SPEC 46313
AL Compact 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. 2x5 mils Tape Shield - MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial
Type MV-105 Single Conductor Aluminum, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, 2x5 Mils Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA
![...](https://d3sx0rvep9h73z.cloudfront.net/cable_image/SPEC46313.png)
Construction:
- Conductor:Class B compact stranded TRIPLE E Aluminum Alloy (AA-8176) per ASTM B801 and B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 2x5 mil copper tape with 25% overlap
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. ST1 (low smoke) Rated for sizes 1/0 and larger. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. 2x5 mils tape shield for higher short circuit withstand.
Specifications:
Sample Print Legend:
SOUTHWIRE [SYMBOL - LIGHTING BOLT] #P# (UL/CSA) 1/C [#AWG or #kcmil] AL 220 MILS NL-EPR 15KV 133% INS LEVEL 25% TS MV-105 FOR CT USE SUN. RES. TC-ER(CSA 1/0 LARGER) FOR DIRECT BURIAL FT4 -ST1 YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Diameter Over Insulation | Diameter Over Insulation Shield | Jacket Thickness | Approx. OD | Copper Weight | Aluminum Weight | Approx. Weight | Max Pull Tension | Min Bending Radius | Conduit Size |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | inch | inch | mil | inch | lb/1000ft | lb/1000ft | lb/1000ft | lb | inch | inch | |
TBA | 2 | 7 | 0.268 | 0.746 | 0.806 | 80 | 0.986 | 16 | 62 | 455 | 398 | 11.8 | 3.0 |
TBA | 1 | 19 | 0.298 | 0.776 | 0.836 | 80 | 1.016 | 16 | 78 | 489 | 502 | 12.1 | 3.0 |
TBA | 1/0 | 19 | 0.336 | 0.814 | 0.874 | 80 | 1.054 | 17 | 99 | 534 | 633 | 12.6 | 3.0 |
TBA | 2/0 | 19 | 0.376 | 0.854 | 0.914 | 80 | 1.094 | 18 | 125 | 585 | 798 | 13.1 | 3.0 |
TBA | 3/0 | 19 | 0.422 | 0.900 | 0.960 | 80 | 1.140 | 19 | 158 | 644 | 1006 | 13.6 | 3.5 |
TBA | 4/0 | 19 | 0.474 | 0.952 | 1.012 | 80 | 1.192 | 20 | 199 | 718 | 1269 | 14.3 | 3.5 |
589002 | 250 | 22 | 0.520 | 1.006 | 1.066 | 80 | 1.266 | 173 | 235 | 930 | 1500 | 15.1 | 3.5 |
TBA | 350 | 35 | 0.615 | 1.101 | 1.161 | 80 | 1.341 | 23 | 329 | 944 | 2100 | 16.0 | 4.0 |
640814 | 500 | 34 | 0.735 | 1.244 | 1.304 | 80 | 1.504 | 208 | 471 | 1341 | 3000 | 18.0 | 4.5 |
TBA | 600 | 58 | 0.812 | 1.308 | 1.368 | 80 | 1.548 | 27 | 565 | 1315 | 3600 | 18.5 | 4.5 |
589001 | 750 | 58 | 0.908 | 1.426 | 1.486 | 80 | 1.746 | 235 | 706 | 1821 | 4500 | 20.9 | 5.0 |
585564 | 1000 | 61 | 1.060 | 1.568 | 1.628 | 110 | 1.888 | 256 | 942 | 2161 | 6000 | 22.6 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90/105°C | Allowable Ampacity In Air 90/105°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 0.267 | 0.336 | 0.053 | 0.052 | 0.707 + j0.426 | 0.336 + j0.051 | 2528 | 120/130 | 150/170 |
1 | 0.211 | 0.266 | 0.049 | 0.050 | 0.636 + j0.41 | 0.266 + j0.048 | 2621 | 135/145 | 175/195 |
1/0 | 0.168 | 0.211 | 0.046 | 0.048 | 0.58 + j0.393 | 0.211 + j0.047 | 2738 | 155/165 | 200/225 |
2/0 | 0.133 | 0.167 | 0.042 | 0.046 | 0.534 + j0.376 | 0.168 + j0.045 | 2862 | 175/190 | 235/260 |
3/0 | 0.105 | 0.133 | 0.039 | 0.044 | 0.498 + j0.358 | 0.134 + j0.043 | 3005 | 200/215 | 270/300 |
4/0 | 0.084 | 0.105 | 0.036 | 0.043 | 0.466 + j0.339 | 0.106 + j0.041 | 3166 | 230/245 | 310/350 |
250 | 0.071 | 0.090 | 0.034 | 0.042 | 0.447 + j0.321 | 0.091 + j0.04 | 3333 | 250/270 | 345/385 |
350 | 0.050 | 0.065 | 0.030 | 0.040 | 0.415 + j0.292 | 0.066 + j0.038 | 3628 | 305/330 | 430/480 |
500 | 0.035 | 0.046 | 0.026 | 0.037 | 0.384 + j0.26 | 0.047 + j0.036 | 3999 | 370/400 | 535/600 |
600 | 0.029 | 0.039 | 0.024 | 0.037 | 0.369 + j0.239 | 0.04 + j0.034 | 4269 | 404/436 | 601/672 |
750 | 0.024 | 0.033 | 0.022 | 0.035 | 0.353 + j0.22 | 0.034 + j0.034 | 4566 | 455/490 | 700/780 |
1000 | 0.018 | 0.026 | 0.020 | 0.035 | 0.331 + j0.194 | 0.027 + j0.033 | 5037 | 525/565 | 840/940 |
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.
Revision: 1.000.000
Updated On: July 3, 2024, 10:13 p.m. UTC