SPEC 45268
AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® {UL} 3/0 AWG AL 4 CDRS TYPE TC-ER THHN OR THWN-2 CDRS AL GW 1 X 4 AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {YYYY}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| TBA | 8 | 4 | 7 | 0.134 | 35 | 1 x 8 | 60 | 0.616 | 77 | 182 | Black |
| TBA | 6 | 4 | 7 | 0.169 | 35 | 1 x 8 | 60 | 0.700 | 114 | 237 | Black |
| TBA | 4 | 4 | 7 | 0.212 | 50 | 1 x 6 | 80 | 0.917 | 182 | 400 | Black |
| TBA | 2 | 4 | 7 | 0.268 | 50 | 1 x 6 | 80 | 1.053 | 276 | 534 | Black |
| TBA | 1 | 4 | 19 | 0.298 | 60 | 1 x 4 | 80 | 1.174 | 356 | 670 | Black |
| TBA | 1/0 | 4 | 19 | 0.336 | 60 | 1 x 4 | 80 | 1.266 | 439 | 783 | Black |
| 675633 | 2/0 | 4 | 12 | 0.376 | 50 | 1 x 4 | 80 | 1.342 | 546 | 1064 | Black |
| 675635 | 3/0 | 4 | 15 | 0.422 | 50 | 1 x 4 | 80 | 1.456 | 678 | 1236 | Black |
| TBA | 4/0 | 4 | 19 | 0.474 | 60 | 1 x 2 | 80 | 1.599 | 864 | 1314 | Black |
| TBA | 250 | 4 | 37 | 0.520 | 70 | 1 x 2 | 110 | 1.819 | 1009 | 1651 | Black |
| 599228 | 300 | 4 | 21 | 0.569 | 60 | 1 x 4 | 110 | 1.924 | 1141 | 2113 | Black |
| TBA | 350 | 4 | 37 | 0.615 | 70 | 1 x 2 | 110 | 2.049 | 1388 | 2124 | Black |
| 668451 | 500 | 4 | 34 | 0.735 | 60 | 1 x 1 | 115 | 2.351 | 1982 | 3123 | Black |
| 597539 | 500 | 4 | 35 | 0.735 | 60 | 1 x 2/0 | 110 | 2.415 | 2029 | 3177 | Black |
| 673261 | 600 | 4 | 35 | 0.813 | 80 | 1 x 3/0 | 110 | 2.545 | 2029 | 3717 | Black |
| TBA | 750 | 4 | 61 | 0.908 | 80 | 1 x 1/0 | 140 | 2.867 | 2946 | 4218 | Black |
| 597540 | 750 | 4 | 58 | 0.908 | 70 | 1 x 3/0 | 140 | 2.925 | 3014 | 4687 | Black |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 8 | 4 | 2.5 | 316 | 1.072 | 1.290 | 0.052 | 32 | 36 |
| TBA | 6 | 4 | 2.8 | 503 | 0.674 | 0.812 | 0.051 | 40 | 44 |
| TBA | 4 | 4 | 3.7 | 801 | 0.424 | 0.510 | 0.048 | 52 | 60 |
| TBA | 2 | 4 | 5.3 | 1274 | 0.267 | 0.321 | 0.045 | 72 | 80 |
| TBA | 1 | 4 | 5.9 | 1606 | 0.211 | 0.254 | 0.046 | 80 | 92 |
| TBA | 1/0 | 4 | 6.3 | 2027 | 0.168 | 0.201 | 0.044 | 96 | 108 |
| 675633 | 2/0 | 4 | 6.7 | 2555 | 0.133 | 0.160 | 0.043 | 108 | 120 |
| 675635 | 3/0 | 4 | 7.3 | 3221 | 0.105 | 0.126 | 0.042 | 124 | 140 |
| TBA | 4/0 | 4 | 8.0 | 4062 | 0.084 | 0.100 | 0.041 | 144 | 164 |
| TBA | 250 | 4 | 9.1 | 4800 | 0.071 | 0.086 | 0.041 | 164 | 184 |
| 599228 | 300 | 4 | 9.6 | 5760 | 0.059 | 0.071 | 0.041 | 184 | 208 |
| TBA | 350 | 4 | 12.3 | 6720 | 0.050 | 0.062 | 0.040 | 200 | 224 |
| 668451 | 500 | 4 | 14.1 | 9600 | 0.035 | 0.044 | 0.039 | 248 | 280 |
| 597539 | 500 | 4 | 14.5 | 9600 | 0.035 | 0.044 | 0.039 | 248 | 280 |
| 673261 | 600 | 4 | 15.7 | 14400 | 0.029 | 0.037 | 0.039 | 272 | 308 |
| TBA | 750 | 4 | 17.2 | 18000 | 0.024 | 0.031 | 0.038 | 308 | 348 |
| 597540 | 750 | 4 | 17.6 | 18000 | 0.024 | 0.031 | 0.038 | 308 | 348 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.005
Updated On: June 25, 2025, 3:57 p.m. UTC


