SPEC 46319

CU Compact 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Type MV-105 Single Conductor Compact Copper, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

...

Construction:

  1. Conductor:Class B compact stranded per ASTM B496
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B496 Compact Round Concentric-lay-standard copper
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE SIMpull® POWER CABLE {UL} XXX AWG CPT CU 220 MILS NL-EPR 15KV 133% INS LEVEL 25%TS MV-105 FOR CT USE SUN. RES. {NESC} PAT www.patentSW.com
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorDiameter Over InsulationDiameter Over Insulation ShieldJacket ThicknessApprox. ODCopper WeightApprox. WeightMax Pull TensionMin Bending RadiusConduit Size
    AWG/KcmilNo. of Strandsinchinchinchmilinchlb/1000ftlb/1000ftlbinchinch
    TBA270.2680.7460.806800.98622159853011.83.0
    TBA1190.2980.7760.836801.01627567066912.13.0
    6472031/0190.3360.8140.874801.05439780084412.63.0
    TBA2/0190.3760.8540.914801.094429871106413.13.0
    TBA3/0190.4220.9000.960801.1405371004134213.63.5
    6409214/0190.4740.9531.013801.1935281012169214.33.5
    TBA250370.5201.0061.066801.2467931329200014.93.5
    647207350350.6151.1021.162801.34211721747280016.14.0
    553998500350.7351.2301.290801.47016462301400017.64.5
    TBA600610.8121.3081.368801.54818772600480018.54.5
    561603750610.9081.4041.495801.73524333331600020.85.0
    TBA1000611.0601.5561.6161101.85631184101800022.25.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedanceShield Short Circuit Current 6 CyclesAllowable Ampacity In Duct 90/105°CAllowable Ampacity In Air 90/105°C
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    20.1620.2040.0530.0520.575 + j0.4260.204 + j0.0512528155/165195/215
    10.1280.1620.0490.0500.532 + j0.4100.162 + j0.0482621175/185225/250
    1/00.1020.1280.0460.0480.497 + j0.3930.128 + j0.0472738200/215260/290
    2/00.0810.1020.0420.0460.469 + j0.3760.103 + j0.0452862230/245300/335
    3/00.0640.0810.0390.0440.446 + j0.3580.082 + j0.0433005260/275345/385
    4/00.0510.0650.0360.0430.426 + j0.3390.066 + j0.0413166295/315400/445
    2500.0430.0560.0340.0420.413 + j0.3210.057 + j0.0403333325/345445/495
    3500.0310.0410.0300.0400.391 + j0.2920.042 + j0.0383628390/415550/610
    5000.0220.0300.0260.0370.368 + j0.2600.031 + j0.0363999465/500685/765
    6000.0180.0260.0240.0370.356 + j0.2390.027 + j0.0344269505/544765/855
    7500.0140.0230.0220.0350.343 + j0.2200.024 + j0.0344566565/610885/990
    10000.0110.0190.0200.0350.324 + j0.1940.02 + j0.0335037640/6901060/1185
    * NEC ampacities are based on:
    * For Duct: Table 310.60(C)(11) Detail 1.
    * For Free Air: Table 310.60(C)(3).
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
    * Capacitive Reactance is between Phase-to-Shield.

    Revision: 1.000.003

    Updated On: July 3, 2024, 10:13 p.m. UTC