SPEC 26232

HVTECK AL 1/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA

Single Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2680.5861400.646650.7961.006501.106536153
    TBA1190.2990.6171400.677650.8271.037501.137566563
    TBA1/0190.3360.6541400.714800.8941.104501.204597383
    TBA2/0190.3760.6941400.754800.9341.144501.244627983
    TBA3/0190.4230.7411400.801800.9811.191501.291668703.5
    TBA4/0190.4750.7931400.853801.0331.243501.343709553.5
    TBA250370.520.8461400.906801.0861.296501.3967510393.5
    TBA350370.6160.9421401.002801.1821.392501.4928212154
    672085500340.7361.0861401.146801.3261.658601.7789414874.5
    TBA750610.9081.2441401.304801.4841.794601.91410720555
    TBA1000611.1171.4531401.5131101.7532.063602.18312426065.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    27.73980.2660.3650.0440.0540.705+j0.5280.366+j0.0592033169176
    185020.2110.2890.0410.0520.633+j0.5120.290+j0.0562129194198
    1/08.46330.1670.2290.0380.0510.576+j0.4940.230+j0.0552243222223
    2/08.77980.1330.1820.0350.0490.532+j0.4750.183+j0.0532367255250
    3/0910060.1050.1440.0320.0470.496+j0.4550.145+j0.0512513290278
    4/09.412690.0840.1150.030.0460.469+j0.4340.116+j0.0492674329309
    2509.815000.070.0960.0270.0440.451+j0.4130.097+j0.0482838370347
    35010.421000.0510.070.0240.0420.424+j0.3790.071+j0.0463136446402
    50012.430000.0360.050.0220.0420.398+j0.3340.051+j0.0463582533451
    75013.445000.0230.0330.0170.0390.372+j0.2910.034+j0.0434071631500
    100015.360000.0170.0250.0150.0370.349+j0.2470.027+j0.0424719707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA276.8114.883.5616.411.6520.2225.551.2728.09799153
    TBA1197.5915.673.5617.201.6521.0126.341.2728.88839763
    TBA1/0198.5316.613.5618.142.0322.7128.041.2730.588810983
    TBA2/0199.5517.633.5619.152.0323.7229.061.2731.609211883
    TBA3/01910.7418.823.5620.352.0324.9230.251.2732.799812953.5
    TBA4/01912.0720.143.5621.672.0326.2431.571.2734.1110414213.5
    TBA2503713.2121.493.5623.012.0327.5832.921.2735.4611215463.5
    TBA3503715.6523.933.5625.452.0330.0235.361.2737.9012218084
    6720855003418.6927.583.5629.112.0333.6842.111.5245.1614022134.5
    TBA7506123.0631.603.5633.122.0337.6945.571.5248.6215930585
    TBA10006128.3736.913.5638.432.7944.5352.401.5255.4518538785.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2195.5817710.87271.200.01340.17720.705+j0.5280.366+j0.0592033169176
    1203.2022340.69230.950.01250.17060.633+j0.5120.290+j0.0562129194198
    1/0213.3628170.54790.750.01160.16730.576+j0.4940.230+j0.0552243222223
    2/0220.9835510.43640.600.01070.16080.532+j0.4750.183+j0.0532367255250
    3/0228.6044770.34450.470.00980.15420.496+j0.4550.145+j0.0512513290278
    4/0238.7656470.27560.380.00910.15090.469+j0.4340.116+j0.0492674329309
    250248.9266750.22970.310.00820.14440.451+j0.4130.097+j0.0482838370347
    350264.1693450.16730.230.00730.13780.424+j0.3790.071+j0.0463136446402
    500314.96133500.11810.160.00670.13780.398+j0.3340.051+j0.0463582533451
    750340.36200250.07550.110.00520.12800.372+j0.2910.034+j0.0434071631500
    1000388.62267000.05580.080.00460.12140.349+j0.2470.027+j0.0424719707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000