SPEC 26421

HVTECK AL 1/C 260NLEPR TS PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 260 NLEPR AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchinchmilinchlb/1000ftlb/1000ftinch
    1190.2990.8572600.917801.0971.307501.407769763.5
    1/0190.3360.8942600.954801.1341.344501.4447910353.5
    2/0190.3760.9342600.994801.1741.384501.4848211044
    3/0190.4230.9812601.041801.2211.431501.5318611864
    4/0190.4751.0332601.093801.2731.583601.7039014564.5
    250370.521.0862601.146801.3261.636601.7569415584.5
    350370.6161.1822601.242801.4221.732601.85210217645
    500370.7361.3022601.362801.5421.852601.97211220465
    750610.9081.4842601.5441101.7842.094602.21412726196
    1000611.1171.6932601.7531101.9932.303752.45314431766.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    19.85020.2110.2890.0490.0570.644+j0.4220.290+j0.0612872193194
    1/010.16330.1670.2290.0450.0550.584+j0.4080.230+j0.0592987221219
    2/010.47980.1330.1820.0420.0530.536+j0.3920.183+j0.0573111253246
    3/010.710060.1050.1440.0390.0510.497+j0.3760.145+j0.0553256288275
    4/011.912690.0840.1150.0370.0510.465+j0.3580.116+j0.0553418327305
    25012.315000.070.0960.0340.050.444+j0.3420.097+j0.0533582367343
    3501321000.0510.070.030.0470.413+j0.3140.071+j0.0513879443399
    50013.830000.0360.050.0270.0440.385+j0.2840.051+j0.0484251529451
    75015.545000.0230.0330.0230.0420.355+j0.2450.035+j0.0464815633505
    100017.260000.0170.0250.0190.040.330+j0.2110.027+j0.0455462711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmmmkg/kmkg/kminch
    1197.5921.776.6023.292.0327.8633.201.2735.7411314523.5
    1/0198.5322.716.6024.232.0328.8034.141.2736.6811815403.5
    2/0199.5523.726.6025.252.0329.8235.151.2737.6912216434
    3/01910.7424.926.6026.442.0331.0136.351.2738.8912817654
    4/01912.0726.246.6027.762.0332.3340.211.5243.2613421674.5
    2503713.2127.586.6029.112.0333.6841.551.5244.6014023194.5
    3503715.6530.026.6031.552.0336.1243.991.5247.0415226255
    5003718.6933.076.6034.592.0339.1747.041.5250.0916730455
    7506123.0637.696.6039.222.7945.3153.191.5256.2418938986
    10006128.3743.006.6044.532.7950.6258.501.9162.3121447266.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1248.9222340.69230.950.01490.18700.644+j0.4220.290+j0.0612872193194
    1/0256.5428170.54790.750.01370.18040.584+j0.4080.230+j0.0592987221219
    2/0264.1635510.43640.600.01280.17390.536+j0.3920.183+j0.0573111253246
    3/0271.7844770.34450.470.01190.16730.497+j0.3760.145+j0.0553256288275
    4/0302.2656470.27560.380.01130.16730.465+j0.3580.116+j0.0553418327305
    250312.4266750.22970.310.01040.16400.444+j0.3420.097+j0.0533582367343
    350330.2093450.16730.230.00910.15420.413+j0.3140.071+j0.0513879443399
    500350.52133500.11810.160.00820.14440.385+j0.2840.051+j0.0484251529451
    750393.70200250.07550.110.00700.13780.355+j0.2450.035+j0.0464815633505
    1000436.88267000.05580.080.00580.13120.330+j0.2110.027+j0.0455462711544
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC