | 18.6 | 4.5 |
TBA | 1000 | 61 | 1.060 | 1.466 | 1.526 | 110 | 1.766 | 3116 | 3964 | 8000 | 21.1 | 5.0 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 0.162 | 0.204 | 0.046 | 0.049 | 0.574 + j0.464 | 0.204 + j0.049 | 2249 | 155/165 | 195/215 |
1 | 0.128 | 0.162 | 0.043 | 0.048 | 0.533 + j0.447 | 0.162 + j0.046 | 2342 | 175/185 | 225/250 |
1/0 | 0.102 | 0.128 | 0.040 | 0.046 | 0.499 + j0.428 | 0.128 + j0.044 | 2459 | 200/215 | 260/290 |
2/0 | 0.081 | 0.102 | 0.036 | 0.044 | 0.472 + j0.410 | 0.102 + j0.043 | 2584 | 230/245 | 300/335 |
3/0 | 0.064 | 0.081 | 0.033 | 0.043 | 0.450 + j0.390 | 0.081 + j0.041 | 2726 | 260/275 | 345/385 |
4/0 | 0.051 | 0.065 | 0.031 | 0.041 | 0.432 + j0.368 | 0.066 + j0.040 | 2887 | 295/315 | 400/445 |
250 | 0.043 | 0.056 | 0.029 | 0.040 | 0.420+ j0.348 | 0.057 + j0.039 | 3054 | 325/345 | 445/495 |
350 | 0.031 | 0.041 | 0.025 | 0.038 | 0.398 + j0.316 | 0.042 + j0.036 | 3349 | 390/415 | 550/610 |
500 | 0.022 | 0.030 | 0.022 | 0.036 | 0.377 + j0.28 | 0.031 + j0.035 | 3721 | 465/500 | 685/765 |
750 | 0.014 | 0.023 | 0.019 | 0.034 | 0.352 + j0.236 | 0.024 + j0.033 | 4288 | 565/610 | 885/990 |
1000 | 0.011 | 0.019 | 0.016 | 0.033 | 0.333 + j0.207 | 0.02 + j0.032 | 4758 | 640/690 | 1060/1185 |
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.
Revision: 1.000.002
Updated On: July 3, 2024, 10:13 p.m. UTC