SPEC 85010

Multi-Conductor CU 600 V FR-XLPE Thermoplastic CPE-TP Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE XHHW-2 TYPE TC CDRS 90C CPE JKT 600V SUNLIGHT RESISTANT MM/YYYY{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    67314016270.05625450.30816484.1815.0370.0331.2-18Black
    61926116470.05625450.35432754.1815.0370.0331.4-14Black
    60431016770.05625450.429561204.1815.0370.0331.7-12Black
    61926316870.05625450.449641324.1815.0370.0331.7-12Black
    14 AWG
    60421014270.07030450.35725642.6313.1700.0581.42025Black
    619930141270.07030600.6631532912.6313.1700.0582.61012Black
    12 AWG
    60421112270.08830450.40440891.6622.0020.0541.62530Black
    606672^12270.08830450.40440891.6622.0020.0541.62530Black
    616890^12470.08830450.445811411.6622.0020.0541.72024Black
    60421212470.08830450.463811491.6622.0020.0541.92024Black
    61930812770.08830600.5611422461.6622.0020.0542.21721Black
    61993712770.08830600.5691422511.6622.0020.0542.21721Black
    61993912970.08830600.6551833111.6622.0020.0542.61721Black
    618414121270.08830600.7322444021.6622.0020.0542.91215Black
    10 AWG
    61994310270.11330450.440641181.0401.2530.0501.73540Black
    606671^10270.11330450.452641311.0401.2530.0501.83540Black
    61836010370.11330450.459971651.0401.2530.0501.83540Black
    61994510470.11330450.5061292031.0401.2530.0502.02832Black
    61924010470.11330450.5061292021.0401.2530.0502.02832Black
    60421910770.11330600.6372263491.0401.2530.0502.52428Black
    61995010970.11330600.7452914431.0401.2530.0502.92428Black
    622897101270.11330800.8753886071.0401.2530.0503.51720Black
    604301$102190.11730450.440641171.0401.2530.0501.73540Black
    604302$104190.11730450.5151292041.0401.2530.0502.02832Black
    604304$1012190.11730800.8873886081.0401.2530.0503.51720Black
    8 AWG
    6042248270.14145600.5881022010.6530.7860.0522.35055Black
    6042998470.14145600.7002063630.6530.7860.0522.84044Black
    6643538670.14145800.8833095420.6530.7860.0523.54044Black
    6 AWG
    6042966270.17745600.6641632800.4110.4950.0512.66575Black
    618351!6370.17745600.6982453900.4110.4950.0512.76575Black
    6042976370.17745600.7062453900.4110.4950.0512.86575Black
    6192386270.17745600.7121633000.4110.4950.0512.86575Black
    6199596470.17745600.7873275060.4110.4950.0513.15260Black
    4 AWG
    6066044270.22545600.7502604080.2580.3100.0483.08595Black
    606674^4270.22545600.7732604130.2580.3100.0483.18595Black
    2 AWG
    6042942270.37745800.9264146220.1620.2110.0283.7115130Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    & 19 strand Class C compressed conductor per ASTM B8
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.004

    Updated On: Dec. 31, 2024, 11:09 p.m. UTC